FEED MSTB FIELD DEVELOPMENT PROJECT

DATA SHEET
MSAI FLOW TRANSMITTER

CONTRACTOR DOCUMENT REVIEW

FOR CONFORMANCE WITH SPECIFICATIONS AND DESIGN DRAWINGS

Review Code
A Accepted as it is or with minor comments

B Accepted as noted – Resubmittal required

C Not Accepted

D Information Only

THIS REVIEW DOES NOT RELIEVE THE CONTRACTOR/VENDOR

OF ANY CONTRACTUAL OBLIGATION, INCLUDING THE

RESPONSIBILITY FOR ENGINEERING AND DETAIL DESIGN.

Date By

EMP MALACCA STRAIT 26 Oct 2021


Azam

0 25/10/21 SAH Issued For Design KHS/SGW DC/SP IW


B 20/10/21 SAH Issued For Approval KHS/SGW DC/SP IW
A 13/09/21 SAH Issued For Review KHS/SGW DC/SP IW
REV DATE BY DESCRIPTION CHECK RVWD APPD
STATUS CODE : IFR = Issued For Review ; IFA = Issued For Approval ; IFD = Issued For Design

TOTAL OR PARTIAL REPRODUCTION AND/OR UTILISATION OF THIS DOCUMENT ARE FORBIDDEN WITHOUT PRIOR WRITTEN
AUTHORIZATION OF THE OWNER

DOCUMENT NO
EMP MALACCA STRAIT S.A
SEL-TBD-I-DS-021

REVISION STATUS
PT Loka Wahana Usaha
0 IFD
DOCUMENT NO.
SEL-TBD-I-DS-021
PAGE 2 OF 4
DATA SHEET FOR MSAI FLOW
TRANSMITTER

CONTRACT NO.

0 25-Oct-21 Issued For Design

B 20-Oct-21 Issued For Approval

A 13-Sep-21 Issued For Review

Rev Date DESCRIPTION

FEED MSTB FIELD DEVELOPMENT PROJECT BY : CHECKED : REVIEWED : APPROVED :


SAH KHS/SGW DC/SP IW

REVISION HISTORICAL SHEET

REV DATE DESCRIPTION


A 13/09/2021 Issued For Review

B 20/10/2021 Updated as per CPY's Comments

0 25/10/2021 No Comment
DOCUMENT NO.
SEL-TBD-I-DS-021
PAGE 3 OF 4
DATA SHEET FOR MSAI FLOW
TRANSMITTER

CONTRACT NO.

0 25-Oct-21 Issued For Design

B 20-Oct-21 Issued For Approval

A 13-Sep-21 Issued For Review

Rev Date DESCRIPTION

FEED MSTB FIELD DEVELOPMENT PROJECT BY : CHECKED : REVIEWED : APPROVED :


SAH KHS/SGW DC/SP IW

TABLE OF CONTENT

Cover …………………………………………………………………. 1
Revision Historical Sheet …………………………………………………………………. 2
Table of Contect …………………………………………………………………. 3
Flow Transmitter Datasheet …………………………………………………………………. 4
DOCUMENT NO.
SEL-TBD-I-DS-021
PAGE 4 OF 4
DATA SHEET FOR MSAI FLOW
TRANSMITTER

CONTRACT NO.

0 25-Oct-21 Issued For Design

B 20-Oct-21 Issued For Approval

A 13-Sep-21 Issued For Review

Rev Date DESCRIPTION

FEED MSTB FIELD DEVELOPMENT PROJECT BY : CHECKED : REVIEWED : APPROVED :


SAH KHS/SGW DC/SP IW
1 Tag Number FT-P-801-001
2 Service Outlet Crude Oil Booster Pump
GENERAL 3 P&ID No. SEL-TBD-O-DW-032 (1 of 2)
4 Line No. / Equipment Tag No. 6"-PL-152-B3-A
5 Ambient Temperature Humidity 70 - 95 degF 60% - 100% RH
6 Fluid Phase Crude Oil Liquid
PROCESS 7 Design Pressure Design Temperature 487 psig 200 deg F
CONDITION 8 Oper. Press. Oper. Temp. 247 psig 100.3 deg F
9 Oper. Flowrate Max. Meter Range 53.15 Am3/h 55 Am3/h
10 Meter Technology Flow (D/P Cell)
11 Element Range : Min Max -250 (VTA) 250 (VTA) inH2O
12 Calibration Range : Min Max 0 100 inH2O
13 Scale Range Min Max 0 55 Am3/h
14 Element Type Diaphragm
15 Element Material 316 SS
16 Body Material 316 SS
17 Process Flanges Material 316 SS
18 Wetted O-Rings Material Mfr. Std.
19 Fill Fluid Yes
TRANSMITTER
20 Bolts and Nuts Mfr. Std.
21 Housing Material Copper Free Aluminium
22 Accuracy ±0.5% of span
23 Process Connection 1/2" NPT
24 Electrical Connection / Cable Gland 1/2" NPT (Note 6)
25 Output 4-20mA Analog, 2-wire
26 Power Supply 24 VDC, Loop Powered
27 Communication Protocol Smart HART
28 Mounting 2" Pipe Stanchion
29 Rating 150% over pressure
30 Process Connection & Rating 1/2" NPT
31 Diaphragm Material 316 SS
32 Housing Material VTA
DIAPHRAGM SEAL 33 Fill Fluid Silicone (VTA)
34 Capilary Material 316 SS
35 Capillary Type Capilary Length VTA VTA
36 Flushing Connection N/A
37 Indicator LCD Digital type (Note 1)
38 Hydrostatic Testing Yes
39 Cleaning N/A
40 Mounting Brackets Yes, 316 SS
41 Transient (Lightning) Protection Yes
42 Name Plate 316 SS, permanently attached
OPTIONS
43 Valve Manifold type 5-way Valve, 1/2" NPTF (Note 2)
44 Valve Manifold Manufacturer Model No. VTA
45 Valve Manifold Material 316 SS
46 Calibration Yes
47 Hazardous Area Certification Class I Div 2 Gr D T3, Ex 'd'
48 Ingress Protection IP 65 min / NEMA 4X
49 Manufacturer VTA
50 Model No. VTA
PURCHASE 51 Purchase Order Number
52 Item Number
53 Serial Number
Notes:
1. Indicator shall be integral with transmitter showing engineering unit, squared-root to flow indication.
2. Drains/Vents port shall be 1/4"NPT plugged.
3. Total performance shall be ±0.15% of span for ±50°F temperature changes at 1:1 to 5:1 rangedown. Stability shall be ±0.125% of URL for 5 years at 50°F temperature
changes.
4. Flow Transmitter refer to specification for flow instrument Doc. No.ALL-GS-I-SP-005.
5. VTA = Vendor to Advice
6. Unused port shall be Ex'd' certified