Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Doc no.

QA/QP/804

Rev no. 00

Rev date 01-05-2018 QUALITY ASSURANCE PLAN FOR 750/900/910/1010 kVA DV CRDI GENSET
Date of inspection:
Type of Genset: Silent Genset model: Quantity:

Agency
Ref.Documents/Accept
Sr.No. Components Characteristics Method of Checks Extent Extent By KOEL Customer/ Remarks
ance Norm
KOEL Inspection
Agency

Condition Visual - Damage Free V W


1 No. /Model
L *W*H - Outside
Dimensional Check Measuring Tape - GA Drawing M W
dimension of Genset assly
No leakage of engine & Fuel
Leakage Test Visual 100% 1 No. /Model No Leakage V W tank during genset test
cycle.
CRDi Genset test
No Load - 3 Mins 100% procedure M W
(D16.901.11.0.PR)
CRDi Genset test
25% Load - 3 Mins 100% procedure M W
(D16.901.11.0.PR)
1 DG Set CRDi Genset test
50% Load - 3 Mins 100% procedure M W
(D16.901.11.0.PR)
CRDi Genset test
Load test 75% Load - 3 Mins 100% 1 No. /Model procedure M W
(D16.901.11.0.PR)
CRDi Genset test
100% Load - 30 Mins 100% procedure M W
(D16.901.11.0.PR)
CRDi Genset test
110% Load -10 Mins 100% procedure M W
(D16.901.11.0.PR)
CRDi Genset test
100% Load - 3 Mins 100% procedure M W
(D16.901.11.0.PR)
Verification of
2 Alternator --- Document Review 100% 100% Alternator Test V V
Certificate
Verification of Engine
3 Engine --- Document Review 100% 100% V V
Test Certificate

Rust Free Visual - 1 No. /Model No rust V V

Base Plate Dimensions Measuring Tape 100% 1 No. /Model Drawing V V


Base Plate with
4
integrated Fuel tank Man hole Breather Visual - Available V V

Fuel return & suction line Visual - 1 No. /Model Available V V

Fuel Drain Visual - Available V V

5 Accessories Loose supply items Visual - 1 No./Model Packing List V V

Company Standard -
6 Canopy Powder Coating DFT Test - 1 No. /Model M W
30045
Note :- M -Measurement , V - Verification & W -Witness