Professional Documents
Culture Documents
Clic Acc Eng
Clic Acc Eng
NOMENCLATURE 3
CONTROL 33
SECURITY INSTRUCTIONS 4 PCO Sistema
Communication Protocol
FEATURES / BENEFITS 5
Design
Reliability CONNECTIVITY 68
Efficiency Ethernet
Flexibility
Communication
Installation ELECTRICAL INFORMATION 75
Maintenance Control Diagrams
Factory test Electrical Diagrams
GENERAL DESCRIPTION 7
General Description INSTALLATION 85
CONTENTS
Components Location
Control Installation
Corrosion Protection Refrigerant Charge
Connectivity
MAINTENANCE 99
MAPPING TABLES 14
Analogue Points TROUBLESHOOTING 105
Digital Points
WARRANTY 110
CLIC
SERIES AC C 300 A C 3 V M N 0 M
NOMENCLATURE
NOMINAL CAPACITY CORROSION PROTECTION UNIT CONFIGURATION
VOLTAGE
TYPE
Standalone Capacity Tandem Capacities 1500 1,500,000 BTU’s E ADSIL+Condenser + Internal
External Parts 2 420-460v/3/60Hz M Mother
300 300,000 BTU’s 600 600,000 BTU’s 1800 1,800,000 BTU’s ADSIL Condenser +
I Internal Parts
3 208-230v/3/60Hz S Son
900 900,000 BTU’s 2100 2,100,000 BTU’s C ADSIL for Condenser
5 546-605v/3/60Hz T Tandem
1200 1,200,000 BTU’s 2400 2,400,000 BTU’s 0 None
This manual contains important safety instructions that should be followed during the installation and maintenance of the unit. Read this manual
thoroughly before attempting to install or operate this unit.
Only qualified personnel should service this equipment. Adhere to all warnings, cautions, operating and safety instructions on the unit placards and in
this manual. Follow all operating and user instructions during and after installation.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier.
Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if
installation procedure is not handled properly.
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual
SAFETY INSTRUCTIONS
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and
national codes including but not limited to, building, electrical and mechanical codes.
Risk of sharp edges, splinters, and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing apropriate safety headgear, gloves, shoes and glasses should attempt to
move the unit, lift it, remove packaging or prepare the unit for installation.
Risk of contact with hot surfaces. Can cause injury.
WARNING The compressors, fan motors, refrigerant discharge lines and reheats are xtremely hot during unit operation. Allow sufficient time
for them to cool before working within the unit cabinet.
Periodically inspect all valves, fittings, and piping for corrosion, rust, leaks, or damage.
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to
bypass or otherwise depart from recommended procedures. Any short-ground of the control board or accompanyng wiring may
destroy the electronic modules or electrical components.
Risk of clogged or leaking drain lines. Can cause equipment and building damage. This unit requires a water drain
connection. Drain lines must be inspected regularly and maintenance must be performed to ensure that drain water
runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no
visible sign of damage or leaks.
This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage can
4
NOTE result in severe property damage and loss of critical equipment. Do not locate unit directly above any equipment that
could sustain water damage.
FEATURES / BENEFITS
reviewed. Our products have efficiency certifications is specially designed to work properly and with
from AHRI and electrical certifications from ETL, minimal vibration and noise.
Once the unit is set, operation is a matter of we also comply with all industry safety standards.
pressing the start and stop button and making We are members of the American Society of All units have a compact and sturdy structure
sure that the unit operates properly, after this Air Conditioning, Refrigeration and Heating while maintaining a slim profile.
the unit will operate automatically, starting itself Engineers (ASHRAE). To support our commitment
according to the demand of the cooling system to customers and our stakeholders our units have
and local conditions. a 1 year mayor warranty after start up, .
• Flexibility
Our units use R410A refrigerant, which is
harmless to the ozone layer and is not toxic or
flammable, even in case of leakage.
The units have smart processors and sensors Finally, the heat exchanger efficiency and
to automatically control the temperature at modular design allow for an easy and quick
optimum operating conditions. installation.
personnel.
(optional sensors).
The simplicity in the design of each unit
allows maximum ease in maintenance. All mayor
The control and monitoring system ensures
components are available to maintenance
the proper operation of the unit by monitoring
personnel by opening the service panel. If an
in real time the health of all mayor components
emergency stop occurs, the control section will
(high and low refrigerant pressure, compressors
indicate the detailed cause of the failure, helping
and fan motors health, etc).
to accelerate and facilitate the solution process.
In case of a malfunction the event will be
recorded for later analysis, facilitating the location
of the possible failure and its solution.
GENERAL DESCRIPTION
savings in the use of refrigerant gas. motors. The fans are weatherproof to ensure
• Compressor continuous operation.
• Thermostatic Expansion
Our two-stage, fixed scroll, digital and
Valve • Expansion Tank
variable compressors have better liquid handling
properties. Because of its axial and radial shape, Used in the system to handle the volume
it allows parts of the scroll to be separated in The Thermostatic Expansion Valve (TEV) variations of the liquid contained in the pipe
the presence of coolant, thus offering protection keeps the evaporator stocked with sufficient system due to temperature changes.
against liquid damage. refrigerant to meet load conditions. It has no way
to turn on or off the compressor, but keeps the
They are more efficient over the full operating superheated refrigerant itself in the suction line • FlowCon Valve
range, operating at sound levels and lower of the compressor. The thermostatic expansion
valve installed in each circuit has been selected This balancing valve is placed in the unit in
vibration than traditional compressors, it has 70%
for a range of specific operation conditions. order to control and maintain a constant water
fewer moving parts, startability under any load
flow in the circuit, with the special feature that
on the system, without removing components,
the flow can be adjusted anytime as needed.
easy service and maintenance due to its compact
size and lightweight and simple design, built
to achieve optimum performance with current
refrigerants without chlorine, without complex
• Temperature Sensor
internal suction valves and discharge for quieter Through digital signals generated by these
operation and increased reliability. devices the temperature is measured accurately
and in real time.
VRW
This units are pioneers in the VRW technology. The most important advantages are no loss of
performance tonnes over distance, uses water as heat medium, requires no special installation, far
better performance at a lower cost.
• UV resistance
• A crystalline finished, non-yellowing
• Positively charged coating to repel H2O
• Magnificent luster and depth of image retention
• Outstanding resistance to solvents and chemicals
• Exceptional abrasion resistance
GENERAL DESCRIPTION
• Energy Efficient
With Corrosion Protection you save energy between 9% to 15%. Its
sealant layer of only 3-5 microns allows heat transfer be more efficient.
