Professional Documents
Culture Documents
Valve Position Measurements: Configuration and Verification Manual
Valve Position Measurements: Configuration and Verification Manual
Valve Position Measurements: Configuration and Verification Manual
Part Number
288622-01
Rev.
NC (01/12)
Valve Position Configuration and Verification Manual
* Denotes a trademark of Bently Nevada, Inc., a wholly owned subsidiary of General Electric
Company.
Proximitor, Keyphasor
Contact Information
The following contact information is provided for those times when
you cannot contact your local representative:
Mailing Address 1631 Bently Parkway South
Minden, Nevada USA 89423
USA
Telephone 1.775.782.3611
1.800.227.5514
Fax 1.775.215.2873
Internet www.ge-mcs.com/bently
ii
Additional Information
NOTE
This manual does not contain all the information required to operate and
maintain the monitoring system. Refer to the following manuals for other
required information.
Customers and third parties, who are not member states of the European Union, who are in
control of the product at the end of its life or at the end of its use, are solely responsible for
the proper disposal of the product. No person, firm, corporation, association or agency that
is in control of product shall dispose of it in a manner that is in violation of any applicable
federal, state, local or international law. Bently Nevada, Inc. is not responsible for the
disposal of the product at the end of its life or at the end of its use.
iii
Valve Position Configuration and Verification Manual
Contents
1. 3500 ENCORE Compatibility Requirements ..................................................... 1
2. ENCORE Nomenclature ........................................................................................ 2
3. ENCORE Valve Position Screen Displays .......................................................... 3
3.1 Display Components ................................................................................................................................. 3
4. Configuration Considerations ............................................................................ 5
5. AC - LVDT Configuration Options ...................................................................... 7
5.1 Transducer Setup + Filtering Tab ....................................................................................................... 7
5.1.1 Reference Information ................................................................................................................... 7
5.1.2 Transducer Type ................................................................................................................................ 8
5.1.3 Customize Button, AC LVDT ......................................................................................................... 8
5.1.4 Valve Stroke Displacement ....................................................................................................... 10
5.2 Variables + Alarms Tab ......................................................................................................................... 10
5.2.1 Direct Full-scale Range ............................................................................................................... 11
5.2.2 Position ................................................................................................................................................ 11
5.2.3 Clamp Value ..................................................................................................................................... 11
5.2.4 Delay ..................................................................................................................................................... 12
5.2.5 Alarm Mode ....................................................................................................................................... 13
5.2.6 OK Mode ............................................................................................................................................. 13
5.2.7 Not OK Channel Defeat .............................................................................................................. 14
5.2.8 Recorder Output ............................................................................................................................. 14
6. Rotary Potentiometer Configuration Options ............................................... 15
6.1 Transducer Setup + Filtering Tab .................................................................................................... 15
6.1.1 Reference Information ................................................................................................................. 15
6.1.2 Transducer Type ............................................................................................................................. 16
6.1.3 Customize .......................................................................................................................................... 16
6.1.4 Valve Stroke Displacement ....................................................................................................... 17
6.2 Variables + Alarms Tab ......................................................................................................................... 18
6.2.1 Direct Full-scale Range ............................................................................................................... 18
6.2.2 Position ................................................................................................................................................ 18
6.2.3 Clamp Value ..................................................................................................................................... 18
6.2.4 Delay ..................................................................................................................................................... 19
6.2.5 Alarm Mode ....................................................................................................................................... 20
6.2.6 OK Mode ............................................................................................................................................. 20
6.2.7 Not OK Channel Defeat .............................................................................................................. 21
6.2.8 Recorder Output ............................................................................................................................. 21
iv
7. Rotary Position Transducer Configuration Options .................................... 22
7.1 Transducer Setup + Filtering Tab .................................................................................................... 22
7.1.1 Reference Information ................................................................................................................. 22
7.1.2 Transducer Type ............................................................................................................................. 23
7.1.3 Customize .......................................................................................................................................... 23
7.1.4 Valve Stroke Displacement ....................................................................................................... 25
7.2 Variables + Alarms Tab ......................................................................................................................... 26
