2 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0 Issued: 2012-05-04
Revision: B
Motor protection A
ABB 3
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Functionality Conf. A
Protection1)
Control
Circuit-breaker control ●
Emergency startup ●
Supervision
Measurement
Disturbance recorder ●
4 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
3
3I 2
IS t, n<
I2>> 46R Ist> 51LR
49, 66, 48, 51LR
1
Io
3I>BF 51BF I2>M 46M 3I< 37
ABB 5
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
1)
1
Io 51N lo> 51N
lo>BF lo>>> 50N
BF (SEF)
3I> 51P-1 3I>>> 50 3θ>M 49M 3I> 51P-1 3I>>> 50 3θ>M 49M
3 3I 2 3 3I 2
IS t, n< IS t, n<
I2>> 46R Ist> 51LR I2>> 46R Ist> 51LR
49, 66, 48, 51LR 49, 66, 48, 51LR
1 Io
3I>BF 51BF I2>M 46M 3I>BF 51BF I2>M 46M 3I< 37
Lockout Lockout 86
relay 86 ESTART ESTART 3I< 37 relay ESTART ESTART
Figure 2. Motor protection and control of contactor and circuit-breaker controlled motors using REM611 with the
standard configuration A. The motor start-up signal is also used to dynamically increase the setting
level of the lowest O/C protection stage of the REF611 on the incoming feeder.
6 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
5. Supported ABB solutions line diagram feature that is especially useful for
ABB’s 611 series protection and control IEDs the 611 series IEDs because of the limited size of
together with the COM600 Station Automation the LHMI. Further, the WHMI of COM600 offers
device constitute a genuine IEC 61850 solution an overview of the whole substation, including
for reliable power distribution in utility and IED-specific single-line diagrams, thus enabling
industrial power systems. To facilitate and convenient information accessibility.
streamline the system engineering, ABB’s IEDs
are supplied with Connectivity Packages To enhance personnel safety, the WHMI also
containing a compilation of software, IED-specific enables remote access to substation devices and
information and a full IED data model including processes. Furthermore, COM600 can be used
event and parameter lists. By utilizing the as a local data warehouse for technical
Connectivity Packages, the IEDs can be readily documentation of the substation and for network
configured via the PCM600 Protection and data collected by the IEDs. The collected network
Control IED Manager and integrated with the data facilitates extensive reporting and analyzing
COM600 Station Automation device or the of network fault situations using the data and
MicroSCADA Pro network control and event handling features of COM600.
management system.
The data historian can be used for accurate
The 611 series IEDs offer native support for the process performance monitoring by following
IEC 61850 standard, including limited binary process and equipment performance calculations
GOOSE messaging. Compared with traditional with real-time and history values. Better
hard-wired inter-device signaling, peer-to-peer understanding of the process behaviour by joining
communication over a switched EthernetLAN time-based process measurements with
offers an advanced and versatile platform for production and maintenance events helps the
power system protection. The 611 series IED’s user to understand the process dynamics.
implementation of the IEC 61850 substation
COM600 also features gateway functionality
automation standard enables access to some
providing seamless connectivity between the
distinctive features that include fast software-
substation IEDs and network-level control and
based communication, continuous supervision of
management systems such as MicroSCADA Pro
the integrity of the protection and communication
and System 800xA.
system, and inherent flexibility for reconfiguration
and upgrades.
Product Version
ABB 7
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
COM600
Web HMI
COM600
Ethernet switch
REB611
REF611 REF611 REM611
High-impedance 1 operate
Overcurrent Overcurrent Short circuit
High-impedance 2 operate
Earth-fault Earth-fault Combined protection
High-impedance 3 operate
Phase unbalance Phase unbalance Thermal overload
Motor restart inhibit High-impedance start
Thermal overload Thermal overload
AR sequence in progress AR sequence in progress Emergency start enabled Segregated supervision
Trip circuit failure Trip circuit failure Supervision alarm Trip circuit failure
Figure 3. Power system example using 611 series IEDs, COM600 and MicroSCADA pro or System 800xA
8 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
ABB 9
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
remotely to the front panel user interface, the binary input threshold (18…176 V DC) can be
Web browser-based user interface and PCM600. selected by adjusting the IED’s parameter
settings.
