Section 2

Technical Particulars

Page 2.1
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
TABLE OF CONTENTS

Description Page

2.1 Design Condition 2.3

2.2 Equipment Overview 2.4

2.3 Performance Guarantee 2.8

2.4 Steam Turbine and Auxiliaries 2.13

2.5 Condenser 2.20

2.6 Generator and Auxiliaries 2.21

2.7 Control System 2.25

2.8 Required Utility Condition 2.26

Page 2.2
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2. Technical Particulars

2.1 Desing condition

Characteristic Specification

Duty Cycle Not specified

Elevation Grade elevation 3.15 m

STG location Indoor

Design ambient temperature (STG area)

Minimum ambient temperature 13.1 degC

Maximum ambient temperature 37.2 degC

Humidity

Minimum relative humidity Not specified

Maximum relative humidity 100%

Wind

Annual velocity 1.7m/s

Maximum velocity 20 m/s at southwest direction

Salt classification Not specified

Dust level Not specified

Snow level Not specified

Seismic condition

Vertical acceleration 0.20g (Toshiba assumed)

Horizontal acceleration 0.20g (Toshiba assumed)

Page 2.3
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.2 Equipment Overview

2.2.1 Steam Turbine

Feature Specification

Type Tandem Compound, Single Reheat

Four-Flow exhaust Condensing Turbine

Casing Number Three(3) cylinders

Control System Electrohydraulic control(EHC)

Exhaust System Downwards

2.2.2 Condenser

Feature Specification

Type Axial 1 passes

Casing Number Single casing

Cleanliness factor (%) 90

Tube Material Titanium

Hotwell Storage Capacity Approx. 2 min.

Page 2.4
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.2.3 LP Heaters

Feature Specification

Heaters LP Htr1 LP Htr2 LP Htr3 LP Htr4

Type Shell and Tube Type

Condensate Water 1,313,104 kg/hr


Flow at 100% Load

Extraction Flow at 41,469 kg/hr 44,353 kg/hr 90,854 kg/hr 56,525 kg/hr
100% Load

Design Press.(barg) ATM/100 ATM/100 1.53/128 4.59/156


/Temp.(degC)
- Shell Side

Design Press.(barg) 23.5/100 23.5/100 23.5/128 23.5/156


/Temp.(degC)
- Tube Side

Heat Transfer Area 790 m2 950 m2 1060 m2 700 m2

Material Shell : SA516 Gr70 Shell : SA516 Gr70

Water Box : SA516 Gr70 Water Box : SA516 Gr70

Tube : SA213 TP304 Tube : SA556 GrB2

2.2.4 Deaerator

Feature Specification

Type Single Shell, Spray and Tray Type

Condensate Water 1,313,104 kg/hr


Flow at 100% Load

Extraction Flow at 61,648 kg/hr


100% Load

Design Press.(barg) 9.6/229


/ Temp.(degC)

Page 2.5
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
Storage Capacity Approx. 3 min.

Material Tank: ASTM A516 Gr.70 or equiv.

Trays: ASTM A240 TP410 or equiv.

Spray Nozzle : Stainless TP 304 for Disk

2.2.5 HP Heaters

Feature Specification

Heaters HP Htr6 HP Htr7 HP Htr8

Type Shell and Tube Type

Feed Water Flow at 1,755,361 kg/hr


100% Load

Extraction Flow at 86,222 kg/hr 153,870 kg/hr 140,517 kg/hr


100% Load

Design Press.(barg) 26.91/227&509 59.85/276&372 87.18/300&420


/Temp.(degC)
- Shell Side

Design Press.(barg) 336.5/229 336.5/276 336.5/301


/Temp.(degC)
- Tube Side

Heat Transfer Area 1650 m2 1920 m2 1710 m2

Material Shell : SA516 Gr70

Water Box : SA516 Gr70

Tube : SA556 Gr.C2

Page 2.6
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.2.6 Generator

Feature Specification

Type Three phase, rotating field, cylindrical rotor,

horizontal type synchronous generator

Frequency 50Hz

Power Factor (pf) 0.85 Lagging

2.2.7 Packaging

Feature Specification

Enclosure Acoustic Mitigation Wall Type

2.2.8 Cooling System

Feature Specification

Cooling System Closed cycle cooling water ( by others )