GENERAL DESCRIPTION
Code: DYD-M009 Version: 0 Date:
11
Model no. E-JUST2.Y.G Pressure range ΔP: 20-400 kPaD 2.9-58 psid
l/sec l/hr GPM Flowcon Setting Model no. E-JUST3.G.B
0.149 535 2.36 1.0 l/sec l/hr GPM Flowcon Setting
0.220 793 3.49 1.1 0.883 3180 14.0 1.0
0.289 1040 4.58 1.2 1.140 4100 18.0 1.1
0.355 1280 5.63 1.3 1.700 4940 21.7 1.2
3 TR. 0.418 1510 6.63 1.4 1.590 5710 25.1 1.3
0.479 1730 7.60 1.5 1.780 6420 28.3 1.4
0.538 1940 8.52 1.6 12.5 TR. 1.960 7070 31.1 1.5
0.594 2140 9.41 1.7 2.130 7660 33.7 1.6
0.647 2330 10.30 1.8 2.280 8200 36.1 1.7
0.699 2520 11.10 1.9 2.410 8700 38.3 1.8
5 TR. 0.748 2690 11.90 2.0 2.540 9150 40.3 1.9
0.795 2860 12.60 2.1 2.660 9570 42.1 2.0
0.841 3030 13.30 2.2 2.770 9960 43.8 2.1
GENERAL DESCRIPTION
Nominal flow rate
Nominalflow rate
3.190 11500 50.6 2.6
1.070 3870 17.00 2.8 3.260 11700 51.7 2.7
1.110 3990 17.60 2.9 3.320 12000 52.7 2.8
7.5 TR. 1.140 4100 18.10 3.0 3.390 12200 53.7 2.9
1.170 4220 18.60 3.1 3.450 12400 54.6 3.0
1.200 1320 19.00 3.2 3.510 12600 55.6 3.1
1.230 4420 19.50 3.3 3.560 12800 56.5 3.2
1.260 4520 19.90 3.4 3.620 13000 57.3 3.3
1.280 4620 20.30 3.5 3.670 13200 58.2 3.4
1.310 4710 20.70 3.6 3.730 13400 59.1 3.5
1.330 4800 21.10 3.7 3.780 13600 59.9 3.6
1.360 4890 21.50 3.8 25 TR. 3.830 13800 60.8 3.7
1.380 4970 21.90 3.9 3.890 14000 61.6 3.8
1.400 5050 22.30 4.0 3.940 14200 62.4 3.9
1.430 5130 22.60 4.1 3.990 14400 63.3 4.0
1.450 5210 23.00 4.2 4.050 14600 64.1 4.1
1.470 5290 23.30 4.3 4.100 14800 65.0 4.2
1.490 5370 23.60 4.4 4.150 14900 65.8 4.3
10 TR. 1.510 5440 24.00 4.5 4.200 15100 66.6 4.4
1.530 5520 24.30 4.6 4.250 15300 67.4 4.5
4.300 15500 68.2 4.6
4.350 15700 68.9 4.7
GENERAL DESCRIPTION
H1 H3
Calibration
H2 H2
L L
Model Calibration
Clic 25 TR. 3.7
Flow direction
ANALOGUE POINTS
14 Code: DYD-M009 Version: 0 Date:
BMS MODBUS MODBUS FUNCTION BMS MODBUS MODBUS FUNCTION
CODE BACNET ADRESS CODE BACNET ADRESS
ADRESS TYPE READ ADRESS TYPE READ
Al_Fases_M 3 0 Coil ED_AP_E2 197 51 DigitalInput
Al_Baja_pres_CM 4 1 Coil ED_Baja_Pres_E2 198 52 DigitalInput
Al_Alta_pres_CM 5 3 Coil ED_Monitor_Fases_E2 199 53 DigitalInput
Al_congelamiento_M 6 4 Coil ED_sensor_flujo_E2 200 54 DigitalInput
Al_flujoM 9 5 Coil ED_AP_E3 202 55 DigitalInput
Al_Fases_E1 26 6 Coil ED_Baja_Pres_E3 203 56 DigitalInput
Al_Baja_pres_E1 27 7 Coil ED_Monitor_Fases_E3 204 57 DigitalInput
Al_Alta_pres_E1 28 8 Coil ED_sensor_flujo_E3 205 58 DigitalInput
Al_congelamiento_E1 29 9 Coil ED_AP_E4 207 59 DigitalInput
Al_flujoE1 32 10 Coil ED_Baja_Pres_E4 208 60 DigitalInput
Al_Fases_E2 41 11 Coil ED_Monitor_Fases_E4 209 61 DigitalInput
Al_Baja_pres_E2 42 12 Coil ED_sensor_flujo_E4 210 62 DigitalInput
Al_Alta_pres_E2 43 13 Coil CompMaes 212 63 DigitalInput
Al_congelamiento_E2 44 14 Coil BombaM 214 64 DigitalInput
Al_flujoE2 47 15 Coil Ventilador_M 215 65 DigitalInput
Al_flujo_Cond_E2 48 16 Coil Comp_E1 216 66 DigitalInput
Al_Fases_E3 56 17 Coil Ventilador_E1 218 67 DigitalInput
Al_Baja_pres_E3 57 18 Coil Valv_rev_M 219 68 DigitalInput
Al_Alta_pres_E3 58 19 Coil BombaE2 221 69 DigitalInput
Al_congelamiento_E3 59 20 Coil Ventilador_E2 222 70 DigitalInput
Al_flujoE3 62 21 Coil Comp_E3 223 71 DigitalInput
Al_Fases_E4 71 22 Coil Ventilador_E3 225 72 DigitalInput
Al_Baja_pres_E4 72 23 Coil Comp_E4 226 73 DigitalInput
Al_Alta_pres_E4 73 24 Coil Ventilador_E4 228 74 DigitalInput
MAPPING TABLES
Al_congelamiento_E4 74 25 Coil Modo_B_C 236 75 Coil
Al_flujoE4 77 26 Coil Al_Agua_Helada_M 238 76 Coil
Al_E1_Offline 80 27 Coil Al_Agua_Helada_E1 239 77 Coil
Al_E2_Offline 81 28 Coil Al_Agua_Helada_E2 240 78 Coil
Al_E3_Offline 82 29 Coil Al_Agua_Helada_E3 241 79 Coil
Al_E4_Offline 83 30 Coil Al_Agua_Helada_E4 242 80 Coil
Al_EAux1_Offline 84 31 Coil Falla_Cont_Cong_M 247 81 Coil
on_off2 85 32 Coil Falla_Cont_Cong_E1 248 82 Coil
Al_Sens_Flujo_M 94 33 Coil Falla_Cont_Cong_E2 249 83 Coil
Al_EAux2_Offline 100 34 Coil Falla_Cont_Cong_E3 250 84 Coil
Reset_Als 112 35 Coil Falla_Cont_Cong_E4 251 85 Coil
Al_Sens_Flujo_E1 126 36 Coil Term_Ch_BC 253 86 Coil
Al_Sens_Flujo_E2 127 37 Coil ED_Humo 261 87 Coil
Al_Sens_Flujo_E3 131 38 Coil ED_Incendio 262 88 Coil
Al_Sens_Flujo_E4 132 39 Coil ED_Inundacion 263 89 Coil
ON_OFF (estado) 143 40 DigitalInput Alarma_Humo 268 90 Coil
ED_sensor_flujo_Maestro 164 41 DigitalInput Alarma_Incendio 269 91 Coil
ED_Monitor_Fases_Maestro 165 42 DigitalInput Alarma_Inundacion 270 92 Coil
ED_Baja_Pres_Maestro 166 43 DigitalInput Al_EAux3_Offline 303 93 Coil
ED_AP_Maestro 167 44 DigitalInput AlarmMantCM 304 94 Coil
on_off3 ( entrada) 168 45 DigitalInput AlarmMantBM 305 95 Coil
ED_selector 169 46 DigitalInput AlarmMantCE1 306 96 Coil
ED_AP_E1 192 47 DigitalInput AlarmMantBE1 307 97 Coil
ED_Baja_Pres_E1 193 48 DigitalInput AlarmMantCE2 308 98 Coil
ED_Monitor_Fases_E1 194 49 DigitalInput AlarmMantBE2 309 99 Coil
ED_sensor_flujo_E1 195 50 DigitalInput
DIGITAL POINTS
Code: DYD-M009 Version: 0 Date:
15
SINGLE UNIT CONFIGURATION DIMENSIONS
SUPERIOR VIEW
W
DESIGN PARAMETERS
ISOMETRIC VIEW
FRONT VIEW
SIDE VIEW
L2 W 86 3/4"
D 32 1/4"
H 83 1/4"
L1 72 3/4"
L2 10 1/2"
H
L1
16
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
DESIGN PARAMETERS
ISOMÉTRIC VIEW
W 86 3/4"
L2
D 64 1/2"
H 83 1/4"
L1 72 3/4"
L2 10 1/2"
L1 H
D
4" VITAULIC CONNECTIONS
17
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
TOP VIEW
W
DESIGN PARAMETERS
ISOMETRIC VIEW
L2
W 86 3/4"
D 116 7/16"
H 83 1/4"
L1 72 3/4"
H L2 10 1/2"
L1
18
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
