119 - El-Adm-07

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

KEY PLAN

Branch Panel: DB-ADM


Location: ADMIN BUILDING Volts: 400/230V A.I.C. Rating: 20 K.A.I.C
Supply From: MCC-3 Phases: 3 Feeder Type: Cu,XLPE/SWA/PVC+Cu,PVC,G
Mounting: RECESSED Wires: 5 Feeder sIZING: 4C- 70 mm²+1C- 35 mm², G
Enclosure: IP52 MCCB Rating: 100A TPN MCCB,ELR
GROUND PHASE PHASE GROUND
CONDUIT CONDUIT
CKT Circuit Description CROSS CROSS Trip Poles A B C A B C Poles Trip CROSS CROSS Circuit Description CKT
DIA (mm)
SECTION SECTION SECTION SECTION
DIA (mm)
NOTES
1 20 Lighting** 2.5 mm² 2.5 mm² 10 A 1 10 VA 268 VA 1 10 A 2.5 mm² 2.5 mm² Lighting** 20 2
3 20 Lighting** 2.5 mm² 2.5 mm² 10 A 1 132 VA 273 VA 1 10 A 2.5 mm² 2.5 mm² Lighting** 20 4
5 20 Lighting** 3.0 mm² 2.5 mm² 10 A 1 264 VA 360 VA 1 20 A 4.0 mm² 4.0 mm² Receptacle* 20 6
7 20 Lighting** 2.5 mm² 2.5 mm² 10 A 1 380 VA 1000 VA 1 20 A 4.0 mm² 4.0 mm² Industrial Plug* 20 8
9 20 Receptacle* 4.0 mm² 4.0 mm² 20 A 1 540 VA 540 VA 1 20 A 4.0 mm² 4.0 mm² Receptacle* 20 10
11 20 Receptacle* 4.0 mm² 4.0 mm² 20 A 1 540 VA 1500 VA 1 20 A 4.0 mm² 4.0 mm² HVAC** 20 12
13 20 Receptacle* 4.0 mm² 4.0 mm² 20 A 1 1080 VA 4500 VA 1 32 A 6.0 mm² 6.0 mm² HVAC** 25 14
15 20 Lighting** 2.5 mm² 2.5 mm² 10 A 1 879 VA 1500 VA 1 20 A 4.0 mm² 4.0 mm² HVAC** 20 16
17 25 HVAC** 6.0 mm² 6.0 mm² 32 A 1 4500 VA 540 VA 1 20 A 4.0 mm² 4.0 mm² Receptacle* 20 18
19 20 Receptacle* 4.0 mm² 4.0 mm² 20 A 1 540 VA 1000 VA 1 20 A 4.0 mm² 4.0 mm² Industrial Plug* 20 20
21 25 Water Heater* 6.0 mm² 6.0 mm² 32 A 1 3125 VA 540 VA 1 20 A 4.0 mm² 4.0 mm² Receptacle* 20 22
23 20 Refrigeration* 4.0 mm² 4.0 mm² 20 A 1 1000 VA 1500 VA 1 20 A 4.0 mm² 4.0 mm² Water Heater* 20 24
25 20 HVAC** 4.0 mm² 4.0 mm² 20 A 1 1500 VA 0 VA 1 16 A -- -- Spare -- 26
27 20 Industrial Plug* 4.0 mm² 4.0 mm² 20 A 1 1000 VA 1500 VA 1 20 A 4.0 mm² 4.0 mm² HVAC** 20 28
29 1680 VA 0 VA 1 20 A -- -- Spare -- 30
10.0 10.0
31 32 DB-UPS 40 A 3 2000 VA 0 VA 1 20 A -- -- Spare -- 32
mm² mm²
33 2000 VA 0 VA 1 20 A -- -- Spare -- 34
35 -- Spare -- -- 20 A 1 0 VA 0 VA 1 20 A -- -- Spare -- 36
TOTAL VA PER PH R/Y/B: 11882 VA 11832 VA 11623 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
HVAC 15900 VA 90.00% 14310 VA
Receptacle 4680 VA 70.00% 3276 VA Total Conn. Load: 35336 VA
Lighting 1243 VA 90.00% 1118 VA Total Est. Demand: 29486 VA
Water Heater 4625 VA 50.00% 2313 VA Total Est. Demand + 20% Spare: 35383 VA
Refrigeration 1000 VA 50.00% 500 VA Total Current: 51 A
Light Current Equipment 4180 VA 100.00% 4180 VA
Industrial Plug 3000 VA 100.00% 3000 VA
Media Converter 1500 VA 100.00% 1500 VA
Notes:
* Circuit protected with RCBO 30mA ** Circuit protected with RCBO 100mA
REFERENCE DRAWINGS
DRAWING TITLE DRAWING NO.