2.2.9 Control System

* Digital Electro-Hydraulic Control (D-EHC) System for steam turbine control

* Distributed Control System (DCS) for main plant control

Page 2.7
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.3 Performance Guarantee and Acceptance Condition

2.3.1 Performance Guarantee

Performance Guarantees shall apply to the steam turbine generator and shall be
achieved during Performance Testing conducted in accordance with this clause.
Liquidated damages associated with failure to achieve these Guarantees are
addressed in commercial proposal.

The Equipment is guaranteed on a “new and clean” basis for any and all tests.
Toshiba will include degradation and correction factors to be applied to correct for
degradation caused by equipment operation during startup and commissioning and
environmental conditions in Performance Test Procedures.

Performance Tests shall be conducted in accordance with the Guarantee Conditions


set forth herein. The corrections that will be allowed are those required to correct
for Test Conditions that differ from the Guarantee Conditions defined herein and
an allowance for test uncertainty as defined by the Performance Test Procedures
and calculated in accordance with the ASME Performance Test Codes.

Table 2.3-1 Performance Guarantees

Parameter Performance Guarantee

Continuous Output(MW) of 100%TMCR at


600,000 kW (*1)
Generator terminals (Capacity guarantee)
Turbine Cycle Heat rate in kJ/kWh at 100%TMCR
under condition of 100% TMCR HBD (DWG.no 7,396 kJ/kWh
3GMG03867)
Continuous Output(MW) of 105% of TMCR at
630,000 kW (*1)
Generator terminals (Capacity guarantee)
Total Auxiliary power consumption(kW) of the
plant on the basis of measured output Generator
terminal minus sent out power measured down 350 kW
stream of Generator Transformer and station
transformer at 100% TMR

*1) *Regarding the Generator Electrical Output Guarantee, main steam flow shall be
available up to B-MCR flow with condensate measuring, not limited to the main steam
flow of guarantee heat balance.

Page 2.8
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.3.2 Gross Steam Turbine Generator Heat Rate

Turbine Gross Heat Rate at generator terminals guarantee is based on the


following conditions .If any conditions are changed, the guarantee data shall be
corrected.

Table 2.3-2 Turbine Gross Heat Rate Guarantee Condition (100%TMCR)

Measurement Value

Target output power at generator terminal (kW) 600,000

Main steam pressure at main stop valve inlet (bara) 250.0

Main steam temperature (deg C) 566

Reheat steam temperature (deg C) 566

Condenser back pressure (mmHg abs.) 57

Top HP heater feed water outlet temperature (deg C) 292.9

Reheat pressure drop between HP turbine exhaust nozzle connected to


8.0
CRV inlet including CRH NRV pressure drop (%)

BFP Motor Driven

Boiler feed pump and Booster pump efficiency (%) 80.0

Condensate pump efficiency (%) 80.0

BFP Discharge Pressure (bara) 312.5

TD (HP8 / HP7 / HP6 / LP4 - 1) (deg C) -2 /0 /-2 /3

DC (All Heaters) (deg C) 5

Steam pressure drop between turbine casing outlet nozzle connections


and feed water heater extraction steam connections 3/5/5/3
(HP8-6 / Dea / LP4-3 /LP2-1) (%)

Cycle loss (%) 0.0

Generator Power Factor 0.90 (*1)

(*1) Power Factor is specified by Vol.2-C, Clause 1.04.01 of EPC RFP

Page 2.9
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
On completion of Thermal Performance Tests of the Steam Turbine Generator, the gross
turbine heat rate shall be determined (taking into account the agreed correction curves)
using the following relationships, unless otherwise agreed (Toshiba may propose any
adjustments in its submitted Test Procedure):

