Professional Documents
Culture Documents
1987 - Switching of Polyphase Transformers Without Inrush Currents
1987 - Switching of Polyphase Transformers Without Inrush Currents
Simulation"
ABSTRACT
The paper examines the ~ethod of avoiding magnetising inrush currents in alI
three phases "hen .,,1tching a bank of three unloaded aingle-phase transfonners
connected in three "ire star-delta. The theory of the lIethod ia described and 1ts
results sre conf1nned both experimentally and by computer a1l1ulat1on.
Th1s type of transient ia a "ell knevn phellOllenon accomp~lng the
connection of a transformer to the a.c. ~a1ns, when a s1..,ltaneous closure of ali
phases is used. If the instants of phase closure are chosen sppropriately, complete
tranaient luppression in alI three phases can be achieved.
The method "eacribed enables °the sppropriate instante of phase closure to b~
found taking the .ains voltages as a reference, and given the residual core
megnet1zation state.
1. INTRODUCTION
5
1s used connected ln three w1re star-delta, f1g.1. Although th1s k1nd
of transformer has three 1ndependent magnetic c1rcu1 ts the electric
delta connect10n of their secondary c01ls 1mposes:
•.,
,o---
u., ?
r------------------
,
I Loop 2
, Seeondary
I
I
I _________________ J
L ....
o o---
depends both on the mains phase sequence and on the times at which
prev10us closures d1d occur.
," ,,'
6 7
Re
in which:
~
"'jsi - Steady state flux at switch closing time ti (1=1,2), ln the
Ül2
primary coil of phase j (j~l,2,3).
•12
°p2
~O - Flux linking the primary coil of phase j (j=l,2,3) being closed
and due either to residual magnetization of the core Cí n this
°1
case "'jo='l'jRem)
for the first closure (j=l,2) or resulting from
previous closures (jz3). '--,
'i'p2
1m O O
To depict as clearly as possible the phasor relationshlps °3 '1'12
(6-1) (6-2)
and
2.1.1. First closure at time t (7-1) (7-2)
1
To achleve absence of translent currents, i.e. to verify eq.(3),
the line voltage u12 should assume a posltive (or negative) peak value hence, we have a secondary vol tage balance which determines a zero
at tlme t1 in order to obtain a zero value for the steady state flux value for the current is in the delta connected secondary:
~12 imposed by the voltage applied to coils of phases 1 and 2, fig.3:
ls = O (B)
<1(12) = ~(12)sl - ( 'l'lRem+ 'I'2Rem)= O (5) Therefore, the residual flux condltlon in phase 3 ( 'I'3Rem) ls
unchanged by the flrst closure of phases 1 and 2.
-----~ _--------------------------
..
"I
113 (9)
c <11
3s2 - 'P3Rem c O
1/1
- "'p2 ., (10)
20
(a)
At time t2 we have for the same co11s the steady state flux (lo)
values:
Fig. 4 - Cloaure of phase 3 at lnatant t (t occura T/4 aeconda after t ,.
2 2 l
(a) Phssor dlagram of voltage and flux, taklng the origin at instant t •
(1\) 2
~. In broken trace, the voltage and f1ux phasors immediate1y before t •
2
[ReJt : Position of real axis corresponding to the origin at instant t •
1
l
hence (f1g.4):
(12) (b) Waveforma of the flux 1inking the primary coi18 of alI three phase8.
and
2.2. The Importanee ot Residual Core Magnetlzatlon
(13)
Supposing the same sequence ot: elosures at instants tet1 and
t••t2, and the residual core magnetization state havlng the following
as requ1red for absence of transients.
