GENERAL NOTE: NORTH : LAND KEY :

1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs GENERAL NOTES :
8. All smoke management system and elevators shall be
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
(within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
11. Emergency light and exit signs shall be provided according to (UAE fire
and life safety code and NFPA 101)
12. All structure elements shall have the fire resistance rating according to
(NFPA 5000 and UAE fire and life safety code)
13. All stairways shall be provided with two ways fire telephone
communication.
14. All portions of these building and common and services areas shall be
fully cover by smoke detections and fully covered by voice announcement
system according to (NFPA 72)
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
16. Standpipe system shall be provided in these building according to (NFPA 14)
FIRE PUMP 17. All fire door and windows shall be according to (NFPA 80)
Capacity= 250 GPM and UAE fire and life safety code
WATER TANK PERGOLA
UNDER GROUND 18. All types of smoke management systems (include pressure difference
ENGINEER REGISTRATION CARD :

C79
AC MACHINE LOUVERS
FIRE WATER TANK between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
Capacity= 11250 Gal. 92B and UAE fire and life safety code and shall be submitted in
shop drawing submittal.
19. All interior finishing material shall be provided as (UAE fire and life

C78
AC MACHINE LOUVERS AC MACHINE LOUVERS AC MACHINE LOUVERS
safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
life safety code and NFPA requirement
21. CO² monoxide detector shall be provided to detect the CO² concentration
AC MACHINE LOUVERS 22. Central battery system for emergency lighting systems and other system
AC MACHINE LOUVERS AC MACHINE LOUVERS AC MACHINE LOUVERS
shall be provided according to UAE fire and life safety code
23. Internal roads indicating how fire-men emergency tracks will maneuver on
the site and occupants assemblies areas
24. Total duration time of full evacuation of the building at discharging level,

S/S
up to assemblies' areas (assemblies' areas shall be sized according total
number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
CAT LADDER roofing Sandwich panel system shall be provided as UAE fire and life safety OWNER:
AC MACHINE LOUVERS AC MACHINE LOUVERS
Chapter 1, after tender is approved bring shop drawing and support
information for civil defense approval

C80
26. Fire pump and fire water tank shall be listed and tested according to civil
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal. CONSULTANT : BASALT ENGINEERING CONSULTANCY
29. All penetrations through fire resistance rated walls shall be protected by
approved fire stop system and materials, installed and tested in accordance PRINCIPAL CONSULTANT
with ASTM E 814 or UL 1479 TEL: +97124436366, FAX: +97124436367
30. All means of egress components details and dimensions shall be provided DEFENSE ROAD, ABU DHABI, U.A.E.
and constructed according to (UAE fire and life safety code and NFPA 101 and 5000) P.O. BOX 33848, ABU DHABI, U.A.E.
31. Consultant and contractors shall comply with UAE fire and life safety E.mail:info@basaltconsultant.com
code chapter 12 in terms of requirements of building under construction WEB: WWW.BASALTCONSULTANT.COM

32. Emergency action plan shall be implementing in these buildings according


to UAE fire and life safety code.
33. Consultant and contractors shall comply with UAE fire and life safety
DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
code Chapter 1 in terms of the requirement of balcony, terrace and windows
34. Private fire hydrant shall provided around these building as per (UAE fire
PROJECT NAME :
and life safety code)

35. Consultant and contractors must comply with the general notes and
applicable codes and standards even if the code requirement was missed
COMMERCIAL BUILDING
during plan review.
36. This building shall be provided with HASSANTUK devices and shall be
connected with fire alarm control Panel.
ZONE : PLOT NO :
37. Fire lift shall be provided in this building according in UAE fire and life
safety code.
AL NAHYAN C79
* All portion of this building shall be fully covered by
smoke detection system and fully covered by SECTOR NO :
announcement system according to UAE fire and life
safety code and NFPA 72
E19_02

* Exit sign and emergency lighting shall be providing in this


building according to UAE fire and life safety code and NFPA PROJECT DESCRIPTION :
* All standpipe system in this building shall be used as
dry riser system according to NFPA 14

* All portion of this building shall be fully protected by


automatic sprinklers system according to UAE fire and life
A010-SITE
PLAN SCALE :

LEGEND
NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD DRAWING TITLE :
ASS AUTOMATIC SPRINKLER SYSTEM
SITE PLAN
OCCUPANT LOAD
FLOOR NO. USAGE AREA (M2 ) FACTOR(M2/PERSON) NO. OF OCCUPANTS TYPE OF FIRE FIGHTING TYPE OF SMOKE MANAGEMENT SYSTEM BREECHING INLET
GROUND SHOPS 231.63 SQ.M 4.6 50
WRS WET RISER SYSTEM
SPRINKLER SYSTEM
EQUIPMENT AREA 31.72 SQ.M 27.9 01
& FOAM SPRINKLER SYSTEM & DRY RISER, FIRE ALARM AND
SERVICES AREA 103.35 SQ.M 27.9 04 DETECTION SYSTEM,FIRE HOSE CABINET NA CIVIL DEFENSE VEHICLE

TOTAL 366.7 SQ.M 55


CAS CLEAN AGENT SYSTEM
DRAWING NO : REVISION NO:
MEZZANINE OFFICES 258.21 SQ.M 9.3 04
SPRINKLER SYSTEM + DRY RISER, FIRE ALARM AND
BUILDING
AFSS AUTOMATIC FOAM SPRINKLER SYSTEM A010 00
SERVICES AREA 101.59 SQ.M 27.9 28
DETECTION SYSTEM,FIRE HOSE CABINET
TOTAL 359.8 SQ.M 32 PASS PRE ACTION SPRINKLER SYSTEM
ACCESS WAY FOR CIVIL DEFENSE VEHICLES SUBMISSION DATE : SCALE :
APARTMENT -1 61.38 SQ.M 18.6 3
1/100 A2
RESIDENTIAL

