Professional Documents
Culture Documents
Muhammad I. (RSM Paper)
Muhammad I. (RSM Paper)
4
Building Department, Ahmadu Bello University Zaria
5
School of Mechanical Engineering, Universiti Sains Malaysia, Engineering Campus
14300 Nibong Tebal, Penang
*
Corresponding Author: Email address: miibrahim114@gmail.com
ABSTRACT
Cooling of photovoltaic modules is an important requirement to prevent decrease in the PV
cells efficiency and a considerable reduction in their life span. Therefore, implementing a
proper cooling method can improve the electrical efficiency and minimize the rate of cell
maiming, thereby maximizing the overall life span of the PV modules. In this present work,
an experimental study was conducted for a hybrid photovoltaic thermal system using
different cooling flow rates in order to examine the effects of cooling on the PV/T system.
Response surface methodology along with central composite design (CCD) was used to
develop mathematical models, and these models were henceforth validated using analysis of
variance (ANOVA) with regression coefficient values of more 0.900 for response
variables. Design expert software was used to carry out a numerical optimization. The RSM
optimized values were 421.55% and 7.18% for the thermal and electrical efficiency. On the
other hand, the optimum values for the experimental results were 425.01% and 9.45% for the
thermal and electrical efficiencies respectively. The experimental results obtained were in
conformity with the predicted RSM model, which shows that the model can be used for
1
Nomenclature
A Area (m2) DF Degree of freedom
solar radiation ANOVA Analysis of variance
Maximum Voltage
Coefficient Of determination
Maximum current
Useful energy
Heat removal factor Greeks
Mass flow rate
Specific heat capacity Efficiency
T Temperature Superscripts
Abbreviations Thermal
PV Photovoltaic Electrical
PV/T Photovoltaic thermal system
RSM Response surface methodology
TTL Transistor Transistor logic
DC Direct current
1.0 Introduction
The rate at which attention are focused towards renewable energy technologies is gaining
momentum on a daily basis. One of the most practical application of renewable energy is the
use of solar photovoltaic (PV) system which convert solar radiation into electricity (Hu et al.,
2016; Siecker et al., 2017). Studies have shown that only small portion of the ultraviolet
radiation that strikes PV module surface are converted into electricity; the remaining part
becomes a waste heat which hampers the performance of the PV module thereby leading to a
reduction in its electrical efficiency (Abdelrazik et al., 2018; Gaur et al., 2017; Kumar et al.,
2020; Odeh & Behnia, 2009; Siecker et al., 2018). This problem has since then created so
much concern by different scholars and enormous efforts have been expended towards
Most of the researches carried out in trying to proffer possible solutions to the degrading PV
efficiency problem, lead to a new system called the photovoltaic thermal (PV/T) system.
2
These system combines both the PV module and a thermal collector together as a single
entity and can provide both electricity and thermal energy concurrently via a cooling medium
(Kazemian et al., 2021; Su et al., 2017). This is achieved by allowing water to pass through
copper tubes attached to the back of the PV module thereby extracting the excess heat from
the PV module. Since the thermo-physical properties of water are generally known to have
good cooling ability, the PV module tends to operate at a standard operating temperature
(STC), which thereby improves the efficiency of the system and at the same time provide
thermal energy for both industrial and residential applications respectively (Abdelrazik et al.,
2018).
Several cooling techniques have been studied by different researchers based on the type of
cooling method used in the absorber, the PV/T can be classified into the following categories:
air based, water based, combination of water/air based, heat pipe based, concentrated based,
PCM based and nano fluid-based, combination of nano fluid and PCM based PV/T
respectively (Gelis et al., 2022; Su et al., 2017; Yu et al., 2021). Also, PV/T collectors
integrate two different systems i.e., the PV module and the thermal collector into hybrid
system called PV/T system. Depending on the design and method of construction, collectors
are available in different forms ranging from flat plate collectors, heat pipe collectors,
al., 2021).
Moreso, both experimental numerical and analytical work are still ongoing by several
researchers to study the performance evaluation of different PV/T systems. Touafek et al.
