PVsyst - Simulation report
Grid-Connected System

Project: ses
Variant: Nouvelle variante de simulation
No 3D scene defined, no shadings
System power: 58.8 kWp

PVsyst TRIAL Oujda-Angad - Morocco

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: ses
Variant: Nouvelle variante de simulation

PVsyst V7.3.4
VC0, Simulation date:
24/06/23 22:01

PVsyst TRIAL
with v7.3.4

Project summary
Geographical Site Situation Project settings
Oujda-Angad Latitude 34.68 °N Albedo 0.20
Morocco Longitude -1.91 °W
Altitude 562 m
Time zone UTC

Meteo data
Oujda-Angad
PVGIS api TMY

System summary

PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 30 / 0 °

System information
PV Array Inverters
Nb. of modules 147 units Nb. of units 24.5 units
Pnom total 58.8 kWp Pnom total 49.0 kWac
Pnom ratio 1.200

Results summary
Produced Energy 109568 kWh/year Specific production 1863 kWh/kWp/year Perf. Ratio PR 84.35 %

PVsyst TRIAL
Project and results summary

Main results
Loss diagram
Predef. graphs
Table of contents

General parameters, PV Array Characteristics, System losses


2
3
4
5
6

PVsyst TRIAL

PVsyst TRIAL
24/06/23 PVsyst Evaluation mode Page 2/6
Project: ses
Variant: Nouvelle variante de simulation

PVsyst V7.3.4
VC0, Simulation date:
24/06/23 22:01

PVsyst TRIAL
with v7.3.4

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 30 / 0 ° Diffuse Imported
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PVsyst TRIAL
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model JKM400M-72H Model SUN2000-2KTL-L1
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 400 Wp Unit Nom. Power 2.00 kWac
Number of PV modules 147 units Number of inverters 49 * MPPT 50% 24.5 units
Nominal (STC) 58.8 kWp Total power 49.0 kWac
Modules 49 Strings x 3 In series Operating voltage 80-600 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.20
Pmpp 53.7 kWp No power sharing between MPPTs
U mpp 111 V
I mpp 482 A

PVsyst TRIAL
Total PV power Total inverter power
Nominal (STC) 59 kWp Total power 49 kWac
Total 147 modules Nb. of inverters 25 units
Module area 296 m² 0.5 unused
Cell area 262 m² Pnom ratio 1.20

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 3.8 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses


Loss Fraction 1.3 % at MPP

PVsyst TRIAL
IAM loss factor
Incidence effect (IAM): Fresnel, AR coating, n(glass)=1.526, n(AR)=1.290

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.999 0.987 0.962 0.892 0.816 0.681 0.440 0.000

PVsyst TRIAL
24/06/23 PVsyst Evaluation mode Page 3/6
Project: ses
Variant: Nouvelle variante de simulation

PVsyst V7.3.4
VC0, Simulation date:
24/06/23 22:01

PVsyst TRIAL
with v7.3.4

Main results
System Production
Produced Energy 109568 kWh/year Specific production 1863 kWh/kWp/year
Perf. Ratio PR 84.35 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL
Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 97.0 30.65 8.16 153.9 151.7 8350 8040 0.889

PVsyst TRIAL
February 113.8 36.33 7.38 158.8 156.3 8500 8187 0.877
March 145.8 53.83 11.31 174.0 170.8 9083 8735 0.854
April 186.5 58.96 16.39 198.0 194.4 10094 9711 0.834
May 215.0 71.05 15.57 207.3 202.9 10688 10284 0.844
June 224.0 69.03 23.14 206.7 201.9 10331 9930 0.817
July 223.8 72.71 27.43 213.1 208.8 10499 10100 0.806
August 219.4 62.35 26.32 225.5 221.3 11110 10699 0.807
September 156.8 57.73 19.46 179.3 176.1 9201 8846 0.839
October 147.1 43.10 19.84 196.8 193.8 10055 9695 0.838
November 108.0 33.40 14.46 166.6 164.1 8809 8488 0.866
December 80.1 30.46 6.62 129.1 127.1 7135 6852 0.902
Year 1917.2 619.60 16.39 2209.2 2169.2 113854 109568 0.843

PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

PVsyst TRIAL
24/06/23 PVsyst Evaluation mode Page 4/6
Project: ses
Variant: Nouvelle variante de simulation

PVsyst V7.3.4
VC0, Simulation date:
24/06/23 22:01

PVsyst TRIAL
with v7.3.4

Loss diagram
1917 kWh/m² Global horizontal irradiation
+15.2% Global incident in coll. plane

-1.81% IAM factor on global

2169 kWh/m² * 296 m² coll. Effective irradiation on collectors

efficiency at STC = 19.95% PV conversion

127985 kWh Array nominal energy (at STC effic.)

PVsyst TRIAL
-0.38% PV loss due to irradiance level

-8.80% PV loss due to temperature

+0.75% Module quality loss

-1.30% Module array mismatch loss


-1.22% Ohmic wiring loss
114222 kWh Array virtual energy at MPP

-3.55% Inverter Loss during operation (efficiency)

-0.33% Inverter Loss over nominal inv. power


0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
-0.01% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
-0.20% Night consumption
109568 kWh Available Energy at Inverter Output
109568 kWh Energy injected into grid

PVsyst TRIAL

PVsyst TRIAL
24/06/23 PVsyst Evaluation mode Page 5/6
Project: ses
Variant: Nouvelle variante de simulation

PVsyst V7.3.4
VC0, Simulation date:
24/06/23 22:01

PVsyst TRIAL
with v7.3.4

Predef. graphs
Diagramme d'entrée/sortie journalier

PVsyst TRIAL

PVsyst TRIAL Distribution de la puissance de sortie système

PVsyst TRIAL

PVsyst TRIAL
24/06/23 PVsyst Evaluation mode Page 6/6