TYPICAL FLOOR
APARTMENT -2 74.17 SQ.M 18.6 4
ASSEMBLY POINT
SPS STAIRCASE PRESSURIZATION SYSTEM
08-01-2023
1&2 APARTMENT -3 62.08 SQ.M 18.6 4 SPRINKLER SYSTEM + DRY RISER, FIRE ALARM AND
DETECTION SYSTEM,FIRE HOSE CABINET CSES CORRIDOR SMOKE EXTRACTION SYSTEM
APARTMENT -4 61.30 SQ.M 18.6 3 PROJECT ID :
APARTMENT -5

APARTMENT -6
60.40 SQ.M

61.56 SQ.M
18.6

18.6
4

4
EXISTING FIRE HYDRANT LOCATION WCFSS WET CHEMICAL FIRE SUPPRESSION SYSTEM B1M-2022-004027-CD02
SERVICES AREA 80.11 SQ.M 27.9 7 SD SMOKE DETECTOR

SUB-TOTAL 461.0 SQ.M 29 NA


ACCESS WAY FOR CIVIL DEFENSE VEHICLE OFFICE USE ONLY :
HD HEAT DETECTOR
TOTAL FOR 1 & 2 922.00 SQ.M 58

APARTMENT -1 RESIDENTIAL 52.16 SQ.M 18.6 3 EGRESS PATH


BSES BASEMENT SMOKE EXTRACTION SYSTEM
APARTMENT -2 RESIDENTIAL 84.79 SQ.M 18.6 5
ROOF FLOOR

32.64 SQ M 27.9 1
BUILDING LIMIT
GUARD RM AREA LP LIFT PRESSURIZATION
SPRINKLER SYSTEM + DRY RISER, FIRE ALARM AND
EQUIPMENT AREA 35.16 SQ M 27.9 1 DETECTION SYSTEM,FIRE HOSE CABINET
PLOT LIMIT MV MECHANICAL VENTILATION
SERVICES AREA 72.25 SQ M 27.9 3

TOTAL 277 SQ.M 13

TOTAL AREA FOR BUILDING (m² ) 1925.5 SQ M 158


AREA TYPE OF SMOKE
LOCATION MANAGMENT SYSTEM

BUILDING NO. TYPE OF AREA OF THE


AREA OF THE
BUILDING REQUIRED REQUIRED APPLIED TYPICAL&MEZZANINE
OCCUPANCY LARGEST FLOOR (INDUSTRIAL & PERIMETER OF THE PERIMETER ON PERIMETER ON PERIMETER ON COMPLY
NA
STORAGE) BUILDING CODE BUILDING BUILDING
FLOOR
(18.20 + 25.48)
1 COMMERCIAL 461.00 SQ.M N/A 87.36 1/6 14.56 =43.68 YES
NORTH : LAND KEY :

GENERAL NOTE:
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
GENERAL NOTES :
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
(within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
11. Emergency light and exit signs shall be provided according to (UAE fire
and life safety code and NFPA 101)
Capacity= 250 GPM 12. All structure elements shall have the fire resistance rating according to
(NFPA 5000 and UAE fire and life safety code)
PUMP ROOM 13. All stairways shall be provided with two ways fire telephone
communication.
14. All portions of these building and common and services areas shall be
fully cover by smoke detections and fully covered by voice announcement
SHOP-1 M
SHOP-2 system according to (NFPA 72)

AREA=58.5 m²
80 3C AREA=61.4 m²
15. All portions of these building shall be fully protected by automatic
1C 96 sprinklers system according to (NFPA 13) and UAE fire and life safety code
M 16. Standpipe system shall be provided in these building according to (NFPA 14)
17. All fire door and windows shall be according to (NFPA 80)
and UAE fire and life safety code
27
53
18. All types of smoke management systems (include pressure difference ENGINEER REGISTRATION CARD :
between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
CM
92B and UAE fire and life safety code and shall be submitted in
CM
shop drawing submittal.
19. All interior finishing material shall be provided as (UAE fire and life
76
22 safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
life safety code and NFPA requirement
F.H.C
FHC 21. CO² monoxide detector shall be provided to detect the CO² concentration
W.C 22. Central battery system for emergency lighting systems and other system
shall be provided according to UAE fire and life safety code
UP UP 23. Internal roads indicating how fire-men emergency tracks will maneuver on
the site and occupants assemblies areas
UP 24. Total duration time of full evacuation of the building at discharging level,
UP LIFT LOBBY up to assemblies' areas (assemblies' areas shall be sized according total
number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
UP roofing Sandwich panel system shall be provided as UAE fire and life safety OWNER:
W.C Chapter 1, after tender is approved bring shop drawing and support
information for civil defense approval
26. Fire pump and fire water tank shall be listed and tested according to civil
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
LIFT-02 LIFT-01 as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
892
CM according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal.
29. All penetrations through fire resistance rated walls shall be protected by CONSULTANT : BASALT ENGINEERING CONSULTANCY
approved fire stop system and materials, installed and tested in accordance
with ASTM E 814 or UL 1479 PRINCIPAL CONSULTANT
ELEC.ROOM 30. All means of egress components details and dimensions shall be provided TEL: +97124436366, FAX: +97124436367
and constructed according to (UAE fire and life safety code and NFPA 101 and 5000)
AREA=9.25 m² SHOP-3 DEFENSE ROAD, ABU DHABI, U.A.E.
SHOP-4 ENTRANCE AREA=53.4 m² 31. Consultant and contractors shall comply with UAE fire and life safety P.O. BOX 33848, ABU DHABI, U.A.E.