(2009) Performed experimental study for a hybrid PV/T system and found out that the hybrid
PV/T yielded more that 80% efficiency. Jaaz et al. (2018) In their work used water jet
impingement to cool compound parabolic photovoltaic thermal system (CP PV/T), and the
results obtained showed that CP PV/T gave better electrical and thermal efficiency compared
3
to the flat plate PV/T system. Rahman et al. (2018) Carried out experimental and numerical
analysis using ANSYS software to test the efficiency of PV/T systems by using different
mass flow rates, it was observed that both the thermal and overall efficiency of the system
were achieved with an increased mass flow rate. Herrando et al. (2014) tried to asses a hybrid
PV and a solar thermal system, and based on the outcome of their work, it was concluded that
the PV/T outperformed the conventional PV. Touafek et al. (2014) developed a prototype
thermal collector using a galvanised plate, this PV/T prototype was studied experimentally
and theoretically and he claimed that it will serve as a good alternative to the other existing
types of collectors. Al-Waeli et al. (2018) conducted an experiment using three different
types PV/T systems: water based, PCM based and nano fluid-based systems. The results of
these systems were compared to that of a conventional PV using three typed of ANN model,
and the output of the model simulation was in agreement with the experimental results carried
out. Sardarabadi et al. (2017) Investigated the effects of nano fluid and Phase change
material (PCM) by using them as a coolant for a PV/T system. Based on the result obtained it
shows that the combination of these two materials increased the efficiency of the system.
Trailing behind several numerical and experimental work carried out by different scholars, a
very important mathematical as well as statistical technique for determining the relationship
experiment, is the use of response surface methodology (RSM). The advantage RSM has
compare to other mathematical models and algorithms such as artificial neural network
(ANN), support vector machine (SVM), genetic algorithms (GA) and ant colony optimization
(ACO), is that it provides more powerful approach in providing satisfactory and adequate
relationship between the connections of input parameters even from a limited experiment
(Elsayed & Lacor, 2011; Rejeb et al., 2020). Also, RSM can be used to solve complex
4
thereby giving much detail information about relevant operating factors (independent
variables) and process responses for the system performances accordingly (Gelis et al., 2022;
Mehmood et al., 2019; Myers et al., 2016; Yesildal et al., 2022). Photovoltaic thermal
system’s electrical and thermal performances as well as optimal flow rate that can provide
best cooling to the PV module, thereby enabling it to perform efficiently under a desired
operating condition can be predicted and analysed using RSM. It is an important technology
and has many application in different areas such as aerospace, automobile, biotechnology for
optimizing performances and improving the design of systems which makes it a concurrent
From among the few studies carried out using RSM method include the work of Kazemian et
al. (2021) who developed different models to predict, electrical power, thermal power,
electrical exergy, thermal exergy and entropy generation for PV/T system incorporated with
PCM using RSM, the developed models yielded a desirability function of 0.85 implying that
the responses were accurately predicted. Also, Rejeb et al. (2020) Used RSM model to
examine the electrical and thermal efficiency behaviour of a nano-based PV/T collector.
From the model developed a strong correlation was achieved to prove that both heat transfer
coefficient and flow rate contributed to the optimal efficiencies achieved during the
experiment. Gelis et al. (2022) Experimentally investigated, the effects of using nano-fluids
on PV/T by applying RSM. The results shows that radiation, flow rate and volumetric
It is evident from the above that response surface methodology (RSM) being a very good
optimization tool has yet not been given much attention by most of the researchers for the
optimization of cooling flow rates in the photovoltaic thermal (PV/T) systems. Hence, the
main objective of this work, was to use the response surface methodology to determine the
optimum cooling flow rate for a hybrid PV/T system. An experimental study of the PV/T
5
system will be performed, using different set of transducers for the entire system’s
instrumentation. This design approach so far, to the best of authors knowledge has not been
implemented by any researcher, as such is a novel idea in the design of PV/T systems.
From the flow chart shown in Fig.1, a step-by-step approach for the research actualization has
been presented. Two similar conventional photovoltaic modules implemented for this work
were sourced, the specifications for the modules are presented in Table 1. A thermal collector
as shown in Fig. 4 was designed and fabricated. The fabricated collector was henceforth
retrofitted to one of the PV modules to serve as the photovoltaic thermal system. The PV/T
and the ordinary PV module were now used to conduct an experimental as discussed in the
subsequent sections.
6
2.2 Description of the (PV/T) system
The schematic diagrams for the hybrid photovoltaic thermal (PV/T) are presented in Fig. 2- 3
which comprises of the PV/T collector, supporting frame, DC pump and hose pipe for the
enabling force circulation of water into the system. The conventional photovoltaic (PV)
modules used for this experiment comprises of two identical units. A thermal collector
comprising of copper tubes as shown in Fig.4 was attached to the rear side of one the PV
modules while the other unit of PV was left without a collector. A Fibre glass material was
used to insulate the modified PV module from all edges before it was covered, in order to
avoid thermal losses. The hybrid water-based PV/T system and the conventional PV were
both mounted sided by side and was set at angle of 90 southwards based on the findings of
(Khatib et al., 2015) in the energy research center of Federal Polytechnic Bida, Niger State
Nigeria as shown in Fig.5. The experimental data for both systems were collected and tested
under the same climatic condition to enable proper validation of the experimental results.