values,
Equations (9), (12) and (13) prove the complete trans1ent 'P1Rem ., + 0.3 Wb (15-1)
suppress10n in alI three phases, when energizlng the transformer wlth
demagnet1sed core, us1ng the spec1fied sequence of phase elosures. 'P2Rem •• - 0.45 Wb (15-2)
As can be seen from f1g.4 the instants t1 and t2 are related by 'P3Rem •• + 0.15 Wb, (15-3)
the equation:
(14) determ1ned by the natural sequence 01' current ext nc t t oris that took í
(19)
Re
Ü12---_
-- iii3
O
1m
Fig. 6 - Closure of phase 3 at instant t2 (t2 oecurs about 1(6.5 seconds after tI)'
Fig. 5 - CloBure of phases I and 2 at instant tI' Phasor diagram of voltage and flux, taking the orlgln at instant t •
2
Phasor diagram of voltage and flux, taking the origin at instant tI' ~. In broken trace, the voltage and flux phasors immediately before t .
2
Obs. In broken trace, the flux that would be imposed to the primary coil of [Relt} : Posltion of real axis corresponding to the origin at instant tI'
phase 3 ir this phase were closed.
/2
/3
"
(24)
(22-1)
(22-2) (25)
(26 )
dt/!sl dI/Js2 d"'s3
+---+---+ (22-3)
dt dt dt
Ra' Raj Reslstance of the sampling resistors used for measuring the
transformer coi1 currents. 3.1. First Closure at Time tI
rpj' rsj Reslstance of the primary (p) and of the secondary (s ) ln this case (tI ~ t < t ) we have loops 1 and 3 closed (see
2
co1ls. fig.2, and eq.(8»:
.\ Leakage inductance of the prlmary (p) and of the secondary
pj' '\sj
(s) co1ls. "p3 : consto (28)
dlp1
4.1. Demagnet1sed Core:
• dt
For computer simulatlon of the transformer, we assumed a non-
(29) -linear characteristic for each single-phase transformer j (j=l,2,3),
of the forro:
~_ lp2
vI "2 (31)
3 - 13
-900
I
õ-------T------------ ----------: -166
! ! I ' O 10 20 30 40
! i I ! t ms
-1800 -i =O -
il=O s 1500
<, O 10 20 30 40
t ms -1
i =O..- s
2 750
i =O _ mA.
3 8000
-is=O_ -is O
mA O
-750
Scales:
-8CXX>
i , i , i3 - saiR mA/div 83. mA/div
1 2 -1500
-is - 200/100/Ra mA/div 2. A/div O
-16CXXl
Seales: t
t - 5 ms/div
i1, 12' i3 - 500/R mA/div 833. mA/div
-24000
-is - 2/l00/Ra A/div 20. A/div O 10 20 30 (a) (b)
40
t - 10 mS/div t ms
Fig.S - Closure of phsses 1 and 2 at instant t (when the value of u12 waS lIaxi.um
l
and going down)and closure of phaae 3 at instant t2 (when the value of u12
(a) (b)
was zero and going negati ve ) - see 2.1. (Demagnet1sed core). It may be
Fig.7 - Simultaneous elosure of aI I phases, ",hen u value
and going "'as zero
pl observed that complete transient suppression in alI three phases, including
positive. Highest transient peak value in phase 1. (Demagnetised core).
the delta connected loop of secondary coils, is achieved.
(a) Experimental results; (b) Slmulatlon results.
(a) Experimental resulte; (b) Simulation results.
iP3 go ng
í negative, we have the residual core magnetization state
shown in fig.9 and the values assumed in eq, (15),
To avoid these transients we use the method discri bed in 2.1.
and the results are shown in fig.8, Let us assume the sarne sequence of closures as establ1shed ln
2.1. which, wi th a demagnetised core. let to a complete transient
4.2. The Effect of Residual Core Magnetization suppression in alI three phases. If we use this sarne sequence for the
The value of fluxes "'j{J=1,2,3) l1nking the primary colls of new residual core magnetization state, we obtaln the transients shown
the transformers and due to residual core magnetization, were measured in !ig.lO. a. To avoid magnetis1ng inrush currents the sequence of
using analogie integrators. Each residual magnetization state of the closures must be as establ1shed in 2.2. for thls new residual flux
core í s obtained by removing simul taneously the gate si gnals to the condi tions. The resul ting current waveforms upon swi tch-on are as
triacs used in the programmable sw tching
í device. The residual flux shown ln f1g. 10.b.
condl tion obtained is determlned by the ensuing natural sequence of
eurrent extlnctlons, that takes place, fo11owlng the removal of gate
slgnals and which occur as the successive phase currents go through
ze r o .