GTHR = [MS x hMS – FW x hFFW + RH x (hHR – hCR)

+ AUX x (hAux – hAuxdrain) + MU x hMU ] / (kWOUT)

Where:

GTHR = Gross Turbine Heat Rate, kcal/kWh

MS = Main Steam flow, kg/h

RH = Reheat Steam flow, kg/h

FW = Feed Water flow, kg/h ( = MS + MU )

AUX = Auxiliary Steam flow, kg/h ( = Zero )

MU = Make Up flow, kg/h

hMS = Enthalpy of Main Steam, kcal/kg

hFFW = Enthalpy of Feedwater, kcal/kg

hHR = Enthalpy of Hot Reheat Steam, kcal/kg

hCR = Enthalpy of Cold Reheat Steam, kcal/kg

hAux = Enthalpy of Auxiliary Steam, kcal/kg

hAuxdrain = Enthalpy of Auxiliary Steam Drain, kcal/kg

hMU = Enthalpy of Cold Reheat Steam, kcal/kg

kWOUT = Generator terminal output after excitation losses, kW

Page 2.10
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
-The following also apply to the performance data;

Performance is measured at the generator terminal less the electrical power supply
to the generator excitation system.

The properties of water and steam for the thermal performance of the STG Plant
are in accordance with the Steam Table of IAPWS-IF97.

TOSHIBA will provide test correction curves in a detailed site specific performance
test procedure during the commissioning phase of the project.

Performance test shall be conducted based on ASME PTC6 method with condensate
flow measuring. Details will be mutually discussed later.

Performance test shall be conducted after F/M removal.

Above performance is based on new and clean condition of the steam turbine. If
more than 8 weeks have elapsed since initial roll before a performance test is to be
conducted, aging correction shall be applied.

According to the ASME PTC 6, measuring uncertainty is unavoidable. Therefore


the measured values shall be evaluated in consideration of those measuring
uncertainty. Consequently tolerance of the same amount of post-test measuring
uncertainty (expected to be +/- 1/3% or larger) shall be applied for test results.

Page 2.11
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.3.3 Steam Turbine Generator and Auxiliary Equipment Auxiliary Power Consumption

This auxiliary power consumption is based on during normal operation at Rated Output
load. The equipments are listed as attachment. Please refer to Section9.1 G-02 “Auxiliary
power consumption list”.

Page 2.12
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.4 Steam Turbine and Auxiliaries

2.4.1 Steam Turbine technical data

The following technical data is typical for the size and type of unit proposed and
except for that information specifically identified as being guaranteed, the data is
preliminary in nature and subject to change based on final equipment design and
component selection.

Measurement Value

Operating speed 3,000 rpm

Steam condition 250bara / 566 / 566 ℃

Vacuum condition 57 mmHg abs.

Type TC4F-33.5”

Tandem Compound, Single Reheat

Four(4)-Flow exhaust Condensing Turbine

Turbine configuration 3 casings (HIP, LPs)

Cylinder method of fastening Upper & Lowerhalf bolted at horizontal joint

Thrust bearing Between HIP and LP, Pad type

HIP turbine

- stages(HP/IP) 13stg / 8stg

- rotor material Cr-Mo-V

- blade material 12Cr

- journal bearing 2, DTP type

- Shaft seal Fin type

Page 2.13
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
Measurement Value

LP turbine

- stages 6 x 4flow

- rotor material 3.5NiCrMoV

- blade material 12Cr

- journal bearing 2, Elliptical type

- Shaft seal Fin type

- Last stage blade

(1) length 33.5” (0.8446m)

(2) exhaust area 6.69 m2

(3) root fixation design Finger type

(4) Method of blade damping Loose shroud cover & loose lug and cover

(5) Erosion protection Self shield

(6) blade material 12Cr

Off frequency Operation 47 Hz to 52 Hz for continuous

Page 2.14
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.4.2 Near-Field Noise (1m from any surface of STG enclosure at turbine operating floor)

Under normal operation of the STG at 100% load, expected noise level is 85 dBA.
Some equipment noise operating levels exceed the 85dBA sound limit. Please see
the following table for noise level information.