7
Table 1: Specification of the PV module
The experimental set-up diagram is presented in Fig.6. The PV/T system constituted several
components put together ranging from mechanical to electrical components. Table 2 shows a
detail instrumentation for the electrical components used for this experiment. Storage tanks,
supporting frames for both the PV modules and storage tank were part of the mechanical
components used as illustrated in Fig.5. The copper tube exit manifold of the thermal
8
collector was connected to a well-insulated water storage tank fabricated with a stainless-steel
material via a water hose pipe. Direct current (DC) water pump was used to supply a coolant
to the system by means of a forced circulation and in this case, water was used as the coolant.
The flow rate of the base fluid (water) was measured using a flow sensor attached to the exit
manifold of the copper tube which was integrated to the back of PV module. The heat
transfer fluid was circulated through the absorber copper tube manifolds to remove excess
9
In order to have closed flow circuit for the working fluid contained in the storage tank, a
spiral type heat exchanger with a cyclic flow was used to cool the working fluid after being
heated up in the PV/T collector. This heat exchanger allows heat coming out from the outlet
copper manifolds to pass via the water inside the storage tank without the two fluids having a
direct contact. Therefore, the process of forced circulation continues until the fluid
temperature in the tank raises appreciably for domestic and other applications. The
experiment was conducted using parameters illustrated in Table 2. In the process of the
rig to obtain the real experimental data. Four temperature sensors were connected to the inlet
and outlet of the collector and PV surfaces to measure system temperatures respectively.
Also, voltage and current sensors were used to measure the load voltage and current while a
radiation sensor was used to measure solar intensity levels. The electrical structure of the
experimental set-up comprises of: battery, DC loads, charge controller, data acquisition
system. Data logger which is a software program was connected directly to a laptop computer
via USB to Serial (TTL) cable. This program transmits read command to the PV/T system,
then capture the parameters generated simultaneously from the PV/T system and then
10
Fig. 5: Experimental set-up of the PV/T system
The performance of photovoltaic thermal (PV/T) system was evaluated based on thermal and
electrical efficiency (Gelis et al., 2022; Kalateh et al., 2022; Kazemian et al., 2021; Rejeb et
The useful energy of the collector was obtained by exposing the PV/T system to solar
radiation thereby measuring both inlet and outlet temperatures as shown using Eqn1 (Duffie
(1)
The is the mass flow rate, is specific heat capacity of water while - denote the
11
difference between inlet and outlet temperatures of the collector respectively. While the
thermal efficiency ( ) signifies the performance of the PV/T system to generate heat and
is given as the ratio of useful heat gain to the overall incident irradiance on the PV/T
(2)
Where is the solar radiation intensity, is the collector area and is the amount of solar
radiation received by the PV panel.
output power to the overall incident solar radiation (Namjoo et al., 2011):
(3)
Where =PV panel area with and being the maximum current and voltage of the
panel respectively.
2.5 Uncertainty analysis
Several factors ranging from human errors to inherent errors of the equipment’s used during
the experimentation may affect the accuracy of the experimental results. In order to ascertain
the accuracy of the measured data it becomes imperative to eliminate such errors that may
arise. Therefore, the uncertainty equation for both thermal and electrical efficiency of the
PV/T system are estimated using the following equation (Holman, 2012; Kline, 1953).
(4)
12
Where represent the total uncertainty of the dependent variables, while the estimated
Therefore, estimating uncertainty values for the thermal measurement properties will be:
The total uncertainty value obtained was below 5%, which implies that the data obtained
from the measuring devices were reliable and within the acceptable engineering
specifications.
