Conduit Wiring Details
Conduit Wiring Details
Nominal cross 20 mm 25 mm 32 mm 38 mm 51 mm 64 mm
sectional area
of conductor in S B S B S B S B S B S B
sq.mm
1 2 3 4 5 6 7 8 9 10 11 12 13
1.50 5 4 10 8 18 12 – – – – – –
2.50 5 3 8 6 12 10 – – – – – –
4 3 2 6 5 10 8 – – – – – –
6 2 – 5 4 8 7 – – – – – –
10 2 – 4 3 6 5 8 6 – – – –
16 – – 2 2 3 3 6 5 10 7 12 8
25 – – – – 3 2 5 3 8 6 9 7
35 – – – – – – 3 2 6 5 8 6
50 – – – – – – – – 5 3 6 5
70 – – – – – – – – 4 3 5 4
Note:
(1) The above table shows the maximum capacity of conduits for a simultaneous
drawing in of cables.
(2) The columns headed ‘S’ apply to runs of conduits which have distance not exceeding
4.25 m between draw in boxes and which do not de ect from the straight by an
angle of more than 15 degrees. The columns headed ‘B’ apply to runs of conduit,
which de ect from the straight by an angle of more than 15 degrees.
(3) Conduit sizes are the nominal external diameters.
47