7.2.1 Direct Full-scale Range ............................................................................................................... 26
7.2.2 Position ................................................................................................................................................ 27
7.2.3 Clamp Value ..................................................................................................................................... 27
7.2.4 Delay ..................................................................................................................................................... 27
7.2.5 Alarm Mode ....................................................................................................................................... 28
7.2.6 OK Mode ............................................................................................................................................. 28
7.2.7 Not OK Channel Defeat .............................................................................................................. 29
7.2.8 Recorder Output ............................................................................................................................. 29
8. Available Setpoints ............................................................................................. 30
8.1 Alarm Setpoint Dialog ........................................................................................................................... 30
9. Verification ........................................................................................................... 32
9.1 Test Equipment and Software Setup ............................................................................................. 32
9.1.1 Test Equipment Setup - AC LVDT ........................................................................................... 32
9.1.2 Test Equipment Setup - Rotary Potentiometer ............................................................... 39
9.1.3 Test Equipment Setup - Rotary Position Transducer ................................................. 42
9.1.4 Verification Screen Setup ........................................................................................................... 43
9.2 Valve Position Channel Adjustments ............................................................................................. 43
9.2.1 Adjusting the Channel Sensitivity with an AC LVDT ..................................................... 43
9.2.2 Adjusting the Scale Factor with a Rotary Pot ................................................................. 44
9.2.3 Adjusting the Scale Factor with a Rotary Position Transducer .............................. 45
9.3 Test Alarms ................................................................................................................................................. 46
9.3.1 Direct Alarms for AC LVDT Channel ..................................................................................... 46
9.3.2 Direct Alarms for a Rotary Pot Channel ............................................................................. 47
9.3.3 Direct Alarms for a Rotary Position Transducer Channel ......................................... 48
9.4 Verify Channel Values ........................................................................................................................... 49
9.4.1 Direct and Position Values for an AC LVDT Channel ................................................... 49
9.4.2 Direct and Position Values for a Rotary Pot Channel ................................................. 50
9.4.3 Direct and Position Values for a Rotary Position Transducer Channel .............. 50
9.5 Test OK Limits ............................................................................................................................................ 51
9.5.1 Testing OK Limits for AC LVDT Channels ........................................................................... 52
9.5.2 Testing OK Limits for Rotary Pots .......................................................................................... 54
9.5.3 Testing OK Limits for a Rotary Position Transducer Channel ................................. 56
v
Section 1 - 3500 ENCORE Compatibility Requirements
1
Valve Position Configuration and Verification Manual
2. ENCORE Nomenclature
3300 ENCORE Upgrade Rack
A 3300 Monitoring System Rack that has been upgraded to contain 3500 ENCORE
modules. The original 3300 I/O modules are retained. 3500/45E and 3500/42E monitors
installed in a 3300 ENCORE Upgrade rack are limited to two measurement channels.
3500 ENCORE Rack
A 3500 ENCORE Monitoring System rack designed to contain 3500 ENCORE modules
including 3500 ENCORE I/O modules. 3500/45E and 3500/42E monitors installed in a
3500 ENCORE rack have four measurement channels.
2
Section 3 - ENCORE Valve Position Screen Displays
1. Direct
2. Position
3
Valve Position Configuration and Verification Manual
1. Measurement Type
2. Upper Full Scale Range (FSR)
3. Upper Danger Setpoint (Red Solid Line)
4. Upper Alert Setpoint (Amber Solid Line)
5. Channel Indicator
6. Zero Point (Black Solid Line)
7. Lower Full Scale Range
8. Channel Measured Value
9. Channel Units
10. Page Number Sequence
4
Section 4 - Configuration Considerations
4. Configuration Considerations
• Measure the Valve Position using:
• Rotary Potentiometers with a Rotary Pot I/O, or
• AC LVDTs with an AC LVDT I/O, or
• Rotary Position Transducers with a standard Position I/O.
• Rotary Pot Position I/O modules are available only if Valve Position is chosen for
Channel Pair 1 and 2 AND Channel Pair 3 and 4.1
• Applications normally measure valve position by using a linear displacement
transducer to measure the position of the valve stem relative to its full stroke,
1. Valve Stem
2. LVDT
1. Cam Shaft
2. Rotary Position Transducer or Potentiometer
5
Valve Position Configuration and Verification Manual
• Configure each channel to display “% Open” or “% Closed”, with 100% correlating to
fully opened or fully closed, respectively.
• There is no Keyphasor* option for this channel type.
• TMR I/O modules are not available for Valve Position Channel types. If Valve Position
channel type is chosen in a TMR configuration, it will be automatically reset to the
previous setting.2
• When you modify a full-scale range, readjust the setpoints associated with this
value.
• The Latching OK Mode and the Not OK Channel Defeat options are not compatible.
• After initially configuring the valve position channels, download the configuration.
• Choose Valve Position as the channel pair type, and then choose the I/O type.
1
Channels 2 and 4 are not available on a 3500/45E module connected to a 3300 I/O
module.
2
The TMR option is not available on 3500 ENCORE systems.
6
Section 5 - AC - LVDT Configuration Options
7
Valve Position Configuration and Verification Manual
Configuration ID
Displays an optional identifier of up to six characters, which, if present, was entered
upon last configuration download to the module.
8
Section 5 - AC - LVDT Configuration Options
After you download an initial configuration to the monitor, use this button to adjust the
Full Upscale or Full Downscale voltage of the AC LVDT when stroking the valve. The
Channel Sensitivity will change as you change the Upscale/Downscale voltages. Refer to
Section "Adjusting the Upscale and Downscale Voltage for Valve Position."