13
Response surface methodology was used to develop a predictive develop that will determine
the relationship between the independent variables and the responses. It was wisely chosen
due to its flexibility and ability to be able to analyses complex interactions of the variables by
accurately approximating the values for the responses at optimum level. This second order
polynomial model is illustrated as follows (Kazemian et al., 2021; Myers et al., 2016):
(5)
Where Y represents response of the model, denotes the total number of factors and
indicates the values for linear, quadratic and interactive coefficients respectively
Central composite design (CCD) was done using four parameters to explore the effects of
variables on the responses. The input parameters considered in this study include: surface
temperature of PV module, useful energy of the collector, solar radiation and mass flow rate
while the responses were thermal efficiency and electrical efficiency respectively. Four
variables along with their coded and uncoded levels have been selected using the RSM design
has presented in Table 4. Similarly, Analysis of variance (ANOVA) was used to validate the
model by establishing the interactions that exist between the process variables and the
several response plots and contours that will enhance clear understanding of the interactions
14
PV surface O
C X1 28 34 40 45.81 52
Temperature
Useful energy gain J/s X2 -260 80 430 760 110
Radiation intensity W/m2 X3 -475 50 575 1100 1625
Flow rate kg/s X4 -0.008 0.036 0.09 0.144 0.196
Design of experiment (DOE) is a systematic series of test, in which decisive changes are
made to input certain factors during an experiment in order to identify causes of significant
changes that will result in the output responses. Thus, Response surface methodology (RSM)
which combines different statistical and numerical techniques for optimization process was
implemented in this study using design expert and ANOVA to investigate the effects of four
different parameters that affect response variables (electrical and thermal efficiency) of a
polynomial equation were computed from the experimental data to predict the values of the
response variables. Regression equations obtained for the two response variables have been
(6)
(7)
Thirty numbers of runs were performed for the RSM experiment using four levels of
independent variables with two responses as presented in Table 5. These experiments were
conducted using central composite designed with coded and uncoded values of independent
15
experimental data actually represented the quadratic model, as it is obvious that coefficient of
determination for thermal and electrical efficiencies were 0.9305 and 0.9711 respectively as
presented in Table 8.
16
Similarly, statistical analysis presented has shown that probability values were < 0.0500
which indicates that the model terms are significant since values with > 0.1000 indicates
that model terms are not significant. It is worth mentioning that both predicted and
experimental values were at close ranges as depicted in and Fig. 7, indicating the accuracy of
the developed model. Table 7 shows -values of 14.34 and 63.78 with less than 0.0001
for both thermal and electrical efficiencies which signifies that the model was reliable and
could be used for predicting both thermal and electrical efficiency with a considerable
accuracy.
17
From the ANOVA results presented in Table 7, it is evident that the most important effects of
independent variables for the electrical efficiency, that emerges in the analysis were
whereas the values for were less significant in the interactions and as such were
discarded in the model developed as presented in Eqn. (7) of the second order polynomial
equation. Additionally, in order to measure the signal to noise ratio, adequate precision values
were calculated and values greater than 4 were obtained:14.490 and 40.138 which shows that
the developed model can be used to navigate the design space to perform predictions
accordingly.
2.998E+0
450.02 14 10 21415.40 45.05 14.34 63.78 0.0001 0.0001
5
1.55 1 1 6018.40 1.55 4.03 2.20 0.0631 0.1544
6018.40
1022.94 5.93 1 1 1022.94 5.93 0.6850 8.39 0.4208 0.0092
12666.15 2.51 1 1 12666.15 2.51 8.48 3.55 0.0107 0.0748
54.80 2.29 1 1 54.80 2.29 0.0367 3.24 0.8507 0.0878
<0.000
4558.27 43.11 1 1 4558.27 43.11 3.05 61.03 0.1011
1
11311.19 0.0727 1 1 11311.19 0.0727 7.57 0.1029 0.0148 0.7519
1538.72 6.37 1 1 1538.72 6.37 1.03 9.01 0.3262 0.0073
747.31 0.0945 1 1 747.31 0.0945 0.5004 0.1337 0.4902 0.7187
919.54 0.6631 1 1 919.54 0.6631 0.6158 0.9387 0.4448 0.3448
6883.86 0.6543 1 1 6883.86 0.6543 4.61 0.9262 0.0485 0.3479
5055.00 1 5055.00 3.38 0.0857
3268.45 1 3268.45 2.19 0.1597
39969.12 1 39969.12 26.76 0.0001
3341.05 1 3341.05 2.24 0.1555
Residua
22400.41 13.42 15 19 1493.36 0.7064
l
3.222E+0
Total 463.95 29 29
5
Fig. 6 presents the relationship between the experimental values versus simulated values by
applying response surface methodology. This a nonlinear graph exhibiting similar trend
18
geometry. Highest thermal efficiency of about 400% was recorded at a period when the
radiation was at its maximum and the lowest thermal efficiency recorded to be 20% when the
Fig.7: Comparison between PV/T system with cooling and conventional PV module
Fig. 7, shows the comparison between the two different photovoltaic systems used for the
experimental study. A thermal collector was retrofitted to one of the PV modules as shown in
Fig. 5 while the other PV was left ordinarily without a collector. The figure shows clearly that
of solar radiation while the temperature of PV/T system with cooling method never exceeded
43 0C throughout the period of the experiment. This was as a result of heat extraction
19
Table 9: Comparison between predict optimization values and experimental results
Numbe
r
Predicte experiment predicte experiment
d al d al
1018.2
1 43.58 760 9 0.144 421.55 425.01 7.18 9.45
2 43.16 760 878.68 0.138 471.96 450.22 6.48 8.33
Three-dimensional (3 D) response surface and contour plots for the fitted quadratic model are
shown in Fig. 8 (a)-(c). As could be observed, the two plots were presented side by
(a)
(b)
20
(c)
Fig. 8: Response surface and contours plots for as a function of (a) flow rate and T
surface (b) radiation and T surface and (c) useful energy and T surface respectively.
