Termal Inspection Powder Line 2022 - 2
Termal Inspection Powder Line 2022 - 2
Q2 - 2022
POWDER LINE
Photo 1
Before After
Severity Severity
Spot Temp. Value Difference Spot Temp. Value Difference
Rating : Rating :
Fault 33.5 3.5 Point 1 28.9 0.4
2 3
Reference 30.0 Reference 29.3
R= 28 A, S= 20 A, T= 15 A
Recommended Repair :
Balance load if possible. Test MCB. Replace MCB if needed. Clean, tighten and recrimp
all connections associated with this unit.
Repair notes
Corrective Action Taken Date of Repaired Signature
Clean, tighten and recrimp all connections
associated
10/01/2023 Jufry
R= 14 A, S= 4.3 A, T= 4.0 A
Equipment Location : Item of Concern :
Lab Area Lighting Panel
Photo 2
Before After
Severity Severity
Spot Temp. Value Difference Spot Temp. Value Difference
Rating : Rating :
Fault 37.1 3.9 Point 1 29.5 1.1
2 3
Reference 33.2 Reference 28.4
R= 65 A, S= 45 A, T= 87 A
Recommended Repair :
Balance load if possible. Test MCB. Replace MCB if needed. Clean, tighten and recrimp
all connections associated with this unit.
Repair notes
Corrective Action Taken Date of Repaired Signature
Clean, tighten and recrimp all connections
10/01/2023 Jufry
Equipment Location : Item of Concern :
Switchroom Bean Cleaning Micronizing PCC panel
Photo 3
Before After
Severity Severity
Spot Temp. Value Difference Spot Temp. Value Difference
Rating : Rating :
Fault 59.7 23 Point 1 24.7 0.4
1 3
Reference 36.7 Reference 24.3
Recommended Repair :
Balance load if possible. Test MCB. Replace MCB if needed. Clean, tighten and recrimp
all connections associated with this unit.
Repair notes
Corrective Action Taken Date of Repaired Signature