TOP VIEW
DESIGN PARAMETERS
ISOMETRIC VIEW
L2
W 86 3/4"
D 148 11/16"
H 83 1/4"
L1 72 3/4"
H L2 10 1/2"
L1
19
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
ISOMETRIC VIEW
TOP VIEW
W
DESIGN PARAMETERS
L2 W 86 3/4"
D 200 5/8"
H 83 1/4"
L1 72 3/4"
H
L1 L2 10 1/2"
20
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
ISOMETRIC VIEW
TOP VIEW
DESIGN PARAMETERS
FRONT VIEW SIDE VIEW
W 86 3/4"
L2
D 284 3/4"
H 83 1/4"
L1 72 3/4"
H
L1 L2 10 1/2"
L3 19 5/8"
21
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
ISOMETRIC VIEW
TOP VIEW
DESIGN PARAMETERS
22
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
ISOMETRIC VIEW
TOP VIEW
DESIGN PARAMETERS
W
L1
H L2 10 1/2"
23
Note: Visually and physically identify the water injection and water return connections in the equipment through the placards “Water In” and “Water Out”.Due to design changes, your equipment may have a different layout
than the one shown on this manual.
B C
CONDUIT
MONITOR
DESIGN PARAMETERS
CLIC-ACC-1800-A-0-2-T-T-N-0-S M S S S S S 291.2 307.7
CLIC-ACC-2100-A-0-2-T-T-N-0-S M S S S S S S 332.1 358.8
CLIC-ACC-2400-A-0-2-T-T-N-0-S M S S S S S S S 373.0 410.0
CLIC-ACC-2700-A-0-2-T-T-N-0-S M S S S S S S S S 413.9 461.1
CLIC-ACC-3000-A-0-2-T-T-N-0-S M S S S S S S S S S 454.8 512.2
CLIC-ACC-3300-A-0-2-T-T-N-0-S M S S S S S S S S S S 495.7 563.3
CLIC-ACC-3600-A-0-2-T-T-N-0-S M S S S S S S S S S S S 536.6 614.5
DESIGN PARAMETERS
Code: DYD-M009 Version: 0 Date:
27
THREE UNITS POWER CONNECTION (MULTI POINT CONNECTION)
CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL
CONNECTION BETWEEN EQUIPMENTS (ARMORED)
DESIGN PARAMETERS
SIX UNITS POWER CONNECTION (MULTI POINT CONNECTION)
CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL
CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL
CONNECTION BETWEEN EQUIPMENTS (ARMORED)
DESIGN PARAMETERS
CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL CONTROL PANEL
CONNECTION BETWEEN EQUIPMENTS (ARMORED)
Flange
Threaded Nipple
Grooved Nipple
DESIGN PARAMETERS
Ø4"
Equipment Capacity # Modules GPM φ Vitaulic CDP ft w.g. (Mother) Val. Reg. Val. Sec CPD Tub+Acc CPD Total
M 25 1 60 4 16.01 6.93 0.47 0.05 24.63
M+E 50 2 120 4 16.01 6.93 0.47 0.36 24.96
M+(E*2) 75 3 180 4 16.01 6.93 0.47 1.16 25.80
M+(E*3) 100 4 240 4 16.01 6.93 0.47 2.64 27.36
M+(E*4) 125 5 300 4 16.01 6.93 0.47 5.04 29.88
M+(E*5) 150 6 360 4 16.01 6.93 0.47 8.56 33.58
M+(E*6) 175 7 420 6 16.01 6.93 0.47 2.39 27.09
M+(E*7) 200 8 480 6 16.01 6.93 0.47 3.50 28.26
M+(E*8) 225 9 540 6 16.01 6.93 0.47 4.93 29.76
M+(E*9) 250 10 600 6 16.01 6.93 0.47 6.69 31.61
• INTRODUCTION
Welcome to CFs operation manual to control one or several water chillers
jointly by using the head temperature sensors, or control independent
units by using the injection temperature sensors in each unit. The system is
designed to control a unit with capacity control by an inverter or a typical
unloader valve in a Digital scroll compressor, this is a "Mother" unit, and
up to four additional units without capacity control, called "Sons" may be
added.
• USED HARDWARE
The "Mother" unit is directly controlled by the main controller, the pCO.
Each "Son" unit is controlled by an expansion module PCOE. If the units are
cooled by water, it requires an extra expansion module for every four “Son”
units.
Each master unit has a 7 inches pGD Touch Tactile Terminal.
CONTROL
Code: DYD-M009 Version: 0 Date:
33
PCO (CONTROL)
Optional Equipment REF. DESCRIPTION
The pCOOEM+ is a microprocessor-based, programmable electronic 1 POWER CONNEC TOR [G(+), G0(-)]
controller that is fully compatible (hardware and software) with the pCO
System family of devices, which includes programmable controllers, user 2 Button for setting pLAN address and secondary display, LEDs
terminals, gateways, communication devices and remote management
devices. These devices represent a powerful control system that can be 3 Universal inputs/outputs
easily interfaced with most Building Management Systems (BMS) available +Vdc: power to active probes
on the market. 4
+5 VR power to ratiometric probes
5 Analogue outputs
7 Fieldbus1 connector
8 BMS2 connector
The pDG Touch 7 inch graphic terminal belongs to the family of touch screen terminals designed
2 Preset for membrane keypad
to make user interface with controllers in the pCO system family easy and intuitive. The electronic
technology used and the new 64K colors display allows high quality images and advanced functionality 3 RS485 port optically-isollated
to obtain a high aesthetic standard. The touch screen panel also facilitates human-machine interaction
making it easier to navigate between the various screens. 4 Ethernet Port 1 (internal switch)
G G0
2 1 3 4 5 6 7 8 9
8 Power supply
EXPANSION BOARD
8 1 POWER CONNECTOR [G(+), G0(-)]
C1
NC1
NO2
C2
NC2
NO3
C3
NC3
NO4
C4
NC4
J5 J6 J7 J8
CONTROL
RS485 network connector (GND, T+, T-) or
B1
B2
GND
+5V Ref
+Vdc
B3
B4
GND
+5V Ref
+Vdc
7 J9 J10
3
tLAN (GND)
Optically-isolated digital inputs, at 24 Vac/
4
Vdc
expansion board
5 Yellow power LED and 3 indicator
4 J4 Serial
6 Serial address
Address
6
IDC1
ID1
ID2
ID3
ID4
1 2 3 4
J1 24Vac J2 J3
tLAN 7 Analogue inputs and power to
GND
VG0
VG
G0
Y1
T+
G
T-
TEMPERATURE SENSOR
DIAGNOSIS INDICATING LIGHTS PT10K NTC temperature sensor, resistive to
(LED STATUS) the sensor response to temperature changes,
the relationship of the curve is at a higher
NORMAL OPERATION CONSTANT GREEN
temperature, the less resistance and vice versa.