(a)
(b)
21
(c)
Fig. 9: Response surface and contours plots for as a function of (a) radiation and useful
energy (b) flow rate and radiation (c) flow rate and useful energy respect to input variables.
(a)
(b)
22
(c)
Fig. 10: Response surface and contours and contour plots for as a function of (a) useful
energy and T surface (b) radiation and T surface (c) flow rate and T surface.
(a
)
23
(b)
(c)
Fig. 11: Response surface and contours plots for as a function of (a) useful energy and
radiation (b) flow rate and radiation (c)flow rate and useful energy respectively.
24
(a)
(b)
Fig. 12: Diagnostic plots for (a) predicted versus actual and (b) normal plots of residuals for
side because simply because the contours plots which are those plots placed by the right-hand
side, assist in giving clear visualization of response surface plots by showing the complexity
of interactions existing between the control factors and responses. Fig. 8(a) shows the
combined effect of surface temperature and flow rate on the thermal efficiency of the
photovoltaic thermal system. The two independent variables had a linear effect on the
response variable. The plots indicate that maximum thermal efficiency is about 400 0C with a
underneath the PV surface by heat transfer fluid. Fig. 8(b) depicts the interactive effect
between radiation and surface temperature on the thermal efficiency. The thermal efficiency
of the PV/T system is a function of radiation and surface temperature. Thus, changes in
25
surface temperature produces resulted to increase in at higher solar intensity than at
lower solar intensity. Fig. 9(c) exhibited similar physical phenomenon, since increase in
radiation improves the heat transfer coefficient by conduction between the PV and absorber
(a)
(b)
Fig. 13: Diagnostic plots for (a) interaction (b) perturbation, for both thermal and electrical efficiency.
Fig. 9(a)-(c) shows different interactions of control factors on thermal efficiency. The
influence of useful energy and radiation on is represented in Fig. 9(a). The two factors
have significant effect on the response variable, as both variables increase with an increase in
of the system. Useful energy of photovoltaic system shows how well the collector is
performing. This implies how efficiently the collector is extracting heat underneath the PV
module via the heat transfer medium (Duffie & Beckman, 2013). Fig. 9(b) explicate the
26
Fig.14: Variation between thermal efficiency and mass flow rate
combine influence of radiation and flow rate on , increase in radiation improves heat
transfer by conduction, as such a corresponding increase in the mass flow rate will result to
more extraction of thermal energy from the surface of the PV thereby increasing the overall
thermal efficiency of the system. This was in agreement with the work carried out by
(Gelis et al., 2022; Javidan & Moghadam, 2021; Rejeb et al., 2020). Further elaboration has
been presented in Fig. 9(c) where the contour plots depicted maximum thermal efficiency at
300% and useful energy at 450 with a corresponding flow rate of 0.068 . This
implies that substantial amount of heat was extracted underneath PV surface as a result of
27
thermal conduction that was taking place between the heat transfer fluid and the absorber
At this juncture, it is crucial to note that when considering Fig. 8-9 as a single entity, shows
that flow rate, solar intensity, collector heat removal factor and surface temperature of the PV
module have positive effect on thermal efficiency enhancement. Similarly, the variations in
electrical efficiency with surface temperature, with respect to useful energy, radiation and
mass flow rate were presented in Fig. 10 (a), (b) and (c) respectively. Critically observing
Fig. 10(a) shows that both PV surface temperature and useful energy exhibit an inverse
relationship with the thermal efficiency. These two factors have a negative effect on the
electrical efficiency.
28
It can be seen from Fig 10(b) that electrical efficiency and radiation were at maximum when
the surface temperature was low. The reason being that at an initial point the surface
temperature was high but when cooling began it gradually decreases. This decrease was as a
result of the cooling effect over the PV surface temperature which thereby increases the
electrical efficiency, and is in line with the work carried out by (Deng et al., 2020; Kazemian
et al., 2021). Similarly, the effects of surface temperature and flow rate are presented in Fig.
