Installing the HDD Page 1 of 5

Open MSS 15, Product Documentation, version 6 (HTML) > Troubleshoot > Maintaining and Troubleshooting
Hardware > Replacing hardware units > Replacing the HDD on CPRT5-A for VMU

Installing the HDD


Procedure

1
Install the HDD by mounting screws that hold the disk module to the carrier.

2
Align the HDD carrier to the guiding rails of the slot.

3
Insert the HDD carrier to the slot until it is firmly in place.

4
Tighten the two retaining screws of the HDD carrier.

Figure: Tighten two screws of the HDD0 carrier

5
Install the RTM with HDD.

http://localhost:9090/informationbrowser/topic/m172200157_html/htm/docs/troubleshooti... 6/13/2017
Installing the HDD Page 2 of 5

For the instructions on installing the RTM, see Install a rear transition module. in section Replacing a rear transition module.

Note: After a while, if the HDD0 is ready, the HDD0 ACT LED turns green.

6
Change the state of VMU to TE-EX.

Step example

ZUSC:VMU,12:SE;
ZUSC:VMU,12:TE;

Note: Upon command execution, the VMU unit restarts along with all its child units. After the restart, the state of the VMU
unit is changed to TE-EX.

7
Change the state of VMU to WO-EX.

Step example

ZUSC:VMU,12:WO;

Note: Upon command execution, the VMU unit restarts along with all its child units. After the restart, the state of the VMU
unit is changed to WO-EX. The child units of the VMU unit resume their initial state ( for example SP-EX or WO-EX).

8
Check the state of the HDD.

Step example

ZISI:,CHU,1:WDU,0:;

9
If the hard disk is a new one, initialize it.

The HDD must be in the WO-ID state so that it can be initialized.

Sub-steps

a)
Change the state to WO-ID.

Step example

ZISC:,CHU,1:WDU,0:WO-ID;

b)
Initialize the disk.

ZIWI:,CHU:WB,<format>,<volume label>,<number of files>,<version limit>,<initials>;

http://localhost:9090/informationbrowser/topic/m172200157_html/htm/docs/troubleshooti... 6/13/2017
Installing the HDD Page 3 of 5

Step example

ZIWI:,CHU,1:WB,F5,MSS_CHU1W0,FFF0,2,XY;

10
Check the version of the unit's IPMI software.

Check whether the soft versions are consistent. If they are consistent, no upgrade is required. If they are inconsistent, an upgrade is
needed.

Step example

WDD:UT=VMU,UI=12;

LOADING PROGRAM VERSION 13.71-0

EXECUTION STARTED

1 VALID PLUG-IN UNITS FOUND

EXECUTION STARTED AT 2016-12-12 09:16:54


100% DONE, PLEASE WAIT 0 H, 0 MIN AND 0 SEC

FUNCTIONAL PLUG-IN UNIT VERSION


UNIT TYPE INDEX CURRENT -> AFTER UPDATE
----------- ------------- --------------------------------
VMU-12 CPRT5_A-0 cprt5-a_em_mmcf_02.01.0017 ->
cprt5-a_em_mmcf_02.01.0017 RABESW_1450

COMMAND EXECUTED

Step result

As displayed in the example, an upgrade is not needed because the current SW version is consistent with the disk version.

11
Update the IPMI software, if needed.

Note: Update must be performed by an experienced person who has sufficient knowledge of the system. For instructions,
see command reference.

Sub-steps

a)
Check the slot of CHU. Get the master and the module number of the related VMU.

Step example

ZWTI:P:CHU;

b)
Check all child units in the VMU.

Step example

ZUSI:VMU,index;

http://localhost:9090/informationbrowser/topic/m172200157_html/htm/docs/troubleshooti... 6/13/2017
Installing the HDD Page 4 of 5

c)
Change all related child units to TE-EX.

Step example

ZUSC:child unit,child unit index:SP;


ZUSC:child unit,child unit index:TE;
ZUSC:VMU,index,BL;
ZUSC:VMU,index,TE;
ZWDF:UT=VMU,UI=index,PT=CPRT5_A,PI=0;
ZUSC:VMU,index,WO-EX;

12
Change the state of the HDD to TE-ID.

Step example

ZISC:,CHU,1:WDU,0:TE-ID;

13
Run the diagnostic on the unit.

Step example

ZUDD:CHU,1,1:WDU,0;

14
Check the diagnostic report.

Step example

ZUDH:CHU,1,1:;

15
Change the working state of the HDD back to WO-ID.

Step example

ZISC:,CHU,1:WDU,0:WO-ID;

16
Copy source WDU to backup WDU of CHU unit.

Step example

ZIWY:S:UNIT=CHU-1,PATH=/,DRIVE=WDU-S;
ZIWY:D:UNIT=CHU-1,PATH=/,DRIVE=WDU-B;
ZIBC:,,,,,,,,,DIR:;

http://localhost:9090/informationbrowser/topic/m172200157_html/htm/docs/troubleshooti... 6/13/2017
Installing the HDD Page 5 of 5

17 Change the HDD state from WO-ID to WO-BU.

Step example

ZISC:,CHU,1:WDU,0:WO-BU;

18
Check that there are no active alarms.

Step example

ZAHO:CHU,1;
ZAHO:WDU,0;

Related resources

Parent topic: Replacing the HDD on CPRT5-A for VMU

Id: DN0966621 © 2017 Nokia. All rights reserved.

http://localhost:9090/informationbrowser/topic/m172200157_html/htm/docs/troubleshooti... 6/13/2017