START DELAY INTEMITENT GREEN
CONTROL
• pCO Digital Outputs (Mother Unit)
Note**: The digital output pump in “Son” Port CO Air HP Air CO Water HP Water
units depends on the initial configuration of
NO1 Comp.1stage/Fan Comp.1stage/Fan - -
the system. It will not be used if the system is
configured with a single Mother pump (pCO NO2 **Pump **Pump - -
unit). NO3 Second Stage Second Stage - -
NO4 Reversible Valve - -
(Fig. 1)
• COMPRESSOR COMPRESOR
Set the switch to the ON position (Figure 2), this will allow the compressor to turn ON and OFF according to the status.
NOTE: Once the pump is turned on it starts a delay of a few seconds until a uniform water flow is detected, at the end of
this delay, the flow switch is monitored, if the switch is open it commands the pump to shutdown (5 tries within a space of 10
seconds), if a uniform water flow is detected the unit starts its operation.
Under normal conditions, the equipment will operate turning on and off the cooling circuit of the unit, according to the
cooling demand. When alarms are presented in the system it will always be indicated on the user interface. (Fig. 2)
The digital control will begin the operation of the compressors according to the logic set on the control.
CONTROL
"ON" (Fig. 3) position.
After a few seconds the computer will command the power of the water pump. If the computer detects water flow it will
command the start of the internal control sequence of this unit.
(Fig. 3)
When the unit is turned on, if all security and safety measures are ok (vacuum pressure, discharge, phase
monitor), the pumps from all the enabled units will be turned on.
Fig. 4 shows the pump start flow diagram.
YES
Unit Ready
to Start
Wait time for
Pump Flow
digital input flow
Starts detected?
detection
NO
Fig.4
Pumps startup control flowchart (applies for any unit).If the number of tries for pump start is exceeded, the general flow alarm
will be tripped, this will halt all further operations in that unit until the alarm is reset.
If after the timeout flow detection, digital input status change is detected, the unit start is enabled by demand for the unit in question. Fig. 5 shows
an example of this case.
If the flow detection fails after the elapsed time for digital input detection, it is necessary to turn off the pump and back on to make an attempt to
start after the waiting time between attempts has elapsed. If after a certain number of attempts flow is still undetected, the flow alarm is triggered and
the operation of the unit in question is disabled, as illustrated by Fig. 6.
Flow Alarm
Flow Alarm
Bomb
Bomb
Time
Time Detection Time
Time Detection Time between attempts
Time between attempts
Fig. 5 Fig. 6
Example of a pump startup routine where flow is detected in the second attempt. Example of a pump startup routine where flow is not detected, after 3 attempts the
flow alarm is tripped.
CONTROL
Note: If the system has an ultrasonic water flow sensor, the digital input
for this value is a virtual input, with a value of “1” or “ok” if the water flow
is the acceptable.
In "Tandem" mode, the control temperature is the reading from the main head sensor. From this reading the global demand is calculated. Fig. 7 shows
an example of calculating demand when the control is set to "Proportional". If the units are in "independent mode", each unit calculates its local demand
from its injection temperature sensor. Local demand for the Mother unit is generated by the same PID control equations, while the demand for Son units
is a starting and stopping cycle with hysteresis, as Fig. 8 shows.
The choice between heating and cooling (when the system was configured as a heat pump) can be performed by the digital input "selector" or by the
user terminal. All units in a tandem always work in the same mode.
Demand (%)
Demand (%)
Temperature Temperature
Fig. 7 Fig. 8
Example of proportional control routine in the case of global demand Example of a proportional control routine for the case of local demand for each son
or demand for mother unit. unit.
Tons of Refrigeration
units are operating, the system will request the start or stop of units to meet 20
demand. In any configuration, the mother compressor (whose capacity is
controlled by a variator or flow valve) is the first to start and the last to stop.
Fig. 9 shows an example of the management of the global demand starting 10
requested, and the system is working in “Tandem Mode”, the system can
perform the rotation of units for better wear balance between the units. The
Fig. 9
types of rotation that may be performed include: Example of managed delivered capacity according to demand, for a mother unit and
two son units of 10T cooling each.
• FIFO. The first unit to start is the first unit to stop.
FAN CONTROL
• LIFO. The first unit to start is the last unit to stop.
• Cumulative operation time. Always starts first the unit with fewer hours
of accumulated work, and the first unit turned off is the one with the most For air-cooled units, the startup routine of the condensing unit is
accomplished in two parts: the fan start and a timeout after the compressor
cumulative hours. start. When the stop of the unit is requested we proceed in the same way,
• Custom. You assign priorities to start and stop each unit. the compressor stops and a scheduled time later the fan stops.
Note: Regardless of the type of unit rotation set, the unit with frequency Procedures for starting and stopping the condensing unit of an air
variator or discharger remains the first to start and the last to stop. cooled machine is shown in Fig. 10.
Note: If a unit is working and stops for any situation (like an alarm), it
will be replaced by the next available unit in the rotation algorithm.
CONTROL
Fan
cooling) or stopping the compressor without stopping the fan. This deicing
is performed simultaneously in all units enabled in the system. You can set Fig. 10
the frequency, mode of work, its duration, and the duration of the drip. This Procedure for starting and stopping of air cooled condensing units.
deice routine can be disabled by the user.
Note*: the BMS1 port requires a communications card (pCOnet to BACnet MS/TP or
pCOweb for BACnet IP). Programming of the logical package in the alternate protocol is
also needed.
NOTE Also can be connected a FLG- Modbus to connect a bacnet MS/TP.
• Phase Failure Alarm: activated by a digital input. The MotorSaver alarm is a high priority situation and stops all machine functions. It is manually reset.
• No Flow Alarm: The No Flow Alarm is a high priority alarm and must be manually reset. This alarm stops all machine functions.
• Freezing Alarm: If the freezing temperature sensor is below a programmed threshold, the freeze alarm is triggered. This condition stops all functions of
the equipment in question. This alarm is automatically restored when the temperature exceeds a value of restitution and keeping the unit in reset mode
(no power to operate) for the scheduled time.
• Freezing Water Alarm: Same case as the freezing alarm, but in this alarm the reading from the injection sensor is considered.
• High Pressure Alarm: It is activated through a digital input. This alarm is a high priority event and stops compressor operation; but it does not stop the
pump. It is a manually reset alarm. If the unit is cooled by air a command is sent to start the fan of the condenser unit. To restore keep the unit in high
return, the compressor will not start until the scheduled time has elapsed.
• Low Pressure Alarm: It is activated through a digital input. This alarm stops the compressor of the unit in question. It is automatically restored but
keeps the unit in a low return mode.
• Disconnection Alarm: If the system was setup with any “Son” units and any of these units disconnects this alarm will be trigged.