CM
code chapter 12 in terms of requirements of building under construction E.mail:info@basaltconsultant.com
AREA=38.4 m² 807
LOBBY 32. Emergency action plan shall be implementing in these buildings according WEB: WWW.BASALTCONSULTANT.COM
to UAE fire and life safety code.
33. Consultant and contractors shall comply with UAE fire and life safety
code Chapter 1 in terms of the requirement of balcony, terrace and windows
DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
34. Private fire hydrant shall provided around these building as per (UAE fire

CCTV-SECURITY
and life safety code) PROJECT NAME :
35. Consultant and contractors must comply with the general notes and
AREA=5.00 m²
applicable codes and standards even if the code requirement was missed
during plan review. COMMERCIAL BUILDING
36. This building shall be provided with HASSANTUK devices and shall be
connected with fire alarm control Panel.
37. Fire lift shall be provided in this building according in UAE fire and life
safety code.
ZONE : PLOT NO :
* All portion of this building shall be fully covered by
smoke detection system and fully covered by AL NAHYAN C79
announcement system according to UAE fire and life
UP safety code and NFPA 72
SECTOR NO :
* Exit sign and emergency lighting shall be providing in this E19_02
building according to UAE fire and life safety code and NFPA

* All standpipe system in this building shall be used as


dry riser system according to NFPA 14 PROJECT DESCRIPTION :
* All portion of this building shall be fully protected by
automatic sprinklers system according to UAE fire and life

A100-GROUND
FLOOR SCALE :
PLAN

TYPE OF FIRE PROTECTION


DRAWING TITLE :
AREA FF FA FHC GROUND FLOOR PLAN
LOCATION
LV

FD2

GROUND FLOOR SPRINKLER FIRE ALARM & FD1 DRAWING NO : REVISION NO:
DRS+FHC WSS
SMOKE DETECTION SYSTEM
CAS
A100 00
FSS
GROUND FLOOR SUBMISSION DATE : SCALE :

NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD 08-01-2023 1/100 A2
OCCUPANT LOAD PROJECT ID :
FLOOR NO. USAGE AREA (M2 ) FACTOR(M2/PERSON) NO. OF OCCUPANTS
EXIT DISCHARGE CAPACITIES FOR STAIR
B1M-2022-004027-CD02
SHOPS 231.63 SQ.M 4.6 50
STAIR mm PER NUMBER OF ACTUAL OFFICE USE ONLY :
GROUND EQUIPMENT AREA OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH
31.72 SQ.M 27.9 01 PERSON OCCUPANT OCCUPANT

SERVICES AREA 103.35 SQ.M 27.9 04 Stair 1 BUSINESS 1200 mm 7.6 158 persons 23 persons

Stair 2 BUSINESS 1200 mm 7.6 158 persons 23 persons


366.7 SQ.M 55
316 persons

EXIT DISCHARGE CAPACITIES FOR STAIR DOOR FIRE FIGHTING SYSTEM IN SERVICE ROOMS

NUMBER OF ACTUAL ROOM NAME SUPPRESSION SYSTEM TYPE OF SMOKE


DOOR mm PER SI.NO.
OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH MANAGMENT SYSTEM
PERSON OCCUPANT OCCUPANT
1 GARBAGE ROOM - FIRE EXTINGUISHER
Stair 1-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
2 FIRE PUMP ROOM - FIRE EXTINGUISHER + SPRINKLER SYSTEM NA
Stair 2-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
3 ELEC. ROOM - FIRE EXTINGUISHER
400 persons
NORTH : LAND KEY :

GENERAL NOTE:
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade GENERAL NOTES :
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
(within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
OFFICE-3 OFFICE-2 OFFICE-1 11. Emergency light and exit signs shall be provided according to (UAE fire
AREA 37.7 m² AREA 31.4 m² AREA 44.1 m² and life safety code and NFPA 101)
12. All structure elements shall have the fire resistance rating according to
25 (NFPA 5000 and UAE fire and life safety code)
14 13. All stairways shall be provided with two ways fire telephone
CM
communication.
TOILET 14. All portions of these building and common and services areas shall be
fully cover by smoke detections and fully covered by voice announcement
system according to (NFPA 72)
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
16. Standpipe system shall be provided in these building according to (NFPA 14)
17. All fire door and windows shall be according to (NFPA 80)

CM
and UAE fire and life safety code
18. All types of smoke management systems (include pressure difference ENGINEER REGISTRATION CARD :
35
27 between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
92B and UAE fire and life safety code and shall be submitted in
O.D.F F.H.C shop drawing submittal.
FHC 19. All interior finishing material shall be provided as (UAE fire and life
safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
2048 CM life safety code and NFPA requirement
1172 CM LOBBY 21. CO² monoxide detector shall be provided to detect the CO² concentration
22. Central battery system for emergency lighting systems and other system
shall be provided according to UAE fire and life safety code
23. Internal roads indicating how fire-men emergency tracks will maneuver on
UP the site and occupants assemblies areas
24. Total duration time of full evacuation of the building at discharging level,
up to assemblies' areas (assemblies' areas shall be sized according total
FD2 number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
roofing Sandwich panel system shall be provided as UAE fire and life safety
OWNER:
LIFT-02 ELEC. LIFT-01 Chapter 1, after tender is approved bring shop drawing and support
information for civil defense approval
PANTRY 26. Fire pump and fire water tank shall be listed and tested according to civil
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal.
29. All penetrations through fire resistance rated walls shall be protected by CONSULTANT : BASALT ENGINEERING CONSULTANCY
approved fire stop system and materials, installed and tested in accordance
OFFICE-4 OFFICE-5 OFFICE-6 with ASTM E 814 or UL 1479 PRINCIPAL CONSULTANT
AREA 30.1 m² AREA 42.4 m² AREA 44.1 m² 30. All means of egress components details and dimensions shall be provided TEL: +97124436366, FAX: +97124436367
and constructed according to (UAE fire and life safety code and NFPA 101 and 5000)
2 CM DEFENSE ROAD, ABU DHABI, U.A.E.

213 31. Consultant and contractors shall comply with UAE fire and life safety P.O. BOX 33848, ABU DHABI, U.A.E.
code chapter 12 in terms of requirements of building under construction E.mail:info@basaltconsultant.com
32. Emergency action plan shall be implementing in these buildings according WEB: WWW.BASALTCONSULTANT.COM
to UAE fire and life safety code.
33. Consultant and contractors shall comply with UAE fire and life safety
code Chapter 1 in terms of the requirement of balcony, terrace and windows DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
34. Private fire hydrant shall provided around these building as per (UAE fire
and life safety code) PROJECT NAME :
35. Consultant and contractors must comply with the general notes and
applicable codes and standards even if the code requirement was missed
during plan review. COMMERCIAL BUILDING
36. This building shall be provided with HASSANTUK devices and shall be
connected with fire alarm control Panel.
37. Fire lift shall be provided in this building according in UAE fire and life
safety code. ZONE : PLOT NO :
* All portion of this building shall be fully covered by
smoke detection system and fully covered by
AL NAHYAN C79
announcement system according to UAE fire and life
safety code and NFPA 72 SECTOR NO :
* Exit sign and emergency lighting shall be providing in this E19_02
building according to UAE fire and life safety code and NFPA