14. Inputs and outputs All binary input and output contacts are pre-
The IED is equipped with three phase-current configured according to the standard
inputs and one residual-current input. The phase- configuration, but can be easily reconfigured by
current inputs and the residual-current input are setting application-based parameters using the
rated 1/5 A, that is, the inputs allow connection of signal configuration functionality of the LHMI and
either 1 A or 5 A secondary current transformers. the WHMI.
The optional residual-current input 0.2/1 A is
normally used in applications requiring sensitive See the Input/output overview table and the
earth-fault protection and featuring core-balance terminal diagrams for more information about the
current transformers. IED's inputs and outputs.
CT VT BI BO
A 4 - 4 6
10 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
All communication connectors, except for the connections are supported. Termination and pull-
front port connector, are placed on integrated up/down resistors can be configured with jumpers
optional communication modules. The IED can be on the communication card. External resistors are
connected to Ethernet-based communication not needed.
systems via the RJ-45 connector (100Base-TX) or
the fibre-optic LC connector (100Base-FX). If The IED supports the following time
connection to a serial bus is required, the 10-pin synchronization methods with a time-stamping
RS-485 screw terminal can be used. resolution of 1 ms:
When the IED uses the RS-485 bus for the serial In addition, the IED supports time synchronization
communication, both two- and four-wire via the Modbus protocol.
Client A
Client B
Network
Network
IEC 61850 ● ● -
MODBUS RTU/ASCII - - ●
MODBUS TCP/IP ● ● -
● = Supported
ABB 11
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Table 6. Dimensions
Description Value
Case 164 mm
Case 160 mm
Burden of auxiliary voltage supply DC < 12.0 W (nominal)/< 18.0 W (max.) DC < 12.0 W (nominal)/< 18.0 W (max.)
under quiescent (Pq)/ operating AC < 16.0 W (nominal)/< 21.0 W (max.)
condition
Ripple in the DC auxiliary voltage Maximum 15% of the DC value (at frequency of 100 Hz)
Description Value
• Continuously 4A 20 A
12 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Description Value
Reaction time 3 ms
Description Value
Description Value
ABB 13
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Description Value
Description Value
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)
14 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Description Value
Modulation Unmodulated
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC
2) For IEDs with an LC communication interface the maximum operating temperature is +70ºC
ABB 15
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
• Common mode 2 kV
• Contact discharge 8 kV
• Air discharge 15 kV
• All ports 4 kV
16 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
150 V rms
• Conducted
• Radiated
ABB 17
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Description Reference
LV directive 2006/95/EC
Description Reference
Description
18 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
ABB 19
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
20 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Characteristic Value
EFIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value 11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)
ABB 21
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
EFHPTOC 40...200000 ms 10
EFIPTOC 20...200000 ms 10
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10 to 5.00
22 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Table 31. Negative phase-sequence overcurrent protection for motors (MNSPTOC) main settings
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
ABB 23
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Characteristic Value
1) Current before = 0.0 x I n , f n = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
24 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence current before = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 25
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Characteristic Value
Table 41. Thermal overload protection for motors (MPTTR) main settings
Characteristic Value
26 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Control functions
Measurement functions
Characteristic Value
±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)
ABB 27
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Characteristic Value
±0.5% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Supervision functions
Description Value
28 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
The LHMI includes a push button (L/R) for local/ For routine testing purposes, the IED cases can
remote operation of the IED. When the IED is in be equipped with test switches, type RTXP 18,
the local mode, the IED can be operated only by which can be mounted side by side with the IED
using the local front panel user interface. When cases.
the IED is in the remote mode, the IED can
execute commands sent from a remote location. Mounting methods:
The IED supports the remote selection of the local/
• Flush mounting
remote mode via a binary input. This feature
• Semi-flush mounting
facilitates, for example, the use of an external
• Semi-flush mounting in a 25° tilt
switch at the substation to ensure that all IEDs
• Rack mounting
are in the local mode during maintenance work
• Wall mounting
and that the circuit breakers cannot be operated
• Mounting to a 19" equipment frame
remotely from the network control center.
