TEST NAME RELAY TEST
Page no. Page 1 of 15
B00+R
Siemens 7SS52
Test Report
01/2023
Customer EETC
Consultant EPS Device ID: F300
500 K.V.BUS BAR
Plant El-Eqtsadyia (2) Function: PROTECTION
Panel No. =B00 + R1, R2, R3, and R4
1 Relay Data
Unit Full Order Code (MLFB) Firmware Version
CU 7SS522-06AB9-21DA0 V 4.73
BU 7SS5231-5CA01-0AA1-/HH V 3.33
Manufacturer SIEMENS
Frequency 50 HZ
Auxiliary Supply 220 VDC
Rated Current 1A
2 Settings
Bus bar Protection
Number of Bus bars : 6
Breaker Failure Protection
Breaker Failure Protection External int.
For Settings and BB Configuration See Digsi Printout
Protection System
Feeder Specification Existing
Identification Identification Device Address
(Feeder Name) Yes No
(Unit Number) (Unit Name)
1 F301A B01A 1
2 F301B B01B 2
3 F302A B02A 3
4 F302B B02B 4
5 F303A B03A 5
6 F303B B03B 6
7 F304A B04A 7
8 F304B B04B 9
9 F305A B05A 8
10 F305B B05B 10
11 F306A B06A 11
12 F306B B06B 12
13 F307A B07A 13
14 F307B B07B 14
15 F308A B08A 15
16 F308B B08B 16
17 F309A B09A 17
18 F309B B09B 18
19 F310A B10A 19
20 F310B B10B 20
21 F313A B13A 21
22 F313B B13B 22
23 F314A B14A 23
24 F314B B14B 24
25 F315A B15A 25
26 F315B B15B 26
27 F316A B16A 27
28 F316B B16B 28
L1 1 2949 97 97 97 97
B08A L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2940 97 97 97 97
B08B L2 0.5 1473 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2940 97 97 97 97
B09A L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2946 97 97 97 97
B09B L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2943 97 97 97 97
B10A L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2952 97 97 97 97
B10B L2 0.5 1476 48 48 48 48
L3 0.25 738 24 24 24 24
L1 1 2449 78 78 78 78
B13A L2 0.5 1225 39 39 39 39
L3 0.25 615 19 19 19 19
L1 1 2457 78 78 78 78
B13B L2 0.5 1227 39 39 39 39
L3 0.25 612 19 19 19 19
L1 1 2447 78 78 78 78
B14A L2 0.5 1225 39 39 39 39
L3 0.25 612 19 19 19 19
L1 1 2462 78 78 78 78
B14B L2 0.5 1225 39 39 39 39
L3 0.25 612 19 19 19 19
L1 1 2946 97 97 97 97
B15A L2 0.5 1470 48 48 48 48
L3 0.25 738 24 24 24 24
L1 1 2949 97 97 97 97
B15B L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2949 97 97 97 97
B16A L2 0.5 1473 48 48 48 48
L3 0.25 735 24 24 24 24
L1 1 2955 97 97 97 97
B16B L2 0.5 1470 48 48 48 48
L3 0.25 735 24 24 24 24
Measured values
Setting L1 L2 L3
Bus
Function value Iref/Ino Pickup Pickup Pickup
Zone Operating Operating Operating
(A) current current current
time (sec) time (sec) time (sec)
(A) (A) (A)
BUS Id sup BZ 0.18 0.189 2.1 0.186 2.1 0.187 2.1
3000/2500
1A Id sup CZ 0.18 0.190 2.1 0.189 2.1 0.189 2.1
BUS Id sup BZ 0.15 0.156 2.1 0.155 2.1 0.156 2.09
3000/3000
2A Id sup CZ 0.15 0.156 2.1 0.155 2.1 0.156 2.09
BUS Id sup BZ 0.18 0.186 2.07 0.186 2.1 0.187 2.1
3000/2500
1B Id sup CZ 0.18 0.189 2.07 0.189 2.1 0.190 2.1
BUS Id sup BZ 0.15 0.153 2.07 0.152 2.09 0.153 2.1
3000/3000
2B Id sup CZ 0.15 0.155 2.07 0.155 2.09 0.155 2.1
Measured Values
Setting L1 L2 L3
Check
Function Value Pickup Pickup
Zone Pickup Operating Operating Operating