Table 5-2: Default AC LVDT Sensitivity, Full Upscale and Full Downscale
Transducer Sensitivity Full Upscale Voltage (V) Full Downscale Voltage (V)
(mVout / mVin / mil)
1 in (25mm) 18639-01 0.73 -14.526 -7.554
2 in (50 mm) 18639-02 0.39 -14.765 -7.316
4 in (101 mm) 18639-05 0.24 -15.624 -6.456
6 in (152 mm) 18639-06 0.26 -18.489 -3.591
8 in (203 mm) 18639-09 0.19 -18.298 -3.782
10 in (254 mm) 18639-07 0.14 -17.725 -4.355
12 in (304 mm) 18639-04 0.09 -16.197 -5.883
20 in (508 mm) 18639-08 0.08 -18.680 -3.400
10
Section 5 - AC - LVDT Configuration Options
5.2.2 Position
The Position Full-scale voltage range is –24 to 0 Vdc. It is the same for all AC LVDT
transducer types and is not adjustable.
5.2.4 Delay
Delay is the time for which a static value must remain at or above an over alarm level,
or below an under alarm level, before the monitor declares an alarm as active.
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all
available static values. Alert is the first level alarm that occurs when the transducer
signal level exceeds the selected Alert/Alarm 1 setpoint. You can set this setpoint on the
Setpoint screen.
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds.
Danger is the second level alarm that occurs when the transducer signal level exceeds
the selected Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
The 100 ms (typical) option applies only to the Danger time delay and has the following
effects:
If the 100 ms option is OFF:
• You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
• You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
• The software sets the Danger time delay to 100 ms.
• You can set the Danger time delay for only the primary static value.
12
Section 5 - AC - LVDT Configuration Options
5.2.5.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops
below the configured setpoint level. The channel will remain in alarm until you use one
of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
5.2.5.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value
drops below the configured setpoint level.
5.2.6 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK, the
status will stay Not OK until you use one of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
13
Valve Position Configuration and Verification Manual
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track
the defined OK status of the transducer.
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed
channel to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a
Bypassed channel.
14
Section 6 - Rotary Potentiometer Configuration Options
15
Valve Position Configuration and Verification Manual
Rack Type
Indicates the type of Rack Interface Module that is installed in the rack
Configuration ID
Displays an optional identifier of up to six characters, which, if present, was entered
upon last configuration download to the module.
6.1.3 Customize
Use this parameter to adjust the Scale Factor of the transducer. Refer to Section
"Adjusting the Scale Factor or Channel Sensitivity."
16
Section 6 - Rotary Potentiometer Configuration Options
After initially downloading configuration to the monitor, use this button to adjust the Full
Upscale or Full Downscale voltage of the Rotary Potentiometer when stroking the
valve.The Scale Factor will change as you change the Upscale/Downscale voltages.
Since this utility provides active feedback from the 3500 rack, it requires a connection
with the rack
17
Valve Position Configuration and Verification Manual
6.2.2 Position
The position Full-scale voltage range is –24 to 0 Vdc. It is not adjustable.
18
Section 6 - Rotary Potentiometer Configuration Options
• Monitor Not Ok status
The clamp value is not shown on the monitor display or in the 3500 Rack Configuration
software.
• 3500 Systems:
The monitor clamps only the Recorder Outputs and the values provided through the
Communication Gateway and Display Interface Module when the static value is
invalid.
• 3500 ENCORE Systems:
The monitor clamps only the Recorder Outputs and the values provided over
Modbus when the static value is invalid.
6.2.4 Delay
Delay is the time for which a static value must remain at or above an over alarm level,
or below an under alarm level, before the monitor declares an alarm as active.
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all
available static values. Alert is the first level alarm that occurs when the transducer
signal level exceeds the selected Alert/Alarm 1 setpoint. You can set this setpoint on the
Setpoint screen.
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds.
Danger is the second level alarm that occurs when the transducer signal level exceeds
the selected Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
The 100 ms (typical) option applies only to the Danger time delay and has the following
effects:
If the 100 ms option is OFF:
• You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
• You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
• The software sets the Danger time delay to 100 ms.
• You can set the Danger time delay for only the primary static value.
19
Valve Position Configuration and Verification Manual
6.2.5.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops
below the configured setpoint level. The channel will remain in alarm until you use one
of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
6.2.5.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value
drops below the configured setpoint level.
6.2.6 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK, the
status will stay Not OK until you use one of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
20
Section 6 - Rotary Potentiometer Configuration Options
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track
the defined OK status of the transducer.
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed
channel to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a
Bypassed channel.
21
Valve Position Configuration and Verification Manual
22
Section 7 - Rotary Position Transducer Configuration Options
Rack Type
Indicates the type of Rack Interface Module that is installed in the rack
Configuration ID
Displays an optional identifier of up to six characters, which, if present, was entered
upon last configuration download to the module.
XX represents the code for the length of the connecting cable from the transducer to the
prox. The following values can be substituted:
50 = 5 meter with integral probe and cable
51 = 5 meter with 1 meter probe and 4 meter extension cable
90 = 9 meter with integral probe and cable
91 = 9 meter with 1 meter probe and 8 meter extension cable
YY represents the mounting option:
00 = panel mount
01 = DIN mount
02 = no mounting hardware
ZZ represents approvals:
00 = no approvals
A sales representative can answer any questions you may have regarding this code.