10(c). There is an inverse relationship between the surface temperature and the electrical
efficiency. Since increase in mass flow rate of the heat transfer fluid leads to decrease in
surface temperature of the PV module which eventually improves the electrical efficiency of
the system. PV modules work optimally when its surface temperature is close to the standard
Fig.11(a)- (c) illustrates the interactive effect between radiation, useful energy and mass flow
rate on the electrical efficiency. The influence of useful energy and radiation on the electrical
efficiency is presented in Fig. 11(a) and it is seen that increase in the useful energy as a result
of increase the electrical efficiency of the PV at a higher solar intensity than at lower solar
intensity (Goswami, 2022). Also, considering Fig. 11(b) and (c), by carefully examining the
interactions taking place, it could be deduced that the rate of useful energy extracted by the
collector is directly proportional to the quantity of radiation absorbed from the PV surface
module. Basically, is expressed in terms of the amount of heat transfer coefficient carried
away in the fluid passing via the collector as presented in Eqn. (2) (Duffie & Beckman,
2013). In essence, increase in electrical efficiency of the PV/T system arises as a result of the
increased mass flow rate which conversely lead to the decrease of the PV surface
29
Moreso, probability plots with strong coefficient of determination values have been
presented in Fig. 12(a). Thus, it was observed that a strong correlation exists between the
RSM predicted output and the experimental results. Accessing model fitness, values are
pertinent indicators to be considered, where values of close to 1 indicate the best fitness
(Zhang et al., 2022). Fig. 12(b) illustrate the probability plots for both and , which
displays how the residuals have been evenly distributed along the straight line with their
deviations very close to the straight line. This implies that there is a strong accuracy in the
developed model.
Nevertheless, in order to examine critical interactive effects between the operating variables
and the response variables, perturbation and interaction plots were also presented in Fig.
13(a) and (b) respectively. By carefully observing the thermal efficiency plots, it could be
observed that solar intensity, surface temperature of the PV module, useful energy and flow
rate respectively were the most influential factors that enhancing the thermal efficiency of the
PV/T system since all these factors increase with a corresponding increase in the thermal
efficiency. Conversely, only radiation and flow rate were noted to be increasing as electrical
efficiency increases. Both temperature and useful energy were observed declining while the
electrical efficiency was increasing. Interestingly, this inverse relationship could be attributed
to the fact that there is always a decrease in the electrical output efficiency each time PV
surface is overheated due to exposure to intense solar radiation (Siecker et al., 2017).
Thus, the best way to proffer possible solution to problem above is by introducing a heat
transfer cooling fluid that can withdraw this excess heat which has risen and accumulated
inside the collector. Therefore, when cooling fluid is introduced, gradually the excess heat
will be unleashed out and both useful energy as well as the surface temperature will steadily
30
The optimal values obtained for the two response variables have been depicted in Fig. 14 and
15 respectively. Numerical optimization was performed using the design expert software to
determine the optimum values for both thermal and electrical efficiencies. The optimum
values suggested by the software were 421.55% with a mass flow rate of 0.144 kg/s for the
thermal efficiency as shown in Fig. 15, while 7.18% with a corresponding mass flow rate of
0.144 kg/s for the electrical efficiency as illustrated in Fig. 16. These values when compared
presented in Table 9.
Design expert software was used to produce three-dimensional response surface plots and
achieve these, several plots were generated by varying useful energy, radiation and flow rate
within experimental ranges while keeping temperature constant as illustrated in Fig. 9 – 12.
Numerical optimization was henceforth executed in order determine the optimum operating
conditions for PV/T system using the optimization tool encamped inside the design expert
minimum level of surface temperature, maximum flow rate, useful energy and radiation were
parameters were found and two solutions with the maximum desirability value were selected
as the optimized operating condition for the photovoltaic thermal (PV/T) system.
The optimized operating variables which were obtained for both electrical and thermal
efficiencies via RSM optimization approach were further explored by conducting another two
different experiments for authentication purposes. This was purposely done in order to be
31
able to compare the RSM model results with the experimental result as presented in Table 8
which were found to be similar as compared to the work of (Gelis et al., 2022; Kazemian et
al., 2021; Rusdi et al., 2019). Thus, for the RSM model, optimum values suggested for both
thermal and electrical efficiencies were 421.55% and 7.18% for the initial optimization while
471.96% and 6.48% for the second numerical optimization. Similarly, the optimum values for
both thermal and electrical efficiencies were 425.01% and 9.45% for the first experiment
conducted while 450.22% and 8.33% for the second experimental respectively. The
experimental results obtained were highly in agreement with the predicted RSM model,
which shows that the model can be used for similar response predictions.
4.0 Conclusion
In this paper, an experimental work for a water-based PV/T system was conducted using
different sets of transducers for the entire system’s instrumentation. Concisely, some of the
salient results and achievements explored from this work are hereby summarized below:
modelled and analyzed using RSM with four deferent sets of independent
variables.