(A) current current
current (A) time (sec) time (sec) time (sec)
(A) (A)
At Feeder
Idiff CZ 0.54 0.542 0.023 0.540 0.027 0.541 0.034
Bay
At TR
Idiff CZ 0.65 0.648 0.022 0.647 0.032 0.648 0.033
Bay Unit
L1 0.67 0.674 30
B01A L2 0.67 0.674 26
L3 0.67 0.674 35
L1 0.67 0.674 27
B01B L2 0.67 0.672 37
L3 0.67 0.673 28
L1 0.67 0.675 34
B02A L2 0.67 0.674 40
L3 0.67 0.674 37
L1 0.67 0.675 39
B02B L2 0.67 0.674 31
L3 0.67 0.675 35
L1 0.804 0.818 30
B03A L2 0.804 0.816 32
L3 0.804 0.816 29
L1 0.804 0.812 34
B03B L2 0.804 0.812 33
L3 0.804 0.812 35
L1 0.67 0.674 25
B04A L2 0.67 0.674 31
L3 0.67 0.673 35
L1 0.67 0.676 27
B04B L2 0.67 0.674 27
L3 0.67 0.674 35
L1 0.67 0.672 28
B05A L2 0.67 0.674 27
L3 0.67 0.673 34
L1 0.67 0.675 33
B05B L2 0.67 0.673 41
L3 0.67 0.674 26
L1 0.804 0.813 32
B06A L2 0.804 0.813 34
L3 0.804 0.811 41
L1 0.804 0.814 35
B06B L2 0.804 0.814 30
L3 0.804 0.813 33
L1 0.67 0.677 39
B07A L2 0.67 0.674 41
L3 0.67 0.674 30
L1 0.67 0.677 26
B07B L2 0.67 0.674 27
L3 0.67 0.675 39
L1 0.67 0.674 27
B08A L2 0.67 0.674 29
L3 0.67 0.674 33
L1 0.67 0.675 34
B08B L2 0.67 0.675 33
L3 0.67 0.675 28
L1 0.67 0.676 42
B09A L2 0.67 0.675 40
L3 0.67 0.674 38
L1 0.67 0.675 29
B09B L2 0.67 0.675 32
L3 0.67 0.675 38
L1 0.67 0.675 36
B10A L2 0.67 0.675 31
L3 0.67 0.675 26
L1 0.67 0.675 38
B10B L2 0.67 0.675 35
L3 0.67 0.675 38
L1 0.804 0.813 35
B13A L2 0.804 0.813 34
L3 0.804 0.813 36
L1 0.804 0.814 28
B13B L2 0.804 0.812 30
L3 0.804 0.813 28
L1 0.804 0.816 35
B14A L2 0.804 0.813 25
L3 0.804 0.812 37
L1 0.804 0.811 34
B14B L2 0.804 0.815 39
L3 0.804 0.812 25
L1 0.67 0.678 40
B15A L2 0.67 0.674 37
L3 0.67 0.673 33
L1 0.67 0.675 38
B15B L2 0.67 0.675 40
L3 0.67 0.675 29
L1 0.67 0.675 40
B16A L2 0.67 0.675 35
L3 0.67 0.675 27
L1 0.67 0.675 33
B16B L2 0.67 0.675 37
L3 0.67 0.675 36
Id = | I1 – I2 | Is = | I1 | + | I2 |
Test connection:
I1∟ 0°
Trip
I2 ∟180º
Bay unit 2 A
Test connection:
11 ∟0 °
Central Bay unit 1 A Test set
unit
Bay unit 2
I2 ∟180º
Bay unit 3 A
Trip
8 BB INTER-TRIP
INTER-TRIP
BB
SETTING
Unit TRIP CURRENT Operating time (ms)
TIME DELAY
SETTING
L1 L2 L3
B01A 0.25 0.67 PU 279 278 282
B01B 0.25 0.67 PU 281 278 284
B02A 0.25 0.67 PU 277 277 281
B02B 0.25 0.67 PU 279 277 282
B03A 0.25 0.67 PU 280 277 284
B03B 0.25 0.67 PU 279 276 282
B04A 0.25 0.67 PU 280 278 283
B04B 0.25 0.67 PU 279 277 282
B05A 0.25 0.67 PU 278 276 281
B05B 0.25 0.67 PU 278 276 281
B06A 0.25 0.67 PU 278 276 281
B06B 0.25 0.67 PU 279 277 282
B07A 0.25 0.67 PU 279 277 283
B07B 0.25 0.67 PU 278 277 281
B08A 0.25 0.67 PU 278 275 281
B08B 0.25 0.67 PU 279 277 282
B09A 0.25 0.67 PU 281 279 284
B09B 0.25 0.67 PU 278 276 281
B10A 0.25 0.67 PU 278 277 282
B10B 0.25 0.67 PU 284 280 285
B13A 0.25 0.67 PU 278 276 282
B13B 0.25 0.67 PU 279 276 283
B14A 0.25 0.67 PU 279 276 282
B14B 0.25 0.67 PU 280 278 282
B15A 0.25 0.67 PU 277 276 280
B15B 0.25 0.67 PU 279 277 282
B16A 0.25 0.67 PU 276 276 282
B16B 0.25 0.67 PU 278 275 281
9 BF function
9.1 SETTING
Operation mode : Trip from external CBF protection