7.1.3 Customize
Use this parameter to adjust the Scale Factor of the transducer. Refer to Section
"Adjusting the Scale Factor or Channel Sensitivity."
23
Valve Position Configuration and Verification Manual
Table 7-5: Default Rotary Position Transducer Scale Factor, Full Upscale and Full
Downscale
Transducer Scale Factor Full Scale Range Valve Opening Full Upscale Full Downscale
(mV/deg) Option Direction (V) Voltage
(V)
0 - 100 Deg 140 0 - 100 % open CW -2.00 -16.00
0 - 100 % closed CW -16.00 -2.00
0 - 100 % open CCW -16.00 -2.00
0 - 100 % closed CCW -2.00 -16.00
0 - 200 Deg 70 0 - 100 % open CW -2.00 -16.00
0 - 100 % closed CW -16.00 -2.00
0 - 100 % open CCW -16.00 -2.00
0 - 100 % closed CCW -2.00 -16.00
0 - 300 Deg 50 0 - 100 % open CW -1.50 -16.50
0 - 100 % closed CW -16.50 -1.50
0 - 100 % open CCW -16.50 -1.50
0 - 100 % closed CCW -1.50 -16.50
24
Section 7 - Rotary Position Transducer Configuration Options
Table 7-6: Rotary Position Transducer OK Limits
Transducer Upper OK Limit Lower OK Limit
(Vdc) (Vdc)
100 degree Rotary Position -16.50 -1.50
200 degree Rotary Position -16.50 -1.50
300 degree Rotary Position -17.00 -1.20
After initially downloading configuration to the monitor, use this button to adjust the Full
Upscale or Full Downscale voltage of the Rotary Position Transducer when stroking the
valve. The Scale Factor will change accordingly as you change the Upscale/Downscale
voltages.
Since this utility provides active feedback from the 3500 rack, it requires a connection
with the rack.
The monitor uses this setting to identify whether the most negative voltage of the
usable voltage range correlates to Full Upscale or Full Downscale. The Valve Opening
Direction means the direction the shaft on the Rotary Position Transducer must turn to
open the valve(s) when viewed from the driver end of the transducer (i.e., the end
attached to the camshaft). The direction of rotation can be either clockwise (CW) or
counter-clockwise (CCW).
ADVISORY
Generally, the Rotary Position Transducer interfaces to the camshaft when the
valves are fully closed. The following table gives the formulas to calculate the
voltage output of the Rotary Position Transducer when the valves are fully
closed. This voltage is based on the transducer’s scale factor, the valve
opening direction, the configured full-scale range, and the configured valve
stroke displacement.
25
Valve Position Configuration and Verification Manual
Full Scale Range Option Valve Opening Direction (degrees Default Voltage for fully closed
rotation) valves (V)
0 – 100% open CW -9 – (SF x VSD/2)
0 – 100% open CCW -9 + (SF x VSD/2)
0 – 100% closed CW -9 – (SF x VSD/2)
0 – 100% closed CCW -9 + (SF x VSD/2)
CW = Clockwise
CCW = Counter Clockwise
SF = Scale Factor (V/mil)
VSD = Vale Stroke displacement (degrees rotation)
7.2.2 Position
The position Full-scale voltage range is –24 to 0 Vdc. It is not adjustable.
7.2.4 Delay
Delay is the time for which a static value must remain at or above an over alarm level,
or below an under alarm level, before the monitor declares an alarm as active.
You can set the Alert time delay in 1 second increments (from 1 to 60 seconds) for all
available static values. Alert is the first level alarm that occurs when the transducer
signal level exceeds the selected Alert/Alarm 1 setpoint. You can set this setpoint on the
Setpoint screen.
You can set the Danger Time Delay at 500 millisecond increments from 1 to 60 seconds.
Danger is the second level alarm that occurs when the transducer signal level exceeds
the selected Danger/Alarm 2 setpoint. You can set this setpoint on the Setpoint screen.
The 100 ms (typical) option applies only to the Danger time delay and has the following
effects:
27
Valve Position Configuration and Verification Manual
If the 100 ms option is OFF:
• You can set the Danger time delay in 1-second increments (from 1 to 60 seconds).
• You can set the Danger time delay for up to 2 available static values.
If the 100 ms option is ON:
• The software sets the Danger time delay to 100 ms.
• You can set the Danger time delay for only the primary static value.
7.2.5.1 Latching
Once a latching alarm is active, it will remain active even after the static value drops
below the configured setpoint level. The channel will remain in alarm until you use one
of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
7.2.5.2 Non-latching
When a non-latching alarm is active, it changes to inactive as soon as the static value
drops below the configured setpoint level.
7.2.6 OK Mode
Latching
If you configure a channel for Latching OK, then once the channel has gone Not OK, the
status will stay Not OK until you use one of the following methods to reset it:
• Pressing the RESET button on the System Monitor
• Closing the contact on the Power Input Module (PIM)
• Clicking the Reset button in the Operator Display software 1
28
Section 7 - Rotary Position Transducer Configuration Options
• Issuing a reset command over Modbus
• Issuing a reset command through the Display Interface Module 1
• Issuing a reset command in the 3500 Rack Configuration Software
1
3500 Only
Non-latching
If you configure a channel for Non-latching OK, the OK status of that channel will track
the defined OK status of the transducer.