The values for the two models developed were 0.9305 and 0.9711 which
shows that the mathematical model was reliable and can be used for predictions
Optimum values were obtained through numerical optimization, with 43.5 0C,
760 J/s, 1018.29 W/m2 and 0.144 kg/s being suggested values for surface
temperature, useful energy, solar radiation and mass flow rate respectively.
Experimental confirmation test was carried out under two optimum optimization
variables and were authenticated, access and verified by comparing the predicted
32
values alongside with the experimental results.
The predicted values were well in conformity with the experimental results which
therefore attest to the veracity and accuracy for the predicted models.
referenc
e therm elect total eff
1 35.33 12.77 48.1
2 61.3 61.3
3 7.5 51.6 59.1
4 9 30 39
5 11.6 58.6 70.2
6 45 13 58
7 11 51 62
8 10.4 55 65.4
9 10.15 45 55.15
References
Abdelrazik, A. S., Al-Sulaiman, F., Saidur, R., & Ben-Mansour, R. (2018). A review on recent
development for the design and packaging of hybrid photovoltaic/thermal (PV/T) solar
systems. Renewable and Sustainable Energy Reviews, 95, 110-129.
Aberoumand, S., Ghamari, S., & Shabani, B. (2018). Energy and exergy analysis of a photovoltaic
thermal (PV/T) system using nanofluids: An experimental study. Solar Energy, 165, 167-177.
Al-Waeli, A. H., Sopian, K., Kazem, H. A., Yousif, J. H., Chaichan, M. T., Ibrahim, A., Mat, S., & Ruslan,
M. H. (2018). Comparison of prediction methods of PV/T nanofluid and nano-PCM system
using a measured dataset and artificial neural network. Solar Energy, 162, 378-396.
Deng, H., Yang, X., Tian, R., Hu, J., Zhang, B., Cui, F., & Guo, G. (2020). Modeling and optimization of
solar thermal-photovoltaic vacuum membrane distillation system by response surface
methodology. Solar Energy, 195, 230-238.
Duffie, J. A., & Beckman, W. A. (2013). Solar Engineering of Thermal Processes (Fourth ed.).
Elsayed, K., & Lacor, C. (2011). Modeling, analysis and optimization of aircyclones using artificial
neural network, response surface methodology and CFD simulation approaches. Powder
technology, 212(1), 115-133.
Gaur, A., Ménézo, C., & Giroux, S. (2017). Numerical studies on thermal and electrical performance
of a fully wetted absorber PVT collector with PCM as a storage medium. Renewable Energy,
109, 168-187.
Gelis, K., Celik, A. N., Ozbek, K., & Ozyurt, O. (2022). Experimental investigation into efficiency of
SiO2/water-based nanofluids in photovoltaic thermal systems using response surface
methodology. Solar Energy, 235, 229-241.
Goswami, D. Y. (2022). Principles of solar engineering: CRC Press.
Herrando, M., Markides, C. N., & Hellgardt, K. (2014). A UK-based assessment of hybrid PV and solar-
thermal systems for domestic heating and power: system performance. Applied Energy, 122,
288-309.
Holman, J. P. (2012). Experimental methods for engineers.
33
Hu, J., Chen, W., Yang, D., Zhao, B., Song, H., & Ge, B. (2016). Energy performance of ETFE cushion
roof integrated photovoltaic/thermal system on hot and cold days. Applied Energy, 173, 40-
51.
Jaaz, A. H., Sopian, K., & Gaaz, T. S. (2018). Study of the electrical and thermal performances of
photovoltaic thermal collector-compound parabolic concentrated. Results in Physics, 9, 500-
510.
Javidan, M., & Moghadam, A. J. (2021). Experimental investigation on thermal management of a
photovoltaic module using water-jet impingement cooling. Energy Conversion and
Management, 228, 113686.
Kalateh, M. R., Kianifar, A., & Sardarabadi, M. (2022). Energy, exergy, and entropy generation
analyses of a water-based photovoltaic thermal system equipped with clockwise counter-
clockwise twisted tapes: An indoor experimental study. Applied Thermal Engineering,
118906.
Kazemian, A., Khatibi, M., & Ma, T. (2021). Performance prediction and optimization of a
photovoltaic thermal system integrated with phase change material using response surface
method. Journal of Cleaner Production, 290, 125748.
Khatib, T., Mohamed, A., Mahmoud, M., & Sopian, K. (2015). Optimization of the tilt angle of solar
panels for Malaysia. Energy sources, part A: Recovery, utilization, and environmental effects,
37(6), 606-613.