CONTROL
• Condenser High Temperature Alarm: This alarm is enabled only when the unit is air-cooled. The alarm is activated when the reading from the
condenser temperature sensor exceeds its limit. No control action is taken.
• Condensate Flow Alarm: the condensate flow alarm functions like the main flow alarm; the alarm routine is activated only when the system is cooled
by water.
• Lack of Refrigerant Alarm: this alarm is activated when a start command is sent because of cooling demand, and after a while no temperature change
is detected in the injection temperature sensor. This alarm takes no action control and can be disabled by the user.
shown.
CONTROL
5. Temperature metric selection (farenheit or • Temperature Graphics
celcius) • Alarms
6. Date • System Overview
• Navigation Menu
• Active Alarms
By pressing the "No Alarms" button, the user will be shown a screen like By pressing the "Alarm Present" button, the alarm screen shown below
the one shown below: is displayed. In this screen all alarms that are active at that time are shown.
Any alarm can be reset with the "Reset" button. It is worth mentioning that
if the alarm condition is not corrected, the alarm will be triggered again.
CONTROL
The graphics properties that can be edited are: Duration (time scale)
and minimum and maximum limits (temperature scale). These properties
are edited in the navigation menu screens where graphics are displayed by
pressing the "graphics settings" button.
The pGD Touch terminal stores a reading for each of the temperatures
mentioned (head injection and return, and injection temperature for every
unit enabled) every 180 seconds (every 3 min) and may save up to 100,000
data samples before rewriting the oldest data. With these parameters, the
pGDTouch can store data up to seven months old (208 days old).
In this screen you can see the alarms that have been activated in a given
CONTROL
period of time. These records are stored in the internal memory of the
terminal so it does not matter if the alarm condition is no longer present, it
will be saved in memory for review at a later time.
CONTROL
Code: DYD-M009 Version: 0 Date:
51
SUMMARY
In the summary page you can view the status and operation of the
whole system. The first screen shows all configured units; the state of the
temperature control (tandem or independent), the operation mode (cooling
or heating), and the state of the compressors. If the control is in “Tandem
Mode” it will also indicate the overall system demand and the next unit to
start and stop according to the established rotation order and the priority
of the units.
In the navigation bar of these pages is the icon of "Input / Output". This
will display a screen with the explicit information of all inputs and outputs
of the configured devices in the initial setup.
This screen is also accessible via the navigation button with Level 1
"Maintenance".
CONTROL
Code: DYD-M009 Version: 0 Date:
53
REGULATION
In the regulation section, the user can modify
to standalone mode.
section). If the working mode selection is done via digital input any other
selection at the terminal will be ignored. If the work mode selection is set by
the user at the terminal, only via this screen can the work mode be edited
CONTROL
or changed, ignoring the state of the digital input.
Clock Adjustment
In the clock settings page the user can set and change the date, time
and how to display the date: there are two options, standard format (day-
Note: To set PD control, select PID and set the integral time to 0.
CONTROL
Note: Even if you select the rotation type as • If the type of rotation is selected as Custom, a window will be enabled to prioritize the start and stop
custom, the unit with frequency variator or
of the units enabled with the button marked
unloader (master unit) will always be the first
to be turned on and the last to be turned off, • The order of priority is ascending, with 1 being the highest and 5 the lowest priority.
regardless of their assigned priority.
• The available unit (without alarms) with higher priority is first turned on or stopped.
As the master unit can regulate its capacity, it has a single proportional control algorithm, P + I,
or PID with independent parameters to the central control. If you want to set the PD control, the user
• Remove the integral error when the set point is reached to avoid fluctuations inherent to the
integral control.
• Integral time
• Derivative time
CONTROL
Set point, for cool as well as heat mode, in General the diferrential ON will be the
to avoid a frezzin or cold water alarm in TANDEM
value to ON and the differential OFF the value to OFF, always respectly the set
(central) mode, the function y same as the general is
point of the unit
respectly the set point,
Example
Differential ON = 5
Note: The diferential ON in general an Sons part
Differential OFF = 0
should be always >0 ,If not the unit never turn ON
Set point = 50
The unit will start in set pojnt + 5 (55) and will turn off in set point -0 (55)
Also you can calibrate the minimum flow to be permitted to start the For water heat pump you will see the condenser sensor, don’t change
system, the chiller system require 2.4 Gal/min per Ton. So if you have a the Max and Min. Value shoul be configured in the facility
10 Ton chiller you will need 24 gal/min, in some cases if the hydronic
installation can´t provide these flow you can rise to 80 % of you permited
flow to reduce the flow alarms, be carful to decrease down to 80 %, could
have several problems in your system
CONTROL
This kind of sensor can´t messure up to 39.6 gal/min so if you have more
of this value the value in tne display tag going to show 295.6 prox. Check
your hydronic system to regulate the flow.
The value consider acceptable will be the same for evaporator and
60
condenser sensor.
DELETE RECORDS
In the last section of the level 2 navigation menu, the user may delete
historical graphics and alarm records from the internal memory of the
pGDTouch terminal.
Note: If the records are deleted they cannot be recovered later.
CONTROL
Code: DYD-M009 Version: 0 Date:
61
CONFIGURATION Global Parameters
The global configuration of the system is • Reset Delay: if the controller is turned off,
protected by password access level 3. when resetting the controller will wait
In the configuration section are the global this time before beginning regulatory
parameters of the system. These are separated processes.
into three categories: • Enable unit on by digital input
• Selecting the operating mode
• Set point Safety Limits
Network Communication
The controller port BMS2 may be used for
monitoring the entire system remotely with an
external supervisor via Modbus RTU protocol.
On this screen the user sets the parameters
of the communication protocol to link to the
external device. These parameters are:
• Address
• Speed (baud per second)
• Stop bits
• Parity
Defrost Configuration
Only for Air-Water Systems with Heat Pump
Function 1
CONTROL
62
7. Activate fan while dripping
8. Defrost halting
The minimum demand to start the master unit is also set here. If the unit
is modulated by a downloader the period is also set here.
You can also determine if the units are of different capacities (only if at
least one “Son” is present).
On the second page of the Devices section, the user sets the parameters
for the alarm routines. The screen contains four groups (or five if the units
are air-water); the following are the alarm routines:
• Water Flow Alarm
• Ice Water / Freezing Alarm
Unit Capacity: Unit protection time lapse: • Low Vacuum Pressure and High Discharge Alarm
If the system is set up with units • Charging time (time between
CONTROL
• Refrigerant Alarm
of different capacities, a button starts of multiple units)
will be enabled that will open this • Discharge time (time between • Condensing Unit High Temperature Alarm (only for air-water equipment)
window, here the user may set the the stop of several units)
enabled units individual capacity. • Minimum time for compressors
cycles
• Minimum time for pump stop
• Start Delay and fan stop (Only
for air-water equipment).
• Waiting time for detection of the digital input once the pump has been
turned on
• Number of attempts to start the pump in case of digital inflow detection
failure
• Timeout between attempts to start the pump
For each of the alarms a trigger value, restoration time and recovery
time (in which the active alarm unit will not restart) should be established.
CONTROL
Each unit has an internal counter that keeps track of how many times
the unit has had a freezing or cold water alarm. If the unit exceeds a certain
number of alarms in a given time, the continuous freezing alarm will be
triggered, which will disable the unit until the user reestablishes the unit.
