Professional Documents
Culture Documents
IT 2014A Panel Signal Analysis Multi 30K 3ph Cada 300403 Scma
IT 2014A Panel Signal Analysis Multi 30K 3ph Cada 300403 Scma
IT 2014A Panel Signal Analysis Multi 30K 3ph Cada 300403 Scma
1 di 5
INDEX
explanation............................................................................................................................................ 2
[ in= value1, …, …%v ] line input voltage, phase 1. ................................................................................. 2
[ in= …, value2, …%v ] line input voltage, phase 2. .................................................................................. 2
[ in= …, …, value3 %v ] line input voltage, phase 3. ................................................................................. 2
[ out= value1, …, …vln; ] ups output voltage, phase 1 ............................................................................ 3
[ out= …, value2, … vln; ] ups output voltage, phase 2 ........................................................................... 3
[ out= …, …, value3 vln; ] ups output voltage, phase 3 ............................................................................ 3
[ out= …….., value 1, …, …%a; ] ups output current, phase1. ................................................................... 3
[ out= …….., …, value 2, … %a; ] ups output current, phase2................................................................... 3
[ out= …….., …, …, value 3 %a; ] ups output current, phase3.................................................................. 4
[by= value1, …, …vl; ] bypass input voltage, phase1 ................................................................................ 4
[by= …, value2, …vl; ] bypass input voltage, phase2 ................................................................................ 4
[by= …, …, value3 vl; ] bypass input voltage, phase3 ............................................................................... 4
[ bat= +value, ………. v; ] battery input voltage, positive branch. ............................................................. 5
[ bat= +…., - value v; ] battery input voltage, negative branch. ................................................................ 5
[i = … v, vdc + = positive value, vdc - = …….; ] inverter input voltage, positive .............................................. 5
[i = … v, vdc + =……., vdc - = negative value; ] inverter input voltage, negative............................................. 5
[ i = value v, …v+, … v-; ] inverter output voltage ..................................................................................... 5
[ ts = 25, tr =…, ti =…, tc =… °c ] temperature of the micro system card .................................................... 6
[ts =…, tr = 23, ti =…, tc =… °c] temperature of the booster power card..................................................... 6
[ts =…, tr = …, ti = 27, tc =… °c] temperature of the inverter power card.................................................... 6
[ts =…, tr = …, ti =…, tc = 25 °c] temperature of the channel..................................................................... 6
[ in= …, …, …%v, value hz ] input frequency ........................................................................................... 6
[ by= …, …, …vl, value hz ] frequency of bypass ..................................................................................... 6
[ out= _, value hz.] output frequency of the ups (calculated value) ............................................................. 7
[ in= value% a;] ups feeding line input current (calculated value). ............................................................. 7
[ value% w;] output power of the ups (calculated value). ........................................................................... 7
inverter output current (normal operation). ............................................................................................... 7
[+ value a; ] battery current (calculated value). ......................................................................................... 7
Technical Information/ Informazione tecnica. IT-2014A Pag. 1 di 5
Explanation
This document shows some tables with the the electric signals path related to the values visualized on the UPS panel.
The measure of the electric signals of alternate voltage " Vac " and of continuous voltage " Vdc " is reported to the
conditions of operation with nominal voltage and load.
For each value present on the panel we consider:
- the meaning of the correlated signal,
- the symbol and the value correspondents, visible on the computer in DEBUG connection,
- the name and the code of the cards on which is present the signal.
- The name with which has identified the signal on each card
- The terminals of the connector on which has connected the signal..
- A component and a point of reference between which is possible to measure with digital multimeter.
- The values of alternate voltage "Vac" and continuous voltage "Vdc" measurable when the ups works in
condition of voltage and nominal load.
The connection "debug" between the UPS and computer can be realized by connecting the serial doors RS232 of the
two unity, with the cable supplied.
For visualizing the values on the computer in DEBUG mode it must be used the program WINDOWS TERMINAL or
MREM.
micro sistem card J3_8 to R17 to pin 29 of U21 (1.27 Vac, 2.3 Vdc, Ref: logic ground on case of X1).
9AATB2032xxxx.
Technical Information/ Informazione tecnica. IT-2014A Pag. 1 di 5
[Ts =…, Tr = 23, Ti =…, Tc =… °C] Temperature of the booster power card
Initial on Debug Temp1_boost (C) : 23
booster power card from J2_2 to J1_4;
9AATB2023xxxx
Booster control card From J2_4 to J3_7;
9AATB2022xxxx
micro sistem card from J4_7 to pin 13 of U16 (0 Vac, 3.08 Vdc, Ref: logic ground on case of X1);
9AATB2032xxxx
[ In= value% A;] UPS feeding line input current (calculated value).
Value calculated by means of output load, input voltage and internal losses of the UPS.