01. Enabling when Boiler is working and main steam pressure >
30 kg/sq. CM
02. Arming when HP bypass BP1 or HP bypass BP2 open >2%
and LP bypass V/V open.
03. On Reheater protection tripping for boiler is as follows.
i) Turbine is in tripped condition and boiler is working if BP1 &
BP2 are not open boiler will trip after 15 seconds.
OR
LP bypass Command is > 35% and both LP bypass v/v not
open for >35 seconds boiler will be tripped.
Once the protection is armed the protection will desarm only
after boiler Tripping.
ARMING:
1. Boiler lighted up / no MFT
and
2. Boiler Pressure > 25 kg/cm2
and
3. Either BP1 or BP2 open 2% and LP bypass open > 2%
once only after that self Latching.
188
PROTECTION:
1. Protection arming
and
2. Turbine trip from CH-1 and CH-2
and
3. EitherLP bypass close or both HP bypass valves close
(<2% open) then boiler will trip after a time delay of
15 seconds.
204
B MAIN TURBINE PROTECTIONS
--------------------------------------------------------------------------------------
DESCRIPTION ALARM TRIP LOGIC
--------------------------------------------------------------------------------------
1.0 MECHANICAL
2.1 ELECTRICAL:
205
Fire Potection 1 channel 1
Fire Protection 1 channel 2
Can be operated from UCB, MOT room near LP bypass, near HP
Turbine. when this is operated :-
1. Turbine Trip
2. SGC - CF pump off
3. SLC CF heater off
4. SLC CF pump off
5. CF Heater 1 & 2 off
6. HP C&F pump 1 & 2 off
7. HP CF Cir pump 1 & 2 off
8. Vacu. Breaker open
1. Turbine trip
2. VACU Breaker Open
3. SGC Oil supply off
4. SLC AOP 1 & 2 off
5. SLC EOP on
6. SLC JOP 1 & 2 off
7. SLC JOP III off
8. SLC Turning gear off
9. AOP 1 & 2 off
10. JOP 1 & 2 off
206
11. JOP III on
4.0 CEP
CEP PERMISSIVES
1. Suction valve open 100 %
2. Discharge Valve Closed/Discharge header PR. > 28 kg/cm
Square
3. Recirculation valve open 100 %
4. Bearing temp < preset value
5. Discharge vent valve 100 % open
6. Hot well level Greater than Preset value
CEP TRIP:
1. Hot well level low low ( 2 out of 2 )
2. Suction valve close (o%)
3. Bearing temp high - high (100 deg celsius)
4. Discharge pressure low low ( 22 kg/ cm2 Falling and CEP
running) standby CEP comes in service at a discharge pres sure of
26 ksc CEP discharge header pressure low alarm comes at 27
KSC
191
3. Recirculation valve open 100%
4. Bearing temp. < preset value
5. CEP on auto
6. Other CEP trip
7. Any one CEP running and discharge header pressure < pre
set Value.
207
AOP : 1 comes into service
Turbine speed greater then 15 RPM & less than 2850
RPM AOP 2 off or any discrepancy
Discharge header pressure less than 4.5 KSC
AOP: 2 Comes into service:
AOP 1 off or discrepancy
speed > 15 RPM < 2850 RPM
Discharge header Pressure < 4.5 KSC
6.0 TD BFP
START PERMISSIVES :-
1. Lube Oil pressure normal > 3.5 KSC at O` MTR near oil tank.
2. TD BFP control valve closed.
3. Position controller output 0 %
4. Disconnecting coupling engaged.
5. Pump Delta T low < 25 D.C.
6. Deareater level normal
7. pump discharge valve closed ( 80% Open)
8. Recirulation valve open (100%)
9. Suction valve open (100%)
10. Warm-up valve closed (0%)
TRIPS:
1. Suction valve not open (90 %)
2. Exhaust valve not open (90%)
192
3. Main pump bearing temp. high-high > 120 Deg. CEL
4. Turbine bearing temp. high- high > 120 degcel.
5. Trip oil pressure low-low <5 kcs ( 2/3 logic)
6. Lube oil pressure low- low < 2.9 ksc. (2/3 logic )
7. Vacuum low-low <0.2 KSC
8. Axial shift of main pump high - high + or - 0.75 mm (2/2
logic)
9. Axial shift of turbine high+or - 0.7 mm ( 2/2 logic )
10. Overspeed trip at 5930 (elec) 5920 (mech.)
11. Seal water temp high -high > 85 dec.cel . for main pump DE/NDE.
side.
208
12. Deareator level low- low
13. Local trip ( mech.) -1.
14. Local trip (Elect) (2/2)
15. UCB trip manual ( Elect. ) (2/2)
7.0 MD BFP:
START PERMISSIVES:
1. Seal water header pr. normal > 15 ksc.
2. Deaerator level normal.
3. Pump bearing temp. normal < 90O C
4. Motor DE/NDE bearing temp. normal < 90O C
5. Hydraulic Coupling bearing temp. normal <90O C
6. Discharge valve closed or header pressure not low.
7. Lube oil pressure normal > 1.2 KSC.
8. Recirculation valve open 100 %
9. Pump suction valve open 100 %
10. Warm-up valve closed O%
11. Main pump delta T Normal < 250 C
12. Hydraulic coupling scoop in min. position.
193
5. Hydraulic Coupling bearing temp. Normal< 90 deg. cel.
6. Discharge Valve closed or header pressure not low.
7. Lube Oil pressure normal > 1.2 ksc.
8. Recirculation valve open 100%
9. Pump suction valve open 100%
10. BEP "C" on auto
209
11. BFP ' A ' Tripped or BFP ` B tripped or BEP ` A `Running and
suction flow> one pump capacity or BFP `B` running and
suction flow > one pump capacity.
MDBFP TRIPS:
Any one condition :
1. Axial Displacement very high> 7 mm
2. Bearing temp very high > 100 O C.
3. Deaerator level low-low .
4. Lube oil pressure very low< 0. 8KSC.
5. Suction valve not open.
6. Seal water temp. (suction side) very high > 85O C.
7. Seal water temp. ( disch. side) very high >85O C
8. Push botton stop.
9. UCB manual stop.
210