Dự án:

Hạng mục: Hệ thống thông gió & Điều hòa không khí
Tiêu đề: Bảng tính toán cột áp
Thực hiện:
Kiểm tra:
Ngày:

Aim To calculate Static pressure for Fan Sizing

Conclusion Provide outside air as indicated in table below

Inputs AS1668.2
Drawing

Analysis

DUCT AIR SIZE EQUIV. AREA AREA VELOC. "Co" DUCT FITTING
SECTION QUANTITY Width Height RESIST. VELOC. DIA. (RECT.) (ROUND) LENGTH ks PRESS. FACTOR RESIST. RESIST.
NO. L/s mm mm Pa/m m/s mm m2 m2 m mm Pa Pa Pa

1 Supply Grille + Juntion 183 450 300 0.07 1.36 403 0.14 0.13 0.15 1.10 0.0 25.0
2 Straight Duct 366 300 300 0.67 4.07 330 0.09 0.09 5.40 0.15 9.92 3.6 0.0
3 Transtion 783 450 300 1.04 5.80 403 0.14 0.13 0.15 20.18 0.05 0.0 1.0
5 Straight Duct 783 450 300 1.04 5.80 403 0.14 0.13 5.60 0.15 20.18 5.8 0.0
6 Transtion 1,090 650 300 0.82 5.59 479 0.20 0.18 0.15 18.75 0.03 0.0 0.6
8 Straight Duct 1,090 650 300 0.82 5.59 479 0.20 0.18 5.70 0.15 18.75 4.7 0.0
9 Transtion 1,464 800 300 0.89 6.10 527 0.24 0.22 0.15 22.33 0.03 0.0 0.7
11 Straight Duct 1,464 800 300 0.89 6.10 527 0.24 0.22 3.50 0.15 22.33 3.1 0.0
12 Transtion 1,647 900 300 0.85 6.10 556 0.27 0.24 0.15 22.33 0.03 0.0 0.7
13 Elbow 1,647 900 300 0.85 6.10 556 0.27 0.24 0.15 22.33 1.00 0.0 22.3
14 Straight Duct 1,647 900 300 0.85 6.10 556 0.27 0.24 2.00 0.15 22.33 1.7 0.0
13 Elbow 1,647 900 300 0.85 6.10 556 0.27 0.24 0.15 22.33 1.48 0.0 33.0
16 VCD 1,647 900 300 0.98 6.10 556 0.27 0.24 0.43 22.33 0.0 8.0
17 Wye 3,650 1250 400 0.83 7.30 755 0.50 0.45 0.15 31.97 0.6100 0.0 19.5
18 Straight Duct 3,650 1150 300 2.23 10.58 620 0.35 0.30 2.00 0.15 67.16 4.5 0.0
19 Transtion 3,650 1150 300 2.23 10.58 620 0.35 0.30 0.15 67.16 0.03 0.0 2.0
19 Transtion 3,650 1150 300 2.23 10.58 620 0.35 0.30 0.15 67.16 0.03 0.0 2.0
13 Elbow 3,650 1250 400 0.83 7.30 755 0.50 0.45 0.15 31.97 1.49 0.0 47.6
27 External Louver 3,650 7450 500 0.01 0.98 1839 3.73 2.66 0.15 0.58 0.0 40.0
23 202
SAFETY MARGIN 10% 26 223
TOTAL EXTERNAL STATIC PRESSURE 248
Dự án:
Hạng mục: Hệ thống thông gió & Điều hòa không khí
Tiêu đề: Bảng tính toán cột áp
Thực hiện:
Kiểm tra:
Ngày:

Aim To calculate Static pressure for Fan Sizing

Conclusion Provide outside air as indicated in table below

Inputs AS1668.2
Drawing

Analysis

DUCT AIR SIZE VELOC. "Co" DUCT FITTING


SECTION QUANTITY Width Height LENGTH PRESS. FACTOR RESIST. RESIST.
NO. L/s mm mm m Pa Pa Pa

1 Exhaust air Grille 306 500 300 2.50 0.0 25.0


2 Shoe 306 500 300 2.50 0.66 0.0 1.6
3 OBD 306 500 300 2.50 0.0 3.0
4 Straight Duct 612 350 350 9.30 14.98 7.6 0.0
5 Elbow 612 350 350 14.98 0.21 0.0 3.1
6 Straight Duct 612 350 350 1.80 14.98 1.5 0.0
7 Reducer (350x350 - 550x350) 612 350 350 14.98 0.23 0.0 3.4
8 Straight Duct 1,224 550 350 8.40 24.26 8.4 0.0
9 VCD 1,224 550 350 24.26 0.0 7.0
10 Reducer (550x350 - 550x450) 1,224 550 350 24.26 0.11 0.0 2.7
11 Wye 1,224 550 450 14.67 0.14 0.0 2.1
12 Straight Duct 2,142 750 450 3.20 24.17 2.3 0.0
13 Straight Duct with aucostic 25mm 2,450 700 400 3.00 45.94 4.4 0.0
14 Transtion ( 700x400 - 1700x700) 2,450 700 400 45.94 0.64 0.0 29.4
15 Round Straight Duct ∅630 1,225 550 600 1.30 8.27 0.3 0.0
16 NRD 1,225 550 350 24.30 0.0 80.0
17 Transtion ( 700x400 - 1700x700) 2,450 700 400 45.94 0.64 0.0 29.4
18 Straight Duct with aucostic 25mm 2,450 700 400 0.70 45.94 1.0 0.0
19 Elbow 2,450 700 400 45.94 0.24 0.0 11.0
20 External Louver 2,450 1000 1600 1.41 0.0 35.0
26 233
28 256
TOTAL EXTERNAL STATIC PRESSURE 284