* All standpipe system in this building shall be used as


dry riser system according to NFPA 14
PROJECT DESCRIPTION :
* All portion of this building shall be fully protected by
automatic sprinklers system according to UAE fire and life
A101-MEZZANINE
FLOOR SCALE :
PLAN

TYPE OF FIRE PROTECTION


DRAWING TITLE :
AREA TYPE OF SMOKE
FF FA
LOCATION MANAGMENT SYSTEM MEZZANINE FLOOR PLAN
FIRE ALARM &
MEZZANINE
FLOOR
SPRINKLER
DRS+FHC SMOKE DETECTION SYSTEM
NA
DRAWING NO : REVISION NO:

MEZZANINE FLOOR A101 00


NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD
SUBMISSION DATE : SCALE :
FLOOR NO. USAGE AREA (M2 )
OCCUPANT LOAD
FACTOR(M2/PERSON) NO. OF OCCUPANTS
FHC
08-01-2023 1/100 A2
MEZZANINE OFFICES 258.21 SQ.M 9.3 04
LV
PROJECT ID :
SERVICES AREA 101.59 SQ.M
359.8 SQ.M
27.9 28
32
FD2
FD1 B1M-2022-004027-CD02
WSS

EXIT DISCHARGE CAPACITIES FOR STAIR DOOR CAS OFFICE USE ONLY :
FSS
DOOR mm PER NUMBER OF ACTUAL
OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH PERSON OCCUPANT OCCUPANT

Stair 1-DOOR BUSINESS 1000 mm 5 200 persons 23 persons

Stair 2-DOOR BUSINESS 1000 mm 5 200 persons 23 persons

400 persons
EXIT DISCHARGE CAPACITIES FOR STAIR
STAIR mm PER NUMBER OF ACTUAL
OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH PERSON OCCUPANT OCCUPANT

Stair 1 BUSINESS 1200 mm 7.6 158 persons 23 persons

Stair 2 BUSINESS 1200 mm 7.6 158 persons 23 persons

316 persons
NORTH : LAND KEY :
GENERAL NOTE:
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be GENERAL NOTES :
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
(within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
11. Emergency light and exit signs shall be provided according to (UAE fire
and life safety code and NFPA 101)
12. All structure elements shall have the fire resistance rating according to
BEDROOM LIVING BEDROOM KITCHEN LIVING LIVING BEDROOM (NFPA 5000 and UAE fire and life safety code)
area =16.77 m² area =19.6 m² area =12.07 m² 10.6 m² area =26.34 m² area =28.49 m² area =13.75 m² 13. All stairways shall be provided with two ways fire telephone
CM communication.
64
10 14. All portions of these building and common and services areas shall be

11

CM
fully cover by smoke detections and fully covered by voice announcement

07
system according to (NFPA 72)

95 5
CM
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
16. Standpipe system shall be provided in these building according to (NFPA 14)
BATH 17. All fire door and windows shall be according to (NFPA 80)
BATH and UAE fire and life safety code
4.4 m²
3.74 m² 18. All types of smoke management systems (include pressure difference
between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
92B and UAE fire and life safety code and shall be submitted in
FD2 shop drawing submittal.
FD2 19. All interior finishing material shall be provided as (UAE fire and life ENGINEER REGISTRATION CARD :
FD2 safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
LOBBY KITCHEN life safety code and NFPA requirement
LOBBY area =7.7 m²
KITCHEN BATH 6.6 m² 21. CO² monoxide detector shall be provided to detect the CO² concentration
4.7 m²
7.5 m² 4.3 m² M 22. Central battery system for emergency lighting systems and other system
3 4C shall be provided according to UAE fire and life safety code
30 F
23. Internal roads indicating how fire-men emergency tracks will maneuver on
the site and occupants assemblies areas
O.D.F F.H.C 24. Total duration time of full evacuation of the building at discharging level,
up to assemblies' areas (assemblies' areas shall be sized according total
04 FHC 03 02 STAIRCASE number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
roofing Sandwich panel system shall be provided as UAE fire and life safety
1172 CM Chapter 1, after tender is approved bring shop drawing and support
CORRIDOR information for civil defense approval
26. Fire pump and fire water tank shall be listed and tested according to civil OWNER:
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
UP as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
05 06 01 28. Fire or smoke damper shall be provided in these building on all duct shaft
according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal.
29. All penetrations through fire resistance rated walls shall be protected by
LIFT-02 ELEC. LIFT-01 approved fire stop system and materials, installed and tested in accordance
with ASTM E 814 or UL 1479
BATH
4.3 m² LOBBY 30. All means of egress components details and dimensions shall be provided
and constructed according to (UAE fire and life safety code and NFPA 101 and 5000)
CONSULTANT : BASALT ENGINEERING CONSULTANCY
4.7 m² BATH KITCHEN 31. Consultant and contractors shall comply with UAE fire and life safety PRINCIPAL CONSULTANT
KITCHEN 5.0 m² 30 area =7.7 m² code chapter 12 in terms of requirements of building under construction TEL: +97124436366, FAX: +97124436367
7.5 m² 34 FD2
DEFENSE ROAD, ABU DHABI, U.A.E.
CM 32. Emergency action plan shall be implementing in these buildings according
to UAE fire and life safety code. P.O. BOX 33848, ABU DHABI, U.A.E.
FD2 LOBBY E.mail:info@basaltconsultant.com
F 33. Consultant and contractors shall comply with UAE fire and life safety
8.0 sq.m code Chapter 1 in terms of the requirement of balcony, terrace and windows WEB: WWW.BASALTCONSULTANT.COM
BATH
4.4 sq.m 34. Private fire hydrant shall provided around these building as per (UAE fire
and life safety code)
DESIGNED BY DRAWN BY

91
ENG. ANAS SAMOUR RIYAZ.M
35. Consultant and contractors must comply with the general notes and

9C
FD2 applicable codes and standards even if the code requirement was missed
PROJECT NAME :

M
CM

during plan review.