Click this check box to cause the monitor to clamp the Recorder Output for a Bypassed
channel to 2 mA.
Clear this check box to cause the monitor to use the selected clamp value for a
Bypassed channel.
29
Valve Position Configuration and Verification Manual
8. Available Setpoints
The table below lists the Alert/Alarm 1 and Danger/Alarm 2 setpoints that are available
for the Valve Position channel types. Modbus uses the setpoint number.
30
Section 8 - Available Setpoints
ADVISORY
Bently Nevada does not recommend configuring Valve Position to trip a
machine.
31
Valve Position Configuration and Verification Manual
9. Verification
ALERT
Do not power an AC LVDT from the I/O without the AC LVDT core in place.
This could result in damage to the monitor and/ or rack.
1. Use a function generator to input a 3.3 Vrms (±0.5 Vrms), 0 Vdc offset, 3400 Hz sine
wave signal into terminals 1 and 2 of the AC LVDT. If a function generator is not
available, terminals 1 and 2 on the back of the internal termination AC LVDT I/O or
the respective terminals of the external termination block can be used to provide a
drive signal of 3.3 Vrms (±0.5 Vrms), -11 Vdc offset, 3400 Hz sine wave to power the
AC LVDT while finding the null position.
32
Section 9 - Verification
Figure 9-16: Finding Electrical Null on AC LVDT Using I/O Module - 3300 Backplane
33
Valve Position Configuration and Verification Manual
Figure 9-17: Finding Electrical Null on AC LVDT Using I/O Module - 3500 Backplane
34
Section 9 - Verification
1. Function Generator
2. AC LVDT
3. Multimeter
4. Short terminals 4 and 5 together
5. Mark electrical null on extension rod when multimeter reads the minimum
AC voltage
2. Use a multimeter to measure the AC voltage output across terminals 3 and 6 of the
AC LVDT. As you move the core of the AC LVDT, observe that the AC voltage across
terminals 3 and 6 decreases from some maximum value to some minimum value
(near the core's center) and then back to some maximum value. Move the AC LVDT's
core until you obtain the minimum AC voltage near the core's center. Mark the core
extension rod to identify this electrical null position of the AC LVDT. Once you
correctly configure the monitor, this null position should equate to a Position
measurement of -11.04 Vdc (±0.24 Vdc).
35
Valve Position Configuration and Verification Manual
3. Place a mark on the LVDT core extension rod equal to half the full range of the AC
LVDT on each side of the electrical null mark. For example, if the full range of the AC
LVDT is 2 inches, then make a mark 1 inch from null position on each side of the
rod. Use these marks to position the core during installation and verification.
Typically, the monitor can be configured for a range down to 50% of the full range
of the AC LVDT.
4. If you will enable alarms in the monitor configuration, you can also mark the alarm
points on the extension rod. For example, if you will set a Danger over alarm for
90% of full scale, then mark the rod at 90% of the full-scale range distance that you
previously marked in Step 3.
5. Interface the AC LVDT to the machine.
6. Connect the AC LVDT to the I/O.
36
Section 9 - Verification
7. Observe that the AC LVDT housing has an orientation mark at one end, and that the
core itself has an orientation mark at one end. When you configure the monitor,
downscale should correspond to movement of the LVDT core in the direction that is
away from the LVDT's housing orientation mark. The opposite direction of rod
travel will correspond to upscale. If this is not the case, you should reverse the
wires at terminals 3 and 6 of either the LVDT or the I/O (but not at both).
8. The datasheet that came with the AC LVDT states the sensitivity of the AC LVDT.
The configuration software uses a default sensitivity (based on your transducer
37
Valve Position Configuration and Verification Manual
type) in its calculations until you adjust the sensitivity or the Full Upscale or Full
Downscale voltages during configuration.
You can calculate the loop Channel Sensitivity for a channel when the AC LVDT and
its associated field wiring are interfaced to the monitor and I/O as follows:
1. Measure the AC voltage in Vac across I/O terminals 1 and 2 to get V ex. This is
the excitation signal that is driving the AC LVDT.
2. Set Range to the full transducer range in inches that you marked in step 3
above.
3. Measure the AC voltage in Vac across I/O terminals 3 and 6 while the core is at
one end of its full range that you marked in step 3 above. This is V 1.
4. Measure the AC voltage in Vac across I/O terminals 3 and 6 while the core is at
the opposite end of its full range. This is V2.
5. Calculate the Channel Sensitivity using the following equation:
Channel Sensitivity = (V1 + V2) / Range / Vex
9. You can manually enter the Channel Sensitivity during configuration or the software
will be automatically calculate and adjust it when you set the full upscale and
downscale voltages of the system.