The high pressure alarm does not reset automatically, the user must
restart it manually. The low pressure alarm is automatically restored when
a change is detected in the corresponding digital input. During alarm
reestablishment the compressor is disabled during the recovery time that
the user sets in this section.
REFRIGERANT ALARM
The Refrigerant Alarm is a user-enabled warning that evaluates the
change in the injection temperature sensor when the compressor starts
working. If it detects a change in the given time the alarm is triggered. This
alarm will not stop any routine control. In this section the user can enable
or disable the alarm, and if applicable, set the minimum detection rate and
the maximum time in which this change should happen to not trigger the
alarm.
CONTROL
CONDENSING UNIT
HIGH TEMPERATURE ALARM
This routine is only enabled if the System is air cooled
brand new installation and re-establish the initial settings. The restoration
resets the parameters of initial system configuration, but does not modify
any other values stored in the controller memory (set points, differentials,
alarms, etc.).
with the new configuration for the correct operation of the units.
Note: When the system is restored, the user must restart both the
controller (pCO) and the terminal (pGDTouch).
CONTROL
Son Unit 1 1
Son Unit 2 2
Son Unit 3 3
Son Unit 4 4
CONTROL
Direction 1 Direction 5
Note: It is important that the addresses are not repeated, or the entire
network of instruments on that port may collapse.
1. Installation
the installation manual. The unit must operate normally and should not be
in alarm condition.
CONNECTIVITY
2. Connectivity
cable.
service provider.
but you may need to seek this option in the other menus of your router. Use
the data of the DDNS host you want to use to configure your connection
provider
• Host: ACunit
• Domain: MyDomain.Com
• Contraseña: 1234567890
The combination of the DDNS host and domain results in the final
for each unit to be hooked up to the internet and is the internet address Domain Name: ACunit.MyDomain.com
you can use to access your unit from outside (WAN) of your local area Internal IP: 192.168.1.61
network (LAN). Along with the DDNS "host" the unit will have an IP address
area network.
70
address.
COMMUNICATION / CONNECTIVITY
You need to allow outside access to your unit through your local area You need to have the Google Chrome browser
network (LAN). The easiest way is to put your unit in the Demilitarized Zone installed on the device from which you want to
(DMZ) of your router. The DMZ (Demilitarized Zone) allows full interaction control the unit and download and install the VNC
of computer signals and commands from the outside, thus avoiding having Viewer extension for Google Chrome. If you still have
to edit or change your local safety schemes. Look in your router's DMZ not installed Google Chrome you can download and
section, correctly select the connected equipment you want to place in the install it for free at www.google.com
DMZ and save your settings. VNC is a technology that allows to access and manipulate remote
Google Chrome, these instructions work for Windows, iOS and Android:
• 4.1. Enter Google Play Store and search for "VNC Viewer for Chrome".
• 4.2. Once on the VNC Viewer for Google Chrome screen click FREE, the
APP will download, please proceed to install it like any other APP on your
device.
76
STRENGTH DIAGRAM: CLIC-ACC-300-A3V-M
Code: DYD-M009
Version: 0
Date:
ELECTRICAL INFORMATION
77
78
CONTROL DIAGRAM: CLIC-ACC-300-A3F-S
Code: DYD-M009
Version: 0
Date:
ELECTRICAL INFORMATION
79
80
CONTROL DIAGRAM: CLIC-ACC-300-A2V-M
Code: DYD-M009
Version: 0
Date:
ELECTRICAL INFORMATION
81
82
CONNECTION DIAGRAM: CLIC-ACC-300-A2V-M
Code: DYD-M009
Version: 0
Date:
ELECTRICAL INFORMATION
83
84
STRENGTH DIAGRAM: CLIC-ACC-300-A2F-S
Code: DYD-M009
Version: 0
Date:
• LOCATION
The units must be installed in accordance
Surrounding Wall
These Units are designed to be installed
Air Vertical Air Vertical Air Vertical Air Vertical Air Air Flow
Flow Discharge Discharge Discharge Discharge C
in exteriors. It is necessary that the unit has air
A A
INSTALLATION
Fig. 13, Recommended unit clearences.
86
WARNING
Damage must not be repaired before the inspection of the transportation company representative and the manufacturer's representative. Before
installing the unit, check that the model and power supply voltage shown on the nameplate are correct. The manufacturer will not accept responsibility
for any damage following acceptance of the unit.
Provide enough space around the outdoor unit to allow the installation and maintenance personnel unrestricted access to all service points. Refer to
submittal drawings for the unit dimensions. A minimum of 1 meter is recommended for compressor service. Provide sufficient clearance for the opening
of control panel doors. Refer to Figure 13 for minimum clearances. In all cases, local codes which require additional clearances will take precedence over
these recommendations.
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or
slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains
or slings) may not be of different length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment
INSTALLATION
or property damage. Failure to follow the instructions above or to properly lift the unit could result in unit dropping and possibly
WARNING
crushing operator/technician which could result in death or serious injury.
All wiring must comply with local codes and the National Electric Code. Typical field wiring diagrams are included at the end of the
manual. Minimum circuit ampacities and other unit electrical data are on the unit nameplate. See the unit order specifications for actual
electrical data. Specific electrical schematics and connection diagrams are shipped with the unit.
• All the terminals and connections must be tightened. Improper connection and fastenings could cause electric shock, short circuit and fire.
• Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
• The unit must be GROUNDED to prevent possible hazards due to insulation failure.
• All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any moving parts of the fan motors.
• Do not operate the chiller with wet hands. It could result in electric shock.
• Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause equipment damage or fire.
• Do not allow water to remain in the water pipes if the unit is not operating for a long period.
Water must be drained out if the unit is not running during winter. Failing to do so would cause the pipe to freeze and crack.
The units have a water input and output for the connection of the chiller to water circuit of the system.
This circuit must be connected to the unit by an authorized technician and must comply with all the current national and local regulations on the
subject.
The components listed below are not included with the unit, but are supplied upon request, also if their installation is compulsory.
If dirt penetrates the water circuit, there could be problems. Therefore always remember the following when connecting the water circuit:
The water pressure must not exceed the maximum operating pressure for the unit.
88
WARNING
CHARGE
completed.
evacuation.
To make a proper evacuation, it is necessary to have a VACUUM PUMP REFRIGERANT CHARGE
(not compressor) and a vacuum gauge. After evacuating the system appropriately, close the valves of the
The procedure is the following: manifold and isolate the vacuum pump, the vacuum gauge and the
• First the access points to the system must be defined. Use the service Nitrogen cylinder.
valves in the outdoor unit on both the drop and the discharge sides To do the refrigerant charge, replace the Nitrogen cylinder shown in Fig.
(liquid line). That is, high-pressure valve connected to the piping of 15 with a refrigerant cylinder. Purge the hose that links the cylinder to the
smaller diameter and the low-pressure valve connected in the piping service valve.
of larger diameter. Open the service valve which gives access to the refrigerant cylinder and
• Only then is it possible to evacuate the system. Basically, we can do then the high-pressure valve of the manifold.
in two ways: To load the system appropriately, verify in the identification labels of the
* Method of Dilution units the amount of refrigerant that should be added to the system.
Turn on the vacuum pump and make the vacuum in the pump (valve 1 With the system shut down, load the refrigerant in liquid form through
shut). the service valve of liquid line (smaller diameter).
