NOTES:

1. Foundation might change to suit the subsoil


condition of the area as directed by the Engineer
2. Reinforced concrete shall be grade C25
3. Plain concrete shall be grade C15
1315 3000 4. Reinforcement from each lot shall be tested and
the results submitted to the Engineer before use
1
D 105 50T2

150
E F and minimum strength must be 460N/mm²
1-2
0-1
1 2 5T 1 5. Unless otherwise specified the minimum cover
300 to reinforcement shall be as follows:-
230 slabs and beams 25mm
230

150
1316 1487 columns 30mm
1650

foundation in dry soil 50mm

1800
0
116 13 foundation in water logged soil 75mm
230

190
8 8 50T B2
1-2 250
0- 1 11- 11 6. Reinforcement steel of varying lengths and
5T 1 10-
6T10-05-250B2

14T 12T10-09-100B1
5T10-06-250T2

08 curved shapes are to be bent to suit structural


8T10-08-150T1 06 shape
7.The mortar for Construction should be of
1600

09
450

designation (iii)
6T10-05-250B2 12
8T10-07-150T1 8T10-08-150T1 12 8.The minimum Compressive strength of the
230 construction blocks should be 5N/mm² for load
bearing wall and 2.5N/mm² for non load
8T10-03-150T1 bearing wall.
SECTION 2-2
230

7
16T0-02-250B2

8T10-12-150T1
12T10-09-100B1
4430

1315 2585
8T10-01-150B1 REVISION NO: DESCRIPTION REVISED BY: DATE
17T10-11-250B2

2830 07
5T10-06-250T2 5T1 1077
0-0
01 2- 250
7T10-04-200T1 T2

450
05 03 300

175 150
174 230

1350
1500
8T10-13-150T1
02 1 5T1 981
03 3T10 - 0
0- 0 2-25 PROJECT :
230

5 5 2-2 0T2 230X300 mm


50
8T10-01-150B1 B2 PLINTH BEAM PROPOSED RESIDENTIAL BUILDING TO BE
2804 4T16, T8-250 BUILT AT KINYEREZI-TABATA
04 100mm Concrete DAR ES SALAAM
1 2 200mm well compacted
A A SECTION 1-1 hard core
>300mm selected soil fill
DRAWING TITLE :
Natural G.L
STAIRCASE PLAN: REINFORCEMENT DETAILS STAIRCASE REINFORCEMENT
DETAILS
CLIENT:
MR. DIDAS D. MROSSO
P.O BOX
DAR ES SALAAM
CONCEPTUAL DESIGN: J.DAMIAN CHECKED BY:
ANALYSIS & DETAILING: J.DAMIAN DRAWN BY: J.DAMIAN
DATE: SCALE:
DRAWN NO: 10
SEPT, 2017 1:35