Branch Panel: DB-UPS


LOCATION: OPERATOR CONTROL ROOM VOLTS: 400/230V A.I.C. RATING: 15 K.A.I.C
SUPPLY FROM: DB-ADM PHASES: 3 FEEDER TYPE: Cu,XLPE/SWA/PVC+Cu,PVC,G
MOUNTING: SURFACE WIRES: 5 FEEDER SIZE 4C-10 mm²+1C- 10 mm², G
ENCLOSURE: NEMA-12 MCCB RATING: 40A TPN MCCB,ELR
GROUND PHASE PHASE GROUND
CONDUIT CONDUIT
CKT DIA (mm) Circuit Description CROSS CROSS Trip Poles R Y B R Y B Poles Trip CROSS CROSS Circuit Description DIA (mm) CKT
SECTION SECTION SECTION SECTION

1 20 Receptacle* 4 mm² 4 mm² 20 A 1 180 VA 500 VA 1 20 A 4 mm² 4 mm² DATA RACK** 20 2


3 25 Media Converter** 6 mm² 6 mm² 32 A 1 500 VA 1000 VA 1 20 A 4 mm² 4 mm² MAIN DATA RACK** 20 4 MAR A.M M.A
00 2023 ISSUED FOR TENDER PACKAGE M.K M.KH Y.A S.W
5 20 WORK STATION (1)* 4 mm² 4 mm² 20 A 1 500 VA 1000 VA 1 32 A 6 mm² 6 mm² Media Converter** 6

TED
ED

ED
ED

D
7 20 FACP** 4 mm² 4 mm² 20 A 1 500 VA 500 VA 1 20 A 4 mm² 4 mm² WORK STATION (1)* 20 8

WN

IEW
CKE

ROV
REV.NO. DATE ISSUED FOR

IGN

MIT
DRA

REV
CHE
9 20 WORK STATION (2)* 4 mm² 4 mm² 20 A 1 500 VA 0 VA 1 20 A -- -- Spare -- 10

DES

SUB

APP
11 20 WORK STATION (2)* 4 mm² 4 mm² 20 A 1 500 VA 0 VA 1 32 A -- -- Spare -- 12
TOTAL VA PER PH R/Y/B: 1680 VA 2000 VA 2000 VA DRAWING
STATUS ISSUED FOR TENDER PACKAGE
TOTAL AMP PER PH R/Y/B: 7A 9A 9A

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals CLIENT
Light Current Equipment 4180 VA 100.00% 4180 VA
Media Converter 1500 VA 100.00% 1500 VA Total Conn. Load: 5680 VA
Total Est. Demand: 5680 VA
Total Est. Demand + 20% Spare: 6816 VA
Total Current: 10 A

Notes:
* Circuit protected with RCBO 30mA ** Circuit protected with RCBO 100mA
CONSULTANT

& PARTNERS
CONSULTING ENGINEERS

TENDER

CONSTRUCTION WORKS
FOR THE UPGRADE OF AL WAGAN STP IN AL AIN

ADMIN BUILDING
PANEL SCHEDULE

TENDER NO. 0-15527

SHEET SIZE A1

SCALE DRAWING No. REV.

1:50 EL-ADM-07 00