07

36. This building shall be provided with HASSANTUK devices and shall be

COMMERCIAL BUILDING
11

connected with fire alarm control Panel.


BEDROOM LIVING BEDROOM KITCHEN LIVING LIVING BEDROOM 37. Fire lift shall be provided in this building according in UAE fire and life
area =16.77 m² area =19.6 m² area =17.35 m² area =6.6 m² area =18.98 m² area =28.49 m² area =13.75
1 m² safety code.
06
4
CM * All portion of this building shall be fully covered by
smoke detection system and fully covered by ZONE : PLOT NO :
announcement system according to UAE fire and life
safety code and NFPA 72
AL NAHYAN C79
* Exit sign and emergency lighting shall be providing in this
building according to UAE fire and life safety code and NFPA
SECTOR NO :
* All standpipe system in this building shall be used as E19_02
dry riser system according to NFPA 14

* All portion of this building shall be fully protected by


automatic sprinklers system according to UAE fire and life PROJECT DESCRIPTION :

A102-FIRST
FLOOR SCALE :
PLAN

DRAWING TITLE :
TYPE OF FIRE PROTECTION EXIT DISCHARGE CAPACITIES FOR STAIR DOOR
TYPE OF SMOKE NUMBER OF ACTUAL
FIRST FLOOR PLAN
AREA DOOR mm PER
FF FA MANAGMENT SYSTEM OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH PERSON OCCUPANT OCCUPANT
LOCATION

FIRST Stair 1-DOOR BUSINESS 1000 mm 5 200 persons 23 persons DRAWING NO : REVISION NO:
FLOOR
SPRINKLER
DRS+FHC
FIRE ALARM &
NA
SMOKE DETECTION SYSTEM Stair 2-DOOR BUSINESS 1000 mm 5 200 persons 23 persons A102 00
400 persons
FIRST FLOOR SUBMISSION DATE : SCALE :
NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD
OCCUPANT LOAD
EXIT DISCHARGE CAPACITIES FOR STAIR
STAIR mm PER NUMBER OF ACTUAL 08-01-2023 1/100 A2
FLOOR NO. USAGE AREA (M2 ) OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH OCCUPANT OCCUPANT
FACTOR(M2/PERSON) NO. OF OCCUPANTS PERSON
PROJECT ID :
APARTMENT -1 RESIDENTIAL 61.38 SQ.M 18.6 3 Stair 1 BUSINESS 1200 mm 7.6 158 persons 23 persons
FHC
LV
B1M-2022-004027-CD02
APARTMENT -2 RESIDENTIAL 74.17 SQ.M 18.6 4 Stair 2 BUSINESS 1200 mm 7.6 158 persons 23 persons FD2

APARTMENT -3 RESIDENTIAL 62.08 SQ.M 18.6 3


FD1 OFFICE USE ONLY :
316 persons WSS
APARTMENT -4 RESIDENTIAL 61.30 SQ.M 18.6 3 CAS
APARTMENT -5 RESIDENTIAL 60.40 SQ.M 18.6 3 FSS

APARTMENT -6 RESIDENTIAL 61.56 SQ.M 18.6 3

SERVICES AREA BUSINESS 80.11 SQ.M 27.9 3

SUB-TOTAL 461.0 SQ.M 22


GENERAL NOTE: NORTH : LAND KEY :
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be GENERAL NOTES :
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
BEDROOM LIVING BEDROOM KITCHEN LIVING LIVING BEDROOM (within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
area =16.77 m² area =19.6 m² area =12.07 m² 10.6 m² area =26.34 m² area =28.49 m² area =13.75 m² safety code and NFPA 10)
CM
64
11. Emergency light and exit signs shall be provided according to (UAE fire
10 and life safety code and NFPA 101)

11

CM
07
12. All structure elements shall have the fire resistance rating according to

95 5
(NFPA 5000 and UAE fire and life safety code)

CM
13. All stairways shall be provided with two ways fire telephone
communication.
BATH 14. All portions of these building and common and services areas shall be
BATH
4.4 m² fully cover by smoke detections and fully covered by voice announcement
3.74 sq.m system according to (NFPA 72)
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
FD2
16. Standpipe system shall be provided in these building according to (NFPA 14)
FD2 17. All fire door and windows shall be according to (NFPA 80)
FD2 and UAE fire and life safety code
18. All types of smoke management systems (include pressure difference
LOBBY KITCHEN between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
LOBBY area =7.7 m²
BATH 4.7 m² 92B and UAE fire and life safety code and shall be submitted in
KITCHEN 6.6 m² shop drawing submittal.
7.5 m² 4.3 m² M ENGINEER REGISTRATION CARD :
4C
19. All interior finishing material shall be provided as (UAE fire and life
3 03 safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
F
life safety code and NFPA requirement
O.D.F F.H.C 21. CO² monoxide detector shall be provided to detect the CO² concentration
04 FHC 03 02 22. Central battery system for emergency lighting systems and other system
shall be provided according to UAE fire and life safety code
23. Internal roads indicating how fire-men emergency tracks will maneuver on
1172 CM STAIRCASE the site and occupants assemblies areas
24. Total duration time of full evacuation of the building at discharging level,
1860 CORRIDOR up to assemblies' areas (assemblies' areas shall be sized according total
DISTANCE BETWEEN EXIT number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
UP roofing Sandwich panel system shall be provided as UAE fire and life safety
Chapter 1, after tender is approved bring shop drawing and support
05 06 01 information for civil defense approval
26. Fire pump and fire water tank shall be listed and tested according to civil
defense requirement and international standards OWNER:
27. All open space floors shall be used as a single tenant floor only, if it used
LIFT-02 ELEC. LIFT-01 as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
BATH LOBBY shall be submitted in shop drawing submittal.
BATH KITCHEN
4.3 m² 4.7 m² 29. All penetrations through fire resistance rated walls shall be protected by
KITCHEN 5.0 m² 30 area =7.7 m² approved fire stop system and materials, installed and tested in accordance
7.5 m² 34 FD2 with ASTM E 814 or UL 1479
CM 30. All means of egress components details and dimensions shall be provided
FD2 LOBBY and constructed according to (UAE fire and life safety code and NFPA 101 and 5000) CONSULTANT : BASALT ENGINEERING CONSULTANCY
F
8.0 m² 31. Consultant and contractors shall comply with UAE fire and life safety PRINCIPAL CONSULTANT
BATH code chapter 12 in terms of requirements of building under construction
TEL: +97124436366, FAX: +97124436367
4.4 m² 32. Emergency action plan shall be implementing in these buildings according DEFENSE ROAD, ABU DHABI, U.A.E.
to UAE fire and life safety code.