Jf ph"g(';> j", Lhe f Lr s t; be í ng d s c onr.ec t e d ,
í for a zero value of
18
19
IOoivfli~~--: s",
II=0 -
~I'''r'~:';'';;''~:i
~!.!I~
., 5. CONCLUSIONS
)2=0 - ,;.~
! ,; I . I;" I' i :".!.","Ii .....;;- ,
)3=0 -
-'I
.. ' .
.• ""'.'I"II"'II ..
I
~~~~-:::
'f'JAem
currents
Three· phase
ln a Ll three
transformers
phases, by executing
can be energized wi thout
an approprla te sequence
inrush
of
-l =0_
s
~
n-u;o;'
..~Ü~ttl·ri Y'3Rem
phase closures.
·'~I········"······-I.
•... .. .-.. .• ~.,' ~.,:.:~;
",:.- The approprl ate sequence of closures depends on the type o~
__." v v:·.·.'· transformer used (a bank of three slngle-phase transformers or a
1-"'1 ; 2-4'2 ; 3-"'3 three-llmb transformer), on the number of loops ln the prlmary clrcuit
Seales: Scales: (neutral present or absent) and on the core residual magnetization at
lI' 12' 13 - 200/R mA/dlv = 333. mA/div; i3 - 200/R mA/div ; 333. mA/div swl tch-on t me, í
-is - 200/100/Ra mA/div 2. A/div; 'I' '2' ~3 - 500 mWb/div Flux conditlons observed at swItch c:osing time linklng a given
t - 5 ms/dlv t - 5 ms/div coil whIch is being connected are due either ·to residual flux
conditions resulting from the last transformer swItch-off operation or
(a) (b) to condit1ons resulting from previous phase closures of the current
Flg.9 - Switching-off of the Y/O bank , when phase 3 i8 the first to be disconnected switch-on sequence.
followlng lts passage through zero golng negative. In order to take care of residual flux conditions when
(a) Current w8veforms ln the prlmary and in the de lta connected seeondary determlning the appropriate sequence of phase closures we can:
eo l s ,
í
(a) Measure the flux Iinking each coll belng closed. (In this case the
(b) Waveforms of the f1uxes lln1<ing eaeh prlmary coil. cIosure sequence must be adjustable): (b ) Disconnect the transformer
Obs. Phase 3 current waveform 111 shown again in (b) to facili ta te by removing the Ioad first, and then opening the primary switches at a
correspondence with (a). fixed instant in the appl1ed vol tage cycle so that the sarne sequence
of natural current extinctions is always obtained, (In this case the
residual . flux condi tions at swi tch-on time and therefore the
corresponding closure sequence to avoid transients will be aIways the
sarne) •
i1=0;
12=0
i3=0 -
6. REFERENCES
-1 =0- -1 =0-
s s
111 W.K. Macfadyen, R.R.S. Simpson, R.D. Slater and W.S. Wood, "Method
of Predlcting Transient-Current Patterns in Transformers". Proc.
IEE. Vol. 120 (no. 11), pp. 1393 - 1396. (1973)
161 J.A. Oliveira Martins, J.F. Borges da Silva, "Device for Inrush
Current Suppression when Energizing Three-Phase Transforme rs". (In
portuguese), paper presented at the Technical Sesslon
nO.1 - Advanced Technologies ln Power Systems, pp.39 - SO, ENDIEL
87, Llsbon, January 1987.
7. APPENDIX
Equipment Specifications:
Sj ~ 60 VA ':j = 3S.23
Raj = R = 0.6 a
a = 1S mA s= 3.2 Wb-1