Open valve 1 and let the system evacuate until it reaches at least 500 For help, use a scale (if not using a graduate cylinder). Allow at least 10
microns. To obtain the measure, close valve 1 and open valve number 2, minutes before turning the unit back on.
allowing the vacuum gauge to feel the system pressure. After reaching 500 Close the discharge valve of the manifold, open the suction valve and
microns, isolate the vacuum pump and open valve 3, letting the Nitrogen with the system in operation complete the charge with refrigerant in gas
in to break the vacuum. Isolate the Nitrogen cylinder. form (between 5% and 20% the total). Check in the scale the refrigerant
weight added to the system. When the charge is complete close the suction
INSTALLATION
Purge the Nitrogen through the connection that links the copper
passage to valve 3. valve of the manifold, disconnect the suction and discharge hoses.Close the
cylinder valve.
The charge procedure will be complete.
Never disconnect the copper tube of valve 3; just REFRIGERANT WITHDRAWAL
loosen the connection to purge the nitrogen If for any reason there is need to remove/lose refrigerant, the service
WARNING
valves of these units allow to remove refrigerant from the system into the
Repeat the procedure at least twice, doing in the last stage the third outdoor unit.
evacuation. Procedure:
At the end of this process, at least 200 microns should be obtained. Step 1: Connect manifold hoses to the vents of the outdoor unit service
In order to obtain a precise reading of vacuum one should isolate the valves.
vacuum pump from the system. Close valve 1 and wait about 15 to have Step 2: Close the service valve of 1/4” liquid line.
a precise measure. If the reading doesn’t remain steady either the system Step 3: Turn on the unit in cooling mode until that the system pressure
still contains humidity or there must be a leakage. Always verify all the reaches 2 psig. Then, close the service valve of the suction line 3/8 “ so that
connections (points 1, 3 and valves). the refrigerant gas remains withdrawn.
* High Vacuum Method
It is applied with a vacuum pump capable to reach vacuum lower than
500 microns in only one evacuation. Proceed as follows: The refrigerant must be adjusted a 20% in
1. Turn on the vacuum pump, then open valve 1 (fig 15). Later on, order to reach the evaporation temperature.
89
isolate the vacuum pump and open the valve. NOTE
You can check the charge in the next page.
3 GAS
OUTFLOWN HIGH PRESSURE
FAUCET MANOMETER
2
1
LOW PRESSURE
VACUUMMETER MANOMETER
INSTALLATION
VACUUM PUMP
Fig. 15.- CHART FOR OBTAINING VACUUM AND FOR REFRIGERANT CHARGING
INSTALLATION
-29 -20.2 26.7 0 32.0 100.8 29 84.2 251.1 58 136.4 515.5
-28 -18.4 28.4 1 33.8 104.5 30 86.0 258.0 59 138.2 527.1
-27 -16.6 30.1 2 35.6 108.3 31 87.8 265.2 60 140.0 539.0
-26 -14.8 31.8 3 37.4 112.2 32 89.6 272.4 61 141.8 551.0
-25 -13.0 33.7 4 39.2 116.2 33 91.4 279.8 62 143.6 563.2
-24 -11.2 35.5 5 41.0 120.3 34 93.2 287.4 63 145.4 575.6
-23 -9.4 37.5 6 42.8 124.5 35 95.0 295.1 64 147.2 588.2
-22 -7.6 39.5 7 44.6 128.8 36 96.8 302.9 65 149.0 600.9
-21 -5.8 41.5 8 46.4 133.1 37 98.6 310.9 66 150.8 613.9
-20 -4.0 43.7 9 48.2 137.6 38 100.4 319.0 67 152.6 627.1
-19 -2.2 45.8 10 50.0 142.2 39 102.2 327.3 68 154.4 640.5
-18 -0.4 48.1 11 51.8 146.9 40 104.0 335.7 69 156.2 654.1
-17 1.4 50.4 12 53.6 151.7 41 105.8 344.3 70 158.0 667.8
ADVANTAGES
1. Left and right connection available
2. Accessories included within the equipment:
a) 2 Way control valve (Son equipment)
b) Flow regulation valve
c) Flow switch
d) Sectioning valves
e) “Y” Filter (Optional)
9.- MANOMETER
10.- 90° ELBOW
11.- CLOSURE VALVE
12.- TEE PIPE
13.- AIR PURGE VALVE
DATE:
JOBSITE:
LOCATION:
INSTALLER CONTRACTOR:
TECHNICIAN/COMPANY
INSTALLATION
• Visually check for refrigerant leaks.
side of the circuit, and cleaned once the system´s initial charge is finished.
• Only Open unit to install system piping. Do not remove • Check water filter to be clean.
connection´s protection until hydraulic circuit is to be closed. • Verify that all service valves are open.
• Check for foreign objects in fan discharge. • Check for adequate makeup of the water supply.
• Check that air intake is not obstructed and has the required • Verify that all piping is water full and air has been vented out.
space suggested on Fig. 1 • Check Thermometers.
• Check Manometers.
93
NOTE WARNING
• Verify that the thermo-magnetic switch is of correct capacity for the unit.
• Check that all electrical connections are tight.
• Check for false contacts on ground, and all wiring.
• Check internal connections for control and power.
• Measure voltage on all lines, and ground, neutral, and trifasic line.
• Check for overload protection on motors to be in position to design requirements, and
on automatic mode.
• Check voltage monitor control (*Motor Saver), to be adjusted to supply the correct
power voltage for the unit.
• STARTUP
After energizing the controller, wait five minutes for the unit to be on line and ready.
Operation sequence will initiate by checking all security pre-programed points on the unit. If all
required conditions are OK the unit will be ready to initiate operation.
UNIT CONTROL To start operation set the ON/OFF switch (Fig 15) to the ON position.
After six seconds the controller will command the start of the water pump.
If water flow is detected on the pipes, the internal sequence of the unit
will begin.
INSTALLATION
ON / OFF
DATE: _____________________________________________________________________________________________________________________________________________
JOBSITE: _________________________________________________________________________________________________________________________________________
LOCATION: _______________________________________________________________________________________________________________________________________
SOFTWARE VERSION:______________________________________________________________________________________________________________________________
"Y" FILTER (Y/N): _______ FLOW SWITCH TYPE (X): ULTRASONIC FLOW SENSOR ____________________ FLOW SWITCH_____________________
96
SETTINGS: TEMPERATURE SETTING:______________ DELAY: ____________________ UNBALANCE: __________________
OPERATION CAPACITY
PUMP VOLTAGE
PUMP AMPACITY
INSTALLATION
SUCTION PRESSURE
DISCHARGE PRESSURE
SUPERHEATING
SUBCOOLING
COMPRESSOR
VOLT L2-L3
AMP L1
AMP L2
AMP L3
OPERATION HOURS
COMPRESSOR START CYCLES COUNTER
OIL LEVEL
VOLT L1-L2
VOLT L1-L3
FAN MOTOR
VOLT L2-L3
AMP L1
AMP L2
____________________ AMP L3
INSTALLATION
VOLT L1-L3
VOLT L2-L3
AMP L1
AMP L2
AMP L3
VOLTAGE UMBALANCE
AMPACITY UMBALANCE
____________________
TECHNICIAN FREQUENCY DRIVER SETTINGS: ___________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________________
RECOMMENDATIONS/COMMENTS: ______________________________________________________________________________________________
_____________________________________________________________________________________________________________________________________
The simple design of the refrigeration circuit totally eliminates potential problems during normal unit operation. No maintenance work is needed on
the refrigeration circuit as long as the unit is operating normally.
