Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 3

Thermographi Inspection

Q2 – 2022

LIQUOR LINE

Problem Found with Severity rating 1 = 0


Problem Found with Severity rating 2 = 1
Problem Found with Severity rating 3 = 0

TOTAL NUMBER OF PROBLEM FOUND = 1


Equipment Location : Item of Concern :
Winnower Aspiration Fan

Photo 1

Before After

IR. Information IR. Information


Date of Creation 10/08/2022 Date of Rescanned 22/02/2023
File Name IR_590 File Name IR_692

Severity Severity
Spot Temp. Value Difference Spot Temp. Value Difference
Rating : Rating :
Fault 48.8 7.4 Point 1 39.0 2.3
2 3
Reference 41.4 Reference 41.3

Description Probable Cause


Phase S Protection Terminal connection loose

R= 18 A, S= 17 A, T= 16 A

Recommended Repair :
Tighten or recrimp connection terminal

Repair notes
Corrective Action Taken Date of Repaired Signature
Tighten or recrimp connection terminal

10/01/2023 Jufry

R=20 A, S= 19 A, T= 16 A