Expected noise level


Equipment
at 100% load operation

MSV/CV 95 dBA

CRV 95 dBA

Lube Oil Unit 95 dBA

EHC Oil Unit 95 dBA

Seal Oil Pump 90 dBA

Gland Steam Packing Unloading Valve 100 dBA

Notes:
Please note that noise levels can also be temporarily exceeded during transitional
states such as: start up, shutdown, turbine bypass operation, load reduction, etc.

Page 2.15
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.4.3 Heat Balance Diagrams

Please refer to attachment diagrams in Sec.9.

Document No. Name

3GMG03867 Rev.0 100% TMCR

3GMG03868 Rev.0 V.W.O (105% Output of TMCR)

3GMG03870 Rev.0 Boiler MCR

Page 2.16
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.4.4 Steam Turbine auxiliary technical data

The following technical data is typical for the size and type of unit proposed and
except for that information specifically identified as being guaranteed, the data is
preliminary in nature and subject to change based on final equipment design and
component selection.

Measurement Value

MSV/CV

- number 2

CRV

- number 2

Main oil tank

- number 1

- reservoir retention time Approx. 5 min.

Main oil pump

- number 1

- type centrifugal

- location Main oil tank

Main oil pump(back-up)

- number 1

- type centrifugal

- location Main oil tank

Emergency oil pump

- number 1

- type centrifugal

- location Main oil tank

Page 2.17
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
Measurement Value

Vapor extractor

- number 2 ( 100% x 2 )

- Type centrifugal

- location Main oil tank

Main oil Cooler

- number 2 ( 100% x 2 )

- Type Plate

Oil Conditioner

- number 1

- Type Coalescing filter type

Page 2.18
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
Measurement Value

Gland steam condenser

- number 1

- type Shell & Tube

Gland steam exhaustor

- number 2 ( 100% x 2 )

- Type centrifugal

- location near gland steam condenser

EHC oil Cooler

- number 2 ( 100% x 2 )

- type Shell & Tube

- location EHC oil unit

EHC oil pump

- number 2 ( 100% x 2 )

- type Piston

- location EHC oil unit

Page 2.19
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.5 Condenser

2.5.1 Condenser Technical Data

The following technical data is typical for the size and type of unit proposed and
except for that information specifically identified as being guaranteed, the data is
preliminary in nature and subject to change based on final equipment design and
component selection.

Measurement Value

Condenser Type Single Shell, one Pass, Axial direction Tube

Condenser Vacuum 703 mmHg

Cleanliness Factor 90 %

Cooling Water Flow 87,600 m3/hr (per unit)

Inlet / Outlet Water Temp. 30 / 37 ℃

Heat Transfer Area 28,236 m2 (per unit)

No. of Tubes 21,680 (per unit)

Tube Length 16.323 m

Tube Material Titanium

Page 2.20
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.6 Generator and Auxiliaries

2.6.1 Applied Standards

Unless other standards are specifically mentioned in this proposal, all materials
used and provided under the Contract, all design calculations and tests shall be in
accordance with the following standards.

(a) Materials;

Appropriate corresponding to JIS or code/standard of country of origin

(b) Performance and tests;

- Generator ・・・・・ IEC60034-1(2010)

- Excitation system ・・・・・ IEEE 421.2 (1990)

- AC and DC motor ・・・・・ IEC60034-1(2010)

(c) Components and standard Relevant Japanese standard

production parts of equipment, and/or manufacturer standards.

including control devices, terminals,

wiring, relays, instruments,

and Excitation control panels and local

panels/racks

Page 2.21
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.6.2 Technical Data of Generator

Type form Three phase, rotating field, cylindrical rotor,


horizontal type synchronous generator

Installation Indoor

No. of phase 3

No. of poles 2 poles

Output 750,000 kVA continuous

(at rated hydrogen pressure of 520kPag)

Voltage 23.5 kV (+/- 5%)

Frequency 50 Hz (+/- 2%)

Speed (R.P.M.) 3,000 R.P.M

Power factor 0.85 lagging – 0.95 leading

Short circuit ratio Not less than 0.50 (at rated kVA base)

Cooling method

- Stator winding Direct water cooled

- Rotor winding Direct hydrogen cooled

Connection of stator winding Wye. Both ends of each phase winding are
brought out from the generator stator through
high voltage bushings. Six(6) bushings are
provided for a generator.