10. The DC voltage output (Position PPL) at any given AC LVDT rod position is related to
the Channel Sensitivity by the following equation:
Vout = 11.04 ± Channel Sensitivity x d x 9.55)
where: 11.04 is from step 2 above
d is the distance moved from the null position
The ± depends on which direction from null the rod has been moved
38
Section 9 - Verification
DANGER
High voltage present. Contact with high voltage can cause shock, burns, or
death. Do not touch exposed wires or terminals.
NOTE
Tests will exceed alarm levels and cause alarms to activate. This could result
in a relay change.
Disconnecting field wiring will cause a Not OK condition.
39
Valve Position Configuration and Verification Manual
2. Make a mark on the pot at the point of the maximum resistance, making sure that
the wiper is still in contact with the coils, and note of this resistance value.
When interfaced to a properly configured monitor, this point will correspond to a
Position measurement reading (in the Verification dialog screen) of -17.38 Vdc
nominal. This point also corresponds to full upscale when configured for 0 to 100%
open or corresponds to full downscale when configured for 0 to 100% closed.
If you must reverse this, you can reverse the wires at terminals CW and CCW of
either the rotary pot or the I/O, but not at both.
3. Make another mark on the pot that will equate to full scale in the clockwise
direction from the mark you made in step 2 above. Note the resistance measured
at this point. This point corresponds to full downscale when configured for 0 to
100% open or to full upscale when configured for 0 to 100% closed.
If you must reverse this, you can reverse the wires at terminals CW and CCW of
either the rotary pot or the I/O, but not at both.
NOTE
For convenience, mark these same resistance positions on a spare Rotary Pot
that you can use to verify the channel during maintenance.
4. If you will enable alarms in the monitor configuration, you can also mark the alarm
points on the pot. For example, if you will set a Danger over alarm for 90% of full
scale then mark the pot at 90% of the full scale stroke travel that you marked
above.
5. Interface the Rotary Pot to the camshaft so that the marks made in steps 2 and 3
correspond to the endpoints of the rotation of the rotary pot with respect to the
actual full valve stroke.
6. Connect the Rotary Pot to the I/O.
40
Section 9 - Verification
1. Rotary Potentiometer I/O Module
2. Rotary Potentiometer (top View)
7. After configuring and downloading the 3500 software settings for the rotary pot
valve position channel, stroke the valve and use the Adjust utility to set the voltage
endpoints that will exactly equate to 0 and 100% open or closed.
As you stroke the valve and adjust the Full Upscale and Downscale voltages, the
Scale Factor will change accordingly, based on the full stroke rotation previously
configured.
NOTE
The 3500 configuration software uses a default Scale Factor of 41 mV/degree
rotation until you adjust the Full Upscale or Full Downscale voltages while
stroking the valve.
The DC voltage output (Position measurement in the 3500 verification screen) at any
given degrees of rotation is related to the Scale Factor by the following:
Vdc(out) = V1 + (S.F. * D) where:
41
Valve Position Configuration and Verification Manual
S.F. = Scale Factor
D = the position from the –17.38 Vdc endpoint in degrees of
rotation.
DANGER
High voltage present. Contact with high voltage can cause shock, burns, or
death. Do not touch exposed wires or terminals.
ADVISORY
1. Test levels will exceed alarm setpoint levels and activate alarms. This
could result in a relay contact state change.
2. Disconnecting field wiring will cause a Not OK condition.
Connect the power supplies and multimeter to the COM and SIG terminals of Channel 1
as shown in the Figure below to simulate the transducer signal. The test equipment
outputs should be floating relative to earth ground.
42
Section 9 - Verification
44
Section 9 - Verification
NOTE
If using a power supply to set the scale factor, repeat steps 1-12 setting the
upscale and downscale voltages with the power supply.
45
Valve Position Configuration and Verification Manual
46
Section 9 - Verification
replace the monitor. Refer to "If a Channel Fails a Verification Test" in your monitor
hardware manual.
14. Disconnect the test equipment and reconnect the field wiring to the channel
terminals on the I/O Module. Verify that the OK LED comes on and the OK relay
energizes. Press the RESET switch to reset the OK LED.
15. Repeat steps 1 through 14 for all configured Case Expansion channels with AC
LVDTs.
47
Valve Position Configuration and Verification Manual
12. Repeat steps 1 through 11 for all configured Valve Position channels using a Rotary
Pot transducer.
48
Section 9 - Verification
49
Valve Position Configuration and Verification Manual
9.4.3 Direct and Position Values for a Rotary Position Transducer Channel
1. Disconnect the field wiring from the channel terminals on the I/O Module.
2. Connect the test equipment per Section "Test Equipment Setup - Rotary Position
Transducer" and run the software as described in Section "Verification Setup."
3. Adjust the power supply voltage for the upscale voltage displayed in the verification
screen.
4. Verify that the Direct and Position bar graph displays are reading full upscale.
50
Section 9 - Verification
5. Verify that the Current Value Box is reading the configured upscale voltage ± 1% of
full-scale (full-scale = upscale volts – downscale volts).