• Mounting with a RTXP 18 test switch to a
19" rack
• Height: 161.5 ±1 mm
• Width: 165.5 ±1 mm
GUID-8DC31119-E1C4-42DA-848B-968FBF8F8F53 V1 EN
ABB 29
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
190
186
164
177
25°
160
160
177
177
230
103 98 107
48
1 53 133
Figure 6. Flush mounting Figure 7. Semi-flush mounting Figure 8. Semi-flush with a 25º tilt
30 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
20. Selection and ordering data number consists of a string of codes generated
The IED type and serial number label identifies the from the IED's hardware and software modules.
protection IED. The label is placed above the
LHMI on the upper part of the plug-in unit. An Use the ordering key information to generate the
order number label is placed on the side of the order number when ordering complete IEDs.
plug-in unit as well as inside the case. The order
REM611HBAAAA1NN1XE
# Description
1-2 Product
Relay RE
3 Main application
Motor protection and control M
4-6 IED series
611 series IED 611
7 IED casing and test switches
Complete relay H
REM611HBAAAA1NN1XE
# Description
9 Standard configuration
Motor protection A
10 AIM I0
1A / 5A A
0.2A / 1A B
11 Communication module
Ethernet 100Base FX (LC) A
Ethernet 100Base TX (RJ45) B
RS485 (including IRIG-B) C
Ethernet 100Base TX (3*RJ45) D
None N
12 Communication protocols
IEC61850 A
Modbus B
13 Language
English 1
English and Chinese 2
GUID-9787276D-05CF-4538-97EC-6271C4CAF69E V2 EN
ABB 31
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
REM611HBAAAA1NN1XE
# Description
14 Option 1
None N
15 Option 2
None N
16 Power supply
48-250Vdc; 100-240Vac 1
24-60Vdc 2
17 For future use
Undefined X
18 Version
Product version 1.0 E
GUID-73E4C093-EA58-456B-9708-962D9AFC1C4B V2 EN
GUID-CED8B9E7-26EF-429A-BACD-995B41278BD9 V2 EN
19” rack mounting kit with cut-out for one IED 1MRS050694
19” rack mounting kit with cut-out for two IEDs 1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001
Mounting bracket for one IED in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001
19” rack mounting kit for one IED and one RTXP18 test switch (the test switch is not 2RCA021952A0003
included in the delivery)
19” rack mounting kit for one IED and one RTXP24 test switch (the test switch is not 2RCA022561A0003
included in the delivery)
32 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
ABB 33
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Signal monitoring ● ● ● ●
Disturbance recorder
● ● ● ●
handling
Modbus® communication
configuration
- ● ● ●
(communication
management)
Event viewing ● - - -
● = Supported
34 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
REM611
X120 X100
1 + 1
BI 1 Uaux
2 2
-
3 3
BI 2
IRF
4
4 5
BI 3
PO1
5
BI 4
6 6
7 1/5A 1) 7
IL1
8 N PO2
9 1/5A
IL2 8
10 N 9
11 1/5A 10
IL3 SO1
12 N
13 1/5A 11
Io 12
14 N 13
SO2
14
16
PO3
17
15
19
TCS1 18
20
22
PO4
21
23
TCS2 24
ABB 35
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
Protection
Switch groups
Configurable timers
Control
Supervision
Measurement
36 ABB
Motor Protection and Control 1MRS757469 B
REM611
Product version: 1.0
1) 10 instances
2) 20 instances
3) 6 instances
ABB 37
38