Anti freeze liquid Not applicable

Insulation class

- Stator winding Class F (B rise)

- Rotor winding Class F (B rise)

Direction of rotation Counter-clockwise (CCW), viewed from the


turbine top

Connection of turbine Directly coupled to turbine

Page 2.22
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
Generator electrical performance curves : Please refer to Sec. 9.

Excitation system Static excitation system.

- Response ratio 2.0

- Ceiling voltage 150% of rated field voltage

- PSS input Power input

2.6.3 Hydrogen Control and Seal Oil System

(a) Hydrogen control system

Please refer to the attached P&ID in Sec.9.

(b) Seal oil system

Please refer to the attached P&ID in Sec.9.

2.6.4 Stator Cooling Water System

Stator cooling water system

Please refer to the attached P&ID in Sec.9.

Page 2.23
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.6.5 Turbine and Generator Auxiliary Motors (AC motors)

Power Three phase 50Hz

Service factor 1.0

Insulation class class F

Temperature rise class B

Rated voltage 400V

2.6.6 Turbine and Generator Auxiliary Motors (DC motors)

Service factor 1.0

Insulation class class F

Temperature rise class F

Rated voltage 220V (DC)

Page 2.24
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.7 Control System

2.7.1 Applied Standards

Components and standard production parts of equipment, including control


devices, terminals, wiring, relays, instruments, control panels and tests shall be
in accordance with the Relevant Japanese standard and/or manufacturer
standards.

2.7.2 Technical Specification

Please refer to Section 4.5 in this proposal for detailed technical specification.

Page 2.25
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.8 Required Utility Condition

The following data is typical for the volume and specification of unit proposed, the
data is preliminary in nature and subject to change based on final equipment
design and component selection.

2.8.1 Circulating water conditions

Measurement Value

Type of water Circulating water

Volume 87,600 m3/h

Supply pressure (Design) 4.0 bar.g

Condition No antifreeze agent

2.8.2 Cooling water conditions - Auxiliary cooling system

Measurement Value

Type of water Closed cycle cooling water

Antifreeze agent No

Operating Design temperature 38 deg C

Design pressure 11 bar.g

2.8.3 Auxiliary steam conditions

Measurement Value

Design temperature 260 deg.C

Design pressure 10 to 15 bar g

Page 2.26
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.8.4 Instrument air conditions

Measurement Value

Volume 0.64 Nm3/min

Supply pressure ( minimum ) 5.5 bar.a

Condition Dried, oilfree, filtered

2.8.5 Auxiliary power source

Measurement Value

(AC)

- Power (Three phase) 400V

- Power (Single phase, Miscellaneous) 230V

- Control (Single phase, UPS) 230V

(DC)

- Power 220V

- Control 220V, 110V,48V DC

Page 2.27
TOSHIBA CORPORATION
SPC-GPH-VLP1-0001 Rev.0
Proprietary Information
© Toshiba Corporation 2011, All Rights Reserved
2.8.6 Steam purity requirements

Following is the recommended steam purity for our turbine.

Normal operation
SiO2 < 20 ppb
Sodium < 3 ppb
Chlorine < 5 ppb
Cation Conductivity < 0.2 μS/cm
Excursions
100hr/incident and 500hr/year
Sodium < 6 ppb
Chlorine < 5 ppb
Cation Conductivity < 0.5 μS/cm
24hr/incident and 100hr/year
Sodium < 10 ppb
Chlorine < 50 ppb
Cation Conductivity < 1.0 μS/cm