Kline, S. J. (1953). Describing uncertainty in single sample experiments. Mech. Engineering, 75, 3-8.
Kumar, R. R., Samykano, M., Pandey, A., Kadirgama, K., & Tyagi, V. (2020). Phase change materials
and nano-enhanced phase change materials for thermal energy storage in photovoltaic
thermal systems: A futuristic approach and its technical challenges. Renewable and
Sustainable Energy Reviews, 133, 110341.
Lupu, A., Homutescu, V., Balanescu, D., & Popescu, e. A. (2018). A review of solar photovoltaic
systems cooling technologies. Paper presented at the IOP Conference Series: Materials
Science and Engineering.
Mehmood, T., Ahmed, A., Ahmed, Z., & Ahmad, M. S. (2019). Optimization of soya lecithin and
Tween 80 based novel vitamin D nanoemulsions prepared by ultrasonication using response
surface methodology. Food chemistry, 289, 664-670.
Myers, R. H., Montgomery, D. C., & Anderson-Cook, C. M. (2016). Response surface methodology:
process and product optimization using designed experiments: John Wiley & Sons.
Namjoo, A., Sarhaddi, F., Sobhnamayan, F., Alavi, M., Mahdavi Adeli, M., & Farahat, S. (2011). Exergy
performance analysis of solar photovoltaic thermal (PV/T) air collectors in terms of exergy
losses. Journal of the Energy Institute, 84(3), 132-145.
Odeh, S., & Behnia, M. (2009). Improving photovoltaic module efficiency using water cooling. Heat
Transfer Engineering, 30(6), 499-505.
Pathak, S. K., Sharma, P. O., Goel, V., Bhattacharyya, S., Aybar, H. Ş., & Meyer, J. P. (2022). A detailed
review on the performance of photovoltaic/thermal system using various cooling methods.
Sustainable Energy Technologies and Assessments, 51, 101844.
Rahman, S., Sarker, M., Mandal, S., & Beg, M. (2018). Experimental and Numerical Analysis of a
Stand-Alone PV/T System to Improve its Efficiency. Sch J Appl Sci Res, 1, 28-33.
Rejeb, O., Ghenai, C., Jomaa, M. H., & Bettayeb, M. (2020). Statistical study of a solar nanofluid
photovoltaic thermal collector performance using response surface methodology. Case
Studies in Thermal Engineering, 21, 100721.
Rusdi, M., Abdullah, M., Chellvarajoo, S., Aziz, A., Abdullah, M., Rethinasamy, P., Veerasamy, S., &
Santhanasamy, D. G. (2019). Stencil printing process performance on various aperture size
and optimization for lead-free solder paste. The International Journal of Advanced
Manufacturing Technology, 102(9), 3369-3379.
34
Sardarabadi, M., Passandideh-Fard, M., Maghrebi, M.-J., & Ghazikhani, M. (2017). Experimental
study of using both ZnO/water nanofluid and phase change material (PCM) in photovoltaic
thermal systems. Solar Energy Materials and Solar Cells, 161, 62-69.
Siecker, J., Kusakana, K., & Numbi, B. (2018). Economic analysis of photovoltaic/thermal systems with
forced circulation under optimal switching control. Paper presented at the 2018 International
Conference on the Domestic Use of Energy (DUE).
Siecker, J., Kusakana, K., & Numbi, e. B. (2017). A review of solar photovoltaic systems cooling
technologies. Renewable and Sustainable Energy Reviews, 79, 192-203.
Su, D., Jia, Y., Lin, Y., & Fang, G. (2017). Maximizing the energy output of a photovoltaic–thermal
solar collector incorporating phase change materials. Energy and Buildings, 153, 382-391.
Touafek, K., Haddadi, M., & Malek, A. (2009). Experimental study on a new hybrid photovoltaic
thermal collector. Applied solar energy, 45(3), 181-186.
Touafek, K., Khelifa, A., & Adouane, M. (2014). Theoretical and experimental study of sheet and
tubes hybrid PVT collector. Energy Conversion and Management, 80, 71-77.
Yesildal, F., Ozakin, A. N., & Yakut, K. (2022). Optimization of operational parameters for a
photovoltaic panel cooled by spray cooling. Engineering Science and Technology, an
International Journal, 25, 100983.
Yu, Q., Chen, X., & Yang, H. (2021). Research progress on utilization of phase change materials in
photovoltaic/thermal systems: A critical review. Renewable and Sustainable Energy Reviews,
149, 111313.
Zhang, S., Jing, J., Qin, M., Zhang, W., Shan, Y., & Cheng, Y. (2022). Experimental study and models of
the settling of sand in heavy oil. Journal of Petroleum Science and Engineering, 110930.
35