Professional Documents
Culture Documents
SSD 11-20
SSD 11-20
3 Basis of Design
Building cooling load is calculated on HAP (Hourly Analysis Program) and generally,
ASHRAE recommendations are followed for design parameters in addition following are
the specific requirements for the project are followed. The calculation outputs show the
peak zone air volume required including the sensible and latent heat gains for each zone.
Results from the heat gain calculations are attached in Appendix. Zone inputs such as
areas of each zone, exposure and properties of facades & glazing, lighting & equipment
loads, and occupancy rate are attached in Appendix.
The Qatar Construction Standards 2014 has been used to identify the
worst-case design figures of external Dry Bulb and Wet Bulb temperatures. These
figures shall be used for the thermal cooling load assessment for heat gain in the
building
Building Fabric
Building fabric details have been provided by the architect and are in line with Kahramaa
minimum requirements.
Noise Level
a) Classrooms 35 to 40 NC
b) Corridors 40 to 45 NC
Occupancy
First Floor
a) Office 6 Person
b) Staff Room 20 Persons
c) Multi-Purpose Hall 107Persons
d) Reception Hall 18 Persons
e) Classroom 1 & 2 17 Persons each
Second Floor
f) Classroom 3 31 Persons
g) Classroom 4 19 Persons
h) Classroom 5 31 Persons
i) Computer Lab 13 Persons
Ventilation
Exhaust
The following features of the building are primarily focused on and have not been
compromised while achieving the energy efficiency of the school building. In the below
sections, different aspects of a building with their impact on an LZC design are discussed.
Additionally, it is described that how these aspects of the building are considered and
what strategy has been adopted in pursuance of LZC design.
Location, Orientation
Architecture
Therefore, from the architectural and interior designing point of view, it was
designed in a way that every classroom is having access to direct sunlight. For the
eastern facade of the building, the window-to-wall ratio was more than 70%
therefore taking the necessary measures to select the right U-value glass
overhang also helped harvest the sunlight while reducing the direct exposure of
the glass thus reducing cooling loads. Additionally, this building structure was
designed as airtight which really helps in the elimination strategy of infiltration. This
strategy created a positive impact in the overall indoor environment.
Sensors
Along with occupancy sensors for lighting control rooms and the
multipurpose hall will be provided with CO2 sensors and a thermostat. This will
enable the occupant to have demand control ventilation and avoid unnecessary
ventilation air thus it will decrease the cooling loads on equipment and energy
consumption. The sensors will be interfaced with BMS as well to monitor ventilation
and cooling requirements. Based on higher CO2 readings DOAS will increase or
decrease the outdoor air supply.
Equipment Condensate
Zoning
The building was divided into 13 zones based on the occupancy, use of
space, & individual control of equipment which means each zone. Briefly on the
ground floor corridor and adjacent toilets (Male & Female) are considered in one
zone, Office and adjacent toilet is considered in one zone, and then in the hallway
and adjacent small rooms (coffee room, store etc.) are considered as a separate
zone. Remaining each space including, reception, classrooms etc. are considered
a separate zone. Dividing the spaces into separate zones helped reduce the
cooling loads because most of the potions in the building have different exposures
due to which their peak loads are on different days throughout the year.
Ventilation
Ground floor corridors and toilets are designed in such a way that cold air
supply from the terminal unit shall be delivered in corridors. As per (ASHRAE
(Firm), 2019) standard 62.1 50 cfm per seat for public toilets and 25 cfm per seat
for private toilets is extracted. To compensate for the extracted air additional supply
of air (outdoor air) shall be delivered in the corridor. For toilets, only air is extracted
to create negative pressure in the toilets so that toilet odours can be stopped from
spreading inside the building.
In any learning environment, poor indoor air quality may badly impact on the
chemical vapours from indoor occupancy, furniture, and paints play a major role in
disturbing indoor air quality. HAP has a feature to comply with the outdoor air
requirements as per ASHRAE standard 62.1. This helped to estimate the required
outdoor airflow along with its sensible & latent loads on the systems.
the readings from its database as per selected types of space. Given below figure (from
ASHRAE) shows the minimum requirements of outdoor air highlighting the relevant
reading those are considered for this building and a complete table has been provided in
Appendices.
Below table represents the actual required OA CFM for each zone of the building
and their cooling loads on systems.
Sensible Latent
Zone# Space Description OA CFM
MBH MBH
First Floor
1 Corridor & Toilets 498.0 29.3 21.8
2 Reception 142.0 8.3 6.2
3 Classroom 2 226.0 13.3 9.9
4 Classroom 1 226.0 13.3 9.9
5 Office & Toilet 72.0 4.2 3.2
6 Staff Room 124.0 7.3 5.4
7 Multipurpose Hall 867.0 51.0 38.0
8 Service Hallway 10.0 0.4 -
Sub Total 2,165 CFM 127.1 94.4
Second Floor
9 Classroom 5 288.0 26.2 19.5
10 Classroom 4 436.0 16.9 12.6
11 Classroom 3 65.0 25.7 119.1
12 Corridor 202.0 3.8 2.8
13 Computer Lab 288.0 11.9 8.8
Sub Total 1,436 CFM 84.4 162.9
Grand Total 3,601 CFM 39.1 TR
Table 4-1 - Outdoor Air for Zones & Respective Cooling Loads
The supply of more outdoor air in the building than exhaust air from the
building helped to keep the building positively pressurized. This positive pressure
pushes air out of the building doors and cracks around windows and door seals
etc. This helped to eliminate air infiltration. Additionally, to stop the infiltration in the
building through the main entrance an additional airlock room/vestibule has been
created with an air curtain. Due to this infiltration load on the equipment was
negligible and therefore not considered in cooling load calculations.
Cooling Loads
The Following table illustrate the cooling loads of the building zones based
on which equipment selection shall be made.
Sensible Latent
Zone# Space Description SHR TR
MBH MBH
First Floor
1 Corridor & Toilets 10.3 2.2 0.8 1.0
2 Reception 14.5 2.4 0.9 1.4
3 Classroom 2 12.5 2.2 0.8 1.2
4 Classroom 1 11.5 2.2 0.8 1.1
5 Office & Toilet 4.7 0.9 0.8 0.5
6 Staff Room 6.9 2.6 0.7 0.8
7 Multipurpose Hall 37.0 14.1 0.7 4.3
8 Service Hallway 7.0 - 1.0 0.6
Sub Total 10.9
Second Floor
9 Classroom 5 18.4 4.1 0.8 1.9
10 Classroom 4 13.3 2.5 0.8 1.3
11 Classroom 3 19.1 4.1 0.8 1.9
12 Corridor 21.7 1.3 0.9 1.9
13 Computer Lab 15.9 1.7 0.9 1.5
Sub Total 8.5 TR
Grand Total 19.4
Table 4-2 - Zones Cooling Loads