91
P.O. BOX 33848, ABU DHABI, U.A.E.

9C
33. Consultant and contractors shall comply with UAE fire and life safety E.mail:info@basaltconsultant.com
FD2 code Chapter 1 in terms of the requirement of balcony, terrace and windows

M
CM

WEB: WWW.BASALTCONSULTANT.COM
34. Private fire hydrant shall provided around these building as per (UAE fire
07

and life safety code)


11

BEDROOM LIVING BEDROOM LIVING LIVING BEDROOM 35. Consultant and contractors must comply with the general notes and DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
area =16.77 m² area =19.6 m² area =17.35 m² area =18.98 m² area =28.49 m² area =13.75 1m² applicable codes and standards even if the code requirement was missed
KITCHEN 06
4
during plan review. PROJECT NAME :
area =6.6 m² CM 36. This building shall be provided with HASSANTUK devices and shall be

COMMERCIAL BUILDING
connected with fire alarm control Panel.
37. Fire lift shall be provided in this building according in UAE fire and life
safety code.

* All portion of this building shall be fully covered by


smoke detection system and fully covered by
announcement system according to UAE fire and life ZONE : PLOT NO :
safety code and NFPA 72
AL NAHYAN C79
* Exit sign and emergency lighting shall be providing in this
building according to UAE fire and life safety code and NFPA
SECTOR NO :
* All standpipe system in this building shall be used as
dry riser system according to NFPA 14
E19_02
* All portion of this building shall be fully protected by
automatic sprinklers system according to UAE fire and life
PROJECT DESCRIPTION :

A103-SECOND
FLOOR SCALE :
PLAN

TYPE OF FIRE PROTECTION EXIT DISCHARGE CAPACITIES FOR STAIR DOOR DRAWING TITLE :
AREA
LOCATION
FF FA
TYPE OF SMOKE
MANAGMENT SYSTEM OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH
DOOR mm PER
PERSON
NUMBER OF
OCCUPANT
ACTUAL
OCCUPANT
SECOND FLOOR PLAN
SECOND Stair 1-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
NA
SPRINKLER FIRE ALARM & FHC
FLOOR DRS+FHC SMOKE DETECTION SYSTEM LV
DRAWING NO : REVISION NO:
Stair 2-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
FD2
FD1
A103 00
400 persons
SECOND FLOOR
EXIT DISCHARGE CAPACITIES FOR STAIR WSS
SUBMISSION DATE : SCALE :
NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD

FLOOR NO. USAGE AREA (M2 )


OCCUPANT LOAD
FACTOR(M2/PERSON) NO. OF OCCUPANTS
OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH
STAIR mm PER
PERSON
NUMBER OF
OCCUPANT
ACTUAL
OCCUPANT
CAS
FSS 08-01-2023 1/100 A2
APARTMENT -1 RESIDENTIAL 61.38 SQ.M 18.6 3 Stair 1 BUSINESS 1200 mm 7.6 158 persons 23 persons PROJECT ID :
APARTMENT -2 RESIDENTIAL 74.17 SQ.M 18.6 4 Stair 2 BUSINESS 1200 mm 7.6 158 persons 23 persons B1M-2022-004027-CD02
APARTMENT -3 RESIDENTIAL 62.08 SQ.M 18.6 3
316 persons OFFICE USE ONLY :
APARTMENT -4 RESIDENTIAL 61.30 SQ.M 18.6 3

APARTMENT -5 RESIDENTIAL 60.40 SQ.M 18.6 3

APARTMENT -6 RESIDENTIAL 61.56 SQ.M 18.6 3

SERVICES AREA BUSINESS 80.11 SQ.M 27.9 3

SUB-TOTAL 461.0 SQ.M 22


GENERAL NOTE:
NORTH : LAND KEY :
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be GENERAL NOTES :
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
TERRACE TERRACE (within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
11. Emergency light and exit signs shall be provided according to (UAE fire
and life safety code and NFPA 101)
12. All structure elements shall have the fire resistance rating according to
S.D (NFPA 5000 and UAE fire and life safety code)
13. All stairways shall be provided with two ways fire telephone
communication.
14. All portions of these building and common and services areas shall be
fully cover by smoke detections and fully covered by voice announcement
LIVING BEDROOM LIVING KITCHEN BEDROOM BATH M.BEDROOM system according to (NFPA 72)
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
16. Standpipe system shall be provided in these building according to (NFPA 14)
M
C 17. All fire door and windows shall be according to (NFPA 80)
90 and UAE fire and life safety code
11 18. All types of smoke management systems (include pressure difference
between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
92B and UAE fire and life safety code and shall be submitted in
shop drawing submittal.
19. All interior finishing material shall be provided as (UAE fire and life ENGINEER REGISTRATION CARD :
FD2