6. If the recorder output is configured, refer to Section "Verify Recorder Output" in your
monitor manual.
7. Adjust the power supply voltage to the downscale voltage displayed in the
verification screen.
8. Verify that the Direct and Position bar graph displays are reading full down scale.
9. Verify that the Current Value Box is reading the configured downscale voltage ± 1%
of full-scale as in step 5.
10. Verify the recorder output as in step 6.
11. Adjust the power supply voltage for the mid-scale voltage. The mid-scale voltage is:
- | Upscale Voltage – Downscale Voltage | / 2
12. Verify that the Direct and Position bar graph displays are reading at the middle of
the graph.
13. Verify that the Current Value Box is reading the mid-scale voltage ± 1% of full-scale
as in step 5.
14. Verify the recorder output as in step 6.
15. If the reading does not meet specifications, check that the input signal is correct. If
the reading still does not meet specifications you must replace the monitor. Refer to
"If a Channel Fails a Verification Test" in your monitor hardware manual.
16. Disconnect the test equipment and reconnect the PWR, COM, and SIG field wiring to
the channel terminals on the I/O Module.
17. Verify that the OK LED comes on and the OK relay energizes.
18. Press the RESET switch on the System Monitor to reset the OK LED.
19. Repeat steps 1 through 18 for all configured channels using a Rotary Position
transducer.
51
Valve Position Configuration and Verification Manual
1. Disconnect the field wiring from the channel terminals on the I/O Module.
2. Connect the test equipment as shown in Section "AC LVDT Test Equipment Setup"
and run the software as described in "Verification Screen Setup".
3. Bypass all other configured channels.
4. Repeat subsections below for in range, out of range, open wiring and shorted wiring
for all configured channels using AC LVDTs.
NOTE
If the Danger Bypass has been activated, then the BYPASS LED will be on. All
other channels in the rack must be OK or bypassed for the OK relay to be
energized.
52
Section 9 - Verification
displayed on the Verification screen is equal to or less positive than the voltage
read in the Current Value box in the Verification screen.
6. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
7. Return to normal operation by adjusting the AC LVDT’s core/extension rod to a
position between the full-scale endpoint marks.
8. Press the RESET switch. Verify that the OK LED comes back on and that the OK relay
energizes. Verify that the Channel OK State line in the Channel Status section reads
OK.
9. If you cannot verify any configured OK limit, you must replace the monitor. Refer to
“If a Channel Fails a Verification Test” in your monitor hardware manual.
10. Disconnect the test equipment and reconnect the field wiring to the channel
terminals on the I/O module. Press the RESET switch and verify that the OK LED
comes on and the OK relay energizes.
11. Return the bypass switches for all configured channels back to their original
settings.
Out of Range OK Test (for ±0.5 in (±13mm), ±1 in (±25mm) or ±2 in (±50mm) AC LVDT
transducer types only)
1. Use a spare LVDT or disconnect the extension rod from the valve linkage and adjust
the extension rod to increase the voltage (less negative) until the OK LED just goes
off.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
3. Verify that the Lower OK limit voltage listed in Table 3-24 and displayed on the
Verification screen is equal to or more negative than the input voltage.
4. Adjust the extension rod to decrease the voltage (more negative) until the OK LED
comes on.
5. Continue to adjust the extension rod to decrease the voltage (more negative) until
the OK LED just goes off.
6. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
7. Verify that the Upper OK limit voltage listed in the Table and displayed on the
Verification screen is equal to or more positive than the input voltage.
NOTE
For LVDT transducers other than the ±0.5 in (±13mm), ±1 in (±25mm) or ±2 in
(±50mm) transducer types, the OK limit voltages listed in the Table are for
open or shorted wiring conditions only.
53
Valve Position Configuration and Verification Manual
Open Wiring OK Test, AC LVDT
1. Open terminal 1 and 2 at the AC LVDT or at the I/O and verify that the OK LED goes
off.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
3. Verify that the DC voltage output (Position bargraph or current value) is more
negative than the Upper OK limit voltage listed in the Table and displayed on the
Verification screen.
4. Reconnect terminal 1 and 2 and verify that the OK LED comes on.
5. Open terminal 3 or 6 at the AC LVDT or at the I/O and verify that the OK LED goes
off.
6. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
7. Verify that the DC voltage output (Position bargraph or current value) is more
positive than the Lower OK limit voltage listed in the Table and displayed on the
Verification screen.
8. Reconnect terminal 3 and 6 and verify that the OK LED comes on.
Shorted wiring OK test, AC LVDT:
1. Short terminal 1 to terminal 2 at the AC LVDT or at the I/O and verify that the OK
LED goes off.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
3. Remove the short.
4. Reconnect the field wiring and adjust the extension rod position of the AC LVDT to
be in the OK range as described in "In Range OK Test, AC LVDT."
5. Press the RESET switch on the System Monitor.
6. Verify that the OK LED comes back on, the OK relay energizes, and the Channel OK
State line in the Channel Status box reads OK.
