1. Remove level switch from AI list. It (LSH 440-040) should be come under DI list.

2. And consider below list for AI.

LT 440-
004A 3D RADAR LEVEL TRANSMITTER
LT 440-
004B 3D RADAR LEVEL TRANSMITTER
DPT 440-
011 SILO DE‐DUSTING SYSTEM
DPT 440-
012 De-dusting system for Wagon loading
GV 440‐
066H1 ALUMINA TO CONTROL VALVE ABOVE LOADING SPOUT 004H
GV 440‐
066K1 ALUMINA TO CONTROL VALVE ABOVE LOADING SPOUT 004K
WL 440-
007 Wagon loading signal from weighing Console # 7
WL 440-
008 Wagon loading signal from weighing Console # 7
DCI 440-  DE-Dusting Motor Current Transducer signal to PLC
DCI 440-  DE-Dusting Motor Current Transducer signal to PLC

3. There are 2 AO signals for Silo-4.


These are mentioned in the below list.

GV 440‐
066H2 ALUMINA TO CONTROL VALVE ABOVE LOADING SPOUT 004H
GV 440‐
066K2 ALUMINA TO CONTROL VALVE ABOVE LOADING SPOUT 004K

4. For each MCC, consider one more DI for “Ready to start” signal.
5. Remove IO for CF-116
6. ZSH & ZSL FOR XV 440-101 and XV 440-103 are mentioned twice in the DI list.
7. Change the tag of GV 440-096 to XV 440-096.
8. For level switch of 66U, 66V, 66W, 66X, 66Y &66Z please consider 2 ZSL. These are:

ZSL 440‐066U-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066U-2 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066V-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066V-2 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066W-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066W-2 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066X-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066X-2 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066Y-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066Y-2 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066Z-1 Limit switch Position Down of Loading Spout (Chute Extend)
ZSL 440‐066Z-2 Limit switch Position Down of Loading Spout (Chute Extend)

9. And consider ZSH for each 66X, 66Y &66Z.