880 CM
safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
life safety code and NFPA requirement
BATH 21. CO² monoxide detector shall be provided to detect the CO² concentration
25 BATH
93 22. Central battery system for emergency lighting systems and other system
CM
shall be provided according to UAE fire and life safety code
23. Internal roads indicating how fire-men emergency tracks will maneuver on
O.D.F F.H.C the site and occupants assemblies areas
FHC 01 24. Total duration time of full evacuation of the building at discharging level,
up to assemblies' areas (assemblies' areas shall be sized according total
number of occupants)
FD2
KITCHEN 1694 25. All curtain walls and cladding insulation, exterior wall cladding and
roofing Sandwich panel system shall be provided as UAE fire and life safety
DISTANCE BETWEEN EXIT LOBBY Chapter 1, after tender is approved bring shop drawing and support
information for civil defense approval
02 1271 CM 26. Fire pump and fire water tank shall be listed and tested according to civil
OWNER:
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
F as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
FD2 FD2 FD2 according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal.
LIFT-02 29. All penetrations through fire resistance rated walls shall be protected by
approved fire stop system and materials, installed and tested in accordance
CAT LADDER with ASTM E 814 or UL 1479
LIFT KITCHEN 30. All means of egress components details and dimensions shall be provided
TEL. ROOM and constructed according to (UAE fire and life safety code and NFPA 101 and 5000) CONSULTANT : BASALT ENGINEERING CONSULTANCY
ROOM STORE WATCHMAN FD2 31. Consultant and contractors shall comply with UAE fire and life safety PRINCIPAL CONSULTANT
code chapter 12 in terms of requirements of building under construction TEL: +97124436366, FAX: +97124436367

ELEC. 32. Emergency action plan shall be implementing in these buildings according
to UAE fire and life safety code.
DEFENSE ROAD, ABU DHABI, U.A.E.
P.O. BOX 33848, ABU DHABI, U.A.E.
ROOM BATH 33. Consultant and contractors shall comply with UAE fire and life safety E.mail:info@basaltconsultant.com
code Chapter 1 in terms of the requirement of balcony, terrace and windows WEB: WWW.BASALTCONSULTANT.COM
34. Private fire hydrant shall provided around these building as per (UAE fire
and life safety code)

35. Consultant and contractors must comply with the general notes and DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
applicable codes and standards even if the code requirement was missed
during plan review. PROJECT NAME :
36. This building shall be provided with HASSANTUK devices and shall be

COMMERCIAL BUILDING
connected with fire alarm control Panel.
37. Fire lift shall be provided in this building according in UAE fire and life
safety code.

* All portion of this building shall be fully covered by


smoke detection system and fully covered by
announcement system according to UAE fire and life
ZONE : PLOT NO :
safety code and NFPA 72
AL NAHYAN C79
* Exit sign and emergency lighting shall be providing in this
building according to UAE fire and life safety code and NFPA
SECTOR NO :
* All standpipe system in this building shall be used as E19_02
dry riser system according to NFPA 14

* All portion of this building shall be fully protected by


automatic sprinklers system according to UAE fire and life PROJECT DESCRIPTION :

A103-ROOF
FLOOR SCALE :
PLAN

TYPE OF FIRE PROTECTION EXIT DISCHARGE CAPACITIES FOR STAIR DOOR DRAWING TITLE :
AREA
LOCATION
FF FA
TYPE OF SMOKE
MANAGMENT SYSTEM OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH
DOOR mm PER
PERSON
NUMBER OF
OCCUPANT
ACTUAL
OCCUPANT
ROOF FLOOR PLAN
ROOF FIRE ALARM & Stair 1-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
FLOOR
SPRINKLER
DRS+FHC SMOKE DETECTION SYSTEM
NA DRAWING NO : REVISION NO:
Stair 2-DOOR BUSINESS 1000 mm 5 200 persons 23 persons
A103 00
ROOF FLOOR 400 persons FHC

NFPA 101,2009 EDITION TABLE 7.2.1.2 WAS FOLLOWED WHEN CALCULATING LOAD
EXIT DISCHARGE CAPACITIES FOR STAIR LV
SUBMISSION DATE : SCALE :
FLOOR NO. USAGE AREA (M2 )
OCCUPANT LOAD
FACTOR(M2/PERSON) NO. OF OCCUPANTS OCCUPANCY CLASSIFICATION OF OCCUPANCY WIDTH
STAIR mm PER
PERSON
NUMBER OF
OCCUPANT
ACTUAL
OCCUPANT
FD2
FD1

WSS
08-01-2023 1/100 A2
APARTMENT -1 RESIDENTIAL 52.16 SQ.M 18.6 3 Stair 1 BUSINESS 1200 mm 7.6 158 persons 23 persons CAS PROJECT ID :
APARTMENT -2 RESIDENTIAL 84.79 SQ.M 18.6 5
Stair 2 BUSINESS 1200 mm 7.6 158 persons 23 persons
FSS B1M-2022-004027-CD02
ROOF FLOOR

GUARD RM AREA 32.64 SQ M 27.9 1


316 persons OFFICE USE ONLY :
35.16 SQ M 27.9 1
EQUIPMENT AREA FIRE FIGHTING SYSTEM IN SERVICE ROOMS
SERVICES AREA 72.25 SQ M 27.9 3 SI. NO. NAME OF ROOM SUPPRESSION SYSTEM
TOTAL 277 SQ.M 13 1. GUARD ROOM - FIRE EXTINGUISHER
2. STORE ROOM - FIRE EXTINGUISHER

3. ELEC.ROOM - FIRE EXTINGUISHER


NORTH : LAND KEY :

PL
GENERAL NOTE:

PLO
1- All items in these documents are guidance only , detailed of fire alarm,
firefighting and all ventilation system in all areas shall be submitted in
shop drawing submittal
2. Fire pump capacity shall be calculated according to the building type and civil
defense requirementand shall be submitted in shop drawing submittal as per
(UAE fire and life safety code).
3. Fire reserve water tank shall be calculated according to the building type and
civil defense requirementand shall be submitted in shop drawing submittal and
as per (UAE fire and life safety code).
4. There are no installations for LPG central system in these building