Ease of maintenance has been taken into consideration during the design stage such that the unit is easily accessible for servicing and maintenance.
By accessing from the front panel of the unit, servicing and maintenance operation can be done easily.
The electrical components are especially easy to access since it is located in the terminal box on top of the front panel.
Under normal circumstances, this chiller requires only a check and cleaning of air intake through the coil surface only. These can be done monthly or
quarterly depending on the surrounding enviroment where the units are installed.
When the surrounding enviroment is very oily or dusty, then the coils must be regularly cleaned by a qualified air conditioner service technician to
ensure sufficient cooling capacity and efficient unit operation. The normal life span might be shortened if no proper service is provided.
MAINTENANCE
For consistent performance and durability, always conduct proper and regular maintenance to the unit.
For prolonged periods of operation time, the heat exchanger will become dirty impairing its effectiveness and reducing the performance of the units.
Consult your local dealer about the cleaning of the heat exchanger.
No major maintenance or servicing needed for the internal water circuit in the unit except the water pump failure. It is advised that regular check on
the stainer to be conducted and change the water stainer if it is dirty or choked.
Always check the water level in the system, in order to protect the moving components in the hydraulic kit from over heating and excessive wear and
tear.
The manufacturer will not be responsible for the malfunction of any unit if the main cause is the
lack of maintenance or operating conditions which do not correspond to those recommended in
this manual.
99
NOTE
COMPRESSOR MAINTENANCE
The scroll type compressors are fully hermetic, and require no maintenance other than checking oil level.
ELECTRICAL TERMINALS
Electrical connections should be inspected and tightened as necessary. The heat and vibration can cause connections to loosen and fall off causing a
voltage or arcing.
• Disconnect the main power supply before repairing or replacing components or cables.
MAINTENANCE
• Tighten all cable connections connected to the terminal block and components.
• Inspect connectors, cables and/or components with burn marks, worn cables, etc. If you find any connector, connection or component with any of the
• The tension in the equipment should be checked with meter periodically to ensure adequate power supply.
CONDENSER
Maintenance consists primarily of routine removal of dirt and debris from the outer surface of the fins and repair or damage fins.
Clean fins with a vacuum cleaner, cold water, compressed air or a soft (non-metallic) brush. When it comes to units installed in a
corrosive atmosphere, cleaning the fins should be part of the regular maintenance program.
In this type of installation dust and debris must be removed quickly to avoid accumulation that will hamper normal operation.
MAINTENANCE
WARNING
Risk of electric shock, can cause injury and death.
Risk of serious injury. The fan can start up and cause injury. Disconnect
all electrical sources before inspecting the fan.
It is recommended to replace the filter drier whenever a repair is made in the cooling line.
EXPANSION VALVE
The expansion valve's function is to keep the evaporator supplied with the proper amount of refrigerant to satisfy the load conditions.
Before adjusting superheat, check that the unit charge is correct and liquid line is full with no bubbles and that the circuit is operating under stable
full load conditions.
The suction superheat for the suction leaving the evaporator is set at the factory to 10 degrees F.
MAINTENANCE
WARNING
Risk of explosive discharge of high pressure refrigerant. It can cause
personal injury or damage to equipment. Never loosen any connections
in the refrigerant lines or electrical lines until they are depressurized on
both sides of the compressor.
MAINTENANCE
Physical inspection of all contactors and Plan x x x x x x x x x x x x
relays on the electrical panel. (Monthly) Real
Check amperage of all electric motors
and compare according to equipment Plan x x x x
nameplate for detect abnormalities.
(Quarterly) Real
Plan x x x x x x x x x x x x
Physically verify false contacts. (Montly)
Real
Check the adjusting and state of the
electrical protections and fuses, these Plan x x x x x x
must be under the manufacturer's
specifications. (Bimonthly) Real
Plan x x x x x x x x x x x x
Electrical panel cleaning. (Montly)
Real
If there is any change of a component in the cooling circuit, is recommended that dehydrating filter be changed.
TROUBLESHOOTING
Defective contactor or coil. Replace.
Compressor will Determine type and cause of shutdown and correct it before restarting
not run System shutdowm by equipment protection devices.
equipment.
Liquid line solenoid will not open. Repair or replace solenoid. Check wiring.
Loose wiring. Check all wire junctions. Tighten all terminal screws.
Compressor running in reverse. Check unit and compressor for correct phasing.
Compressor
noisy or
vibrating Improper piping or support on sucction or discharge. Relocate, add, or remove hangers.
High discharge
pressure
Condenser fan control wiring not correct. Correct wiring.
Lack of refrigerant. Check for leaks, repair, add charge. Check liquid sight glass.
Fouled liquid line filter drier. Check pressure drop across filter drier. Replace.
Expansion valve malfunctioning. Repair or replace and adjust for proper superheat.
Low suction
Condensing temperature too low. Check means for regulating condenser temperature.
pressure
Compressors not staging properly. See corrective steps- Compressor staging intervals too low.
TROUBLESHOOTING
Excess or wrong oil used. Recover or change oil.
Operating beyond design conditions. Correct so conditions are within allowable limits.
Compressor Short cycling. Stabilize load or correct control settings for application.
thermal
protection
switch open Voltage range or imbalance. Check and correct.
Level too high with compressor operating. Confirm correct superheat, remove oil.
Compressor oil Insufficient water flow- Level too high. Correct flow, verify superheat.
level too high or
too low Excessive liquid in crankcase- Level too high. Check crankcase heater. Check liquid line solenoid valve operation.
Expansion valve operation or selection. Confirm superheat at minimum and maximum load conditions.
High condenser temperature. See corrective steps for High Discharge Pressure.
Equipment
No water flow in the system. Drain the system.
does not start.
Equipment Air suction and discharge clogged. Remove all possible obstacles.
starts but it is
not cooling
enough. Insufficient refrigerant in the system. Contact the manufacturer. Check the system for leaks.
TROUBLESHOOTING
Insufficient water flow in the system. Check the pumping system.
The water in the system is dirty or contaminated. Drain dirty or contaminated water and replace it with clean water.
• Warranty service can only be carried out by an Authorized Service Center, as long as the manufacturer products have been traded by the manufacturer
and it’s authorized Mexico distributors. The address of the nearest Authorized Service Center can be consulted calling the following telephone number:
01 800 890 59 17
• To enforce this guarantee the fault or device status must be notified at 01 800 890 59 17, keep the number of the reporting service that will be provided
when reporting the fault, besides the service report to validate that the equipment stopped operating due to a defect of the equipment components.
• During the term of this warranty, the manufacturer, through its Authorized Service Centers is committed to repair the equipment when the fault is
attributable to a manufacturing error. In which case the manufacturer will be responsible for the delivery of the spare(s) and cover the cost of labor
required.
• Spare parts and parts used to repair the appliance will have no cost to the customer, as long as the warranty period specified in this policy has not been
completed.
• This warranty does not cover damage or repairs required as a result of failures in the equipment installation.
WARRANTY
1. When the product had been used under conditions other than normal.
2. When the product has not been operated in accordance with the instructions for use included with the computer.
3. When the equipment has been altered, repaired or installed by unauthorized personal by the manufacturer.
In case of loss of this policy, the consumer can request a replacement to the place of purchase or to the manufacturer, with prior presentation of proof
of purchase (invoice).