7. Return the bypass switch for all configured channels to their original setting.
1. Disconnect the field wiring from the channel terminals on the I/O Module.
54
Section 9 - Verification
2. Connect the test equipment as shown in Section 5.1.10.1.2 and run the software as
described in Section "Test Equipment Setup - Rotary Potentiometer." Connect to
both channels.
3. Bypass all other configured channels.
4. Repeat all subsections below for in range, out of range, and open wiring for all
configured channels using a Rotary Pot.
In Range OK Test, Rotary Pot
1. Adjust the shaft to a position between the full-scale endpoint marks on the pot.
Verify that the Position bar graph display in the Verification screen reads within the
OK Limits for the Rotary Pot.
2. Verify that the OK relay on the System Monitor indicates OK (energized). See the
3500/20, 3500/22 or 3500/23E Operation and Maintenance Manual.
3. Press the RESET switch. Verify that the monitor OK LED is on and that the Channel
OK State line in the Channel Status section of the Verification screen reads OK.
Out of Range OK Test, Rotary Pot
1. Use a spare pot or disconnect the primary pot from the valve linkage and adjust the
pot shaft to a position outside the full-scale endpoint marks until the OK LED just
goes off.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK. The Lower OK limit voltage is equal to or more
negative than the input voltage and the Upper OK limit voltage is equal to or more
positive than the input voltage listed in Table 3-26 and displayed on the Verification
screen.
Open Wiring OK Test, Rotary Pot
1. Open CW or CCW of the field wiring and verify that the OK LED goes off.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK. The Lower OK limit voltage listed in the Table
and displayed on the Verification screen is equal to or more negative than the input
voltage.
3. Open “S” of the field wiring and verify that the OK LED goes off.
4. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK. The Upper OK limit voltage listed in the Table
and displayed on the Verification screen is equal to or more positive than the input
voltage.
5. Reconnect the field wiring and adjust the Pot as in the Section "In Range OK Test,
Rotary Pot."
6. Press the RESET switch.
7. Verify that the OK LED comes back on, the OK relay energizes, and the Channel OK
State line in the Channel Status box reads OK.
8. Return the bypass switch for all configured channels to their original setting.
55
Valve Position Configuration and Verification Manual
1. Disconnect the field wiring from the channel terminals on the I/O Module.
2. Connect the test equipment as shown in Section "Test Equipment Setup - Rotary
Position Transducer" and run the software as described in Section "Verification
Screen Setup." Connect to both channels.
3. Bypass all other configured channels.
4. Repeat all subsections below for in range, out of range, open wiring and shorted
wiring for all configured channels using a Rotary Position Transducer.
In Range OK Test, Rotary Position Transducer
1. With the input voltage set to approximately the mid-scale voltage, press the RESET
switch on the System Monitor.
2. Verify that the OK LED comes on, the OK relay energizes, and the Channel OK State
line in the Channel Status box reads OK.
Out of Range Test, Rotary Position Transducer
1. Increase the input power supply voltage (more negative) until the OK LED just goes
off (upper limit).
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
3. Verify that the Upper OK limit voltage displayed on the Verification screen is equal
to or more positive than the input voltage.
4. Decrease the input voltage (less negative) to approximately the mid-scale voltage.
5. Press the RESET switch.
6. Verify that the OK LED comes back on, the OK relay energizes, and the Channel OK
State line in the Channel Status box reads OK.
7. Gradually decrease the input voltage (less negative) until the OK LED just goes off
(lower limit).
8. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
9. Verify that the Lower OK limit voltage displayed on the Verification screen is equal
to or more negative than the input voltage.
56
Section 9 - Verification
10. If you cannot verify any configured OK limit, you must replace the monitor. Refer to
“If a Channel Fails a Verification Test” in your monitor hardware manual.
Open Wiring OK Test, Rotary Position Transducer
1. Reconnect the field wiring to the channel terminals on the I/O Module.
2. Press the RESET switch on the System Monitor.
3. Verify that the OK LED comes back on, the OK relay energizes, and the Channel OK
State line in the Channel Status box reads OK.
4. Open the probe or extension cable on the transducer or the PWR, COM or SIG wires
on the I/O module.
5. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
6. Verify that the Lower OK limit voltage displayed on the Verification screen is equal
to or more negative than the input voltage.
Shorted Wiring OK Test, Rotary Position Transducer
1. Short the probe or extension cable on the transducer or the PWR or SIG wires on
the I/O module to COM.
2. Verify that the Channel OK State line in the Channel Status box reads Not OK and
that the OK Relay indicates Not OK.
3. Verify that the Lower OK limit voltage displayed on the Verification screen is equal
to or more negative than the input voltage.
4. Reconnect the field wiring and adjust the Rotary Position Transducer as in Section
"In Range OK Test, Rotary Position Transducer."
5. Press the RESET switch on the System Monitor.
6. Verify that the OK LED comes back on, the OK relay energizes, and the Channel OK
State line in the Channel Status box reads OK.
7. Return the bypass switch for all configured channels to their original setting.
57