5. All gas piping (LPG central system) shall be exposed on the outside
GENERAL NOTES :
elevations (filling line and risers) if the system is provided
6. Determine the total area of the opening between adjacent façade
of two different buildings as percentage as per (UAE fire and life safety
code and international codes)
7. All stairways shall be provided with marking signs
8. All smoke management system and elevators shall be
interlocking with the alarm system
9. All horizontal and vertical opening (on external façade, on internal, shafts
or voids) shall be fire rated according to the rating degree of the compartment
(within the building or on elevation)
10. All portable fire extinguishers shall be provided as per (UAE fire and life
safety code and NFPA 10)
11. Emergency light and exit signs shall be provided according to (UAE fire
and life safety code and NFPA 101)
12. All structure elements shall have the fire resistance rating according to
(NFPA 5000 and UAE fire and life safety code)
13. All stairways shall be provided with two ways fire telephone
communication.
14. All portions of these building and common and services areas shall be
fully cover by smoke detections and fully covered by voice announcement
system according to (NFPA 72)
15. All portions of these building shall be fully protected by automatic
sprinklers system according to (NFPA 13) and UAE fire and life safety code
16. Standpipe system shall be provided in these building according to (NFPA 14)
ENGINEER REGISTRATION CARD :
17. All fire door and windows shall be according to (NFPA 80)
and UAE fire and life safety code ROOF
18. All types of smoke management systems (include pressure difference
between adjacent zones) shall be following (NFPA 90A, NFPA 92A, NFPA
92B and UAE fire and life safety code and shall be submitted in
shop drawing submittal.
19. All interior finishing material shall be provided as (UAE fire and life
safety code and NFPA 101)
20. Fire command center room shall be provided according to (UAE fire and
life safety code and NFPA requirement UC 254x76x28
21. CO² monoxide detector shall be provided to detect the CO² concentration
22. Central battery system for emergency lighting systems and other system
shall be provided according to UAE fire and life safety code GRATING
23. Internal roads indicating how fire-men emergency tracks will maneuver on
the site and occupants assemblies areas
24. Total duration time of full evacuation of the building at discharging level,
up to assemblies' areas (assemblies' areas shall be sized according total OWNER:
number of occupants)
25. All curtain walls and cladding insulation, exterior wall cladding and
roofing Sandwich panel system shall be provided as UAE fire and life safety
Chapter 1, after tender is approved bring shop drawing and support
information for civil defense approval
26. Fire pump and fire water tank shall be listed and tested according to civil
defense requirement and international standards
27. All open space floors shall be used as a single tenant floor only, if it used
as a multiple tenancy, then fire rated corridor not less than one hour shall be
connected to the bath staircases
28. Fire or smoke damper shall be provided in these building on all duct shaft
CONSULTANT : BASALT ENGINEERING CONSULTANCY
according to (UAE fire and life safety code and NFPA 90A, NFPA90B) and
shall be submitted in shop drawing submittal. PRINCIPAL CONSULTANT
29. All penetrations through fire resistance rated walls shall be protected by UC 254x76x28 TEL: +97124436366, FAX: +97124436367
approved fire stop system and materials, installed and tested in accordance
DEFENSE ROAD, ABU DHABI, U.A.E.
with ASTM E 814 or UL 1479
P.O. BOX 33848, ABU DHABI, U.A.E.
30. All means of egress components details and dimensions shall be provided
and constructed according to (UAE fire and life safety code and NFPA 101 and 5000)
IPE 200 E.mail:info@basaltconsultant.com
200x100 WEB: WWW.BASALTCONSULTANT.COM
31. Consultant and contractors shall comply with UAE fire and life safety
code chapter 12 in terms of requirements of building under construction DETAIL-F
32. Emergency action plan shall be implementing in these buildings according
to UAE fire and life safety code. DESIGNED BY ENG. ANAS SAMOUR DRAWN BY RIYAZ.M
33. Consultant and contractors shall comply with UAE fire and life safety
code Chapter 1 in terms of the requirement of balcony, terrace and windows PROJECT NAME :
34. Private fire hydrant shall provided around these building as per (UAE fire
and life safety code)

35. Consultant and contractors must comply with the general notes and
COMMERCIAL BUILDING
applicable codes and standards even if the code requirement was missed
during plan review.
36. This building shall be provided with HASSANTUK devices and shall be
ZONE : PLOT NO :
50mm dia.STEEL
GUARD RAIL PAINTED
connected with fire alarm control Panel.
38mm dia.STEEL
37. Fire lift shall be provided in this building according in UAE fire and life HANDRAIL PAINTED

AL NAHYAN C79
FIXED TO GUARD RAIL

safety code. 30mm dia.STEEL


INCLINED BALUSTER LINE
PAINTED

* All portion of this building shall be fully covered by


smoke detection system and fully covered by 50mm dia.STEEL
VERTICAL BALUSTER
SECTOR NO :
announcement system according to UAE fire and life
E19_02
PAINTED

safety code and NFPA 72


50mm dia.STEEL
BALLUSTER PAINTED
FIXED TO THE FLOOR

* Exit sign and emergency lighting shall be providing in this


building according to UAE fire and life safety code and NFPA 30mm dia.STEEL
INCLINED BALLUSTER
PAINTED
PROJECT DESCRIPTION :
* All standpipe system in this building shall be used as
dry riser system according to NFPA 14
FLOOR FINISH
BALLUSTER PAINTED

* All portion of this building shall be fully protected by


FIXED TO THE FLOOR

30 MM THK.TREAD
automatic sprinklers system according to UAE fire and life AS SPECIFIED

20 MM THK.MORTAR

SECTION A-A SECTION A-A 20mm THK.RISER


AS SPECIFIED

STAIR-2 STAIR-1
DETAIL- W
NOTE: THIS DIMENSIONS ARE CONSIDERED IN MM. DRAWING TITLE :

STAIRCASE / SECTION-AA

DRAWING NO : REVISION NO:

GRATING 30 30 A300 00
SUBMISSION DATE : SCALE :
C 254x76x28
GRATING TREAD
NB40
HANDRAIL
08-01-2023 1/100 A2
ANGLE 75x75x6 PROJECT ID :

PIPE
NB32
B1M-2022-004027-CD02
OFFICE USE ONLY :
5 STAIR STRINGER

10 STEP(TYP.)

3mm THK.
ANGLE 75x75x6 CLOSER PLATE ANGLE 75x75x6 TYPICAL SECTIONAL OF WALL
WELDED TO FLANGES MOUNTED HANDRAIL
SCALE

STRINGER BEAM
UC 254x76x28
C 254x76x28
DETAIL-E OF CONNECTION BET.
STAIR & LANDING HANDRAIL TO STRINGER CONNECTION DET.B (TYP)
SCALE N.T.S
DETAIL- Z

A300-SECTION-AA
SCALE :