FOCP-FCC-CJI-EA-2015-0002-003 Data Sheet For Low Voltage Motor Control Centre

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

PROVISION OF EPC SERVICE FOR FIELD

CONTROL CENTER FOR MAJNOON


OPERATION CENTER PROJECT

DETAIL DESIGN FOCP-FCC-CJI-EA-2015-0002 REV.: 003 PAGE 1 OF 7

DATA SHEET
FOR
LOW VOLTAGE MOTOR CONTROL CENTRE

003 ISSUED FOR AS-BUILT 18.11.2019 Xu DD Li Q Liu XM Wang YT

002 ISSUED FOR CONSTRUCTION 18.11.2019 Xu DD Li Q Liu XM Wang YT

001 ISSUED FOR APPROVAL 22.10.2019 Xu DD Li Q Liu XM Wang YT

REV. DESCRIPTION DATE PREP'D CHK'D REV'D APP'D


STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 2 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 A APPLICABLE SPECIFICATION & STANDARD MAJ-0066-FOC-01-ELE-SPC-0002
3 SPECIFICATION FOR LOW VOLTAGE MOTOR
4 B QUANTITY CONTROL CENTRE
5
6 C CLIMATIC CONDITIONS
7 1 AMBIENT TEMPERATURE -4~54℃
8 2 ALTITUDE ( ABOVE MSL ) 4~10 Mtrs. AVERAGE SEA LEVEL
9 3 RELATIVE HUMIDITY 16.8 to 65.9 %
10 4 ATMOSPHERE DUST LADEN
11
12 D SYSTEM PARTICULARS
13 1 PRIMARY SYSTEM : 400 V ± 10 %
14 2 VOLTAGE 50 Hz ± 5 %
15 3 FREQUENCY 3 PHASE / 4 WIRE + PE
16 4 NO. OF PHASES / WIRE SOLID GROUND
17 5 GROUNDING 50 kA, 3-Ph, SYMM.1 sec
18 6 FAULT LEVEL INDOOR
19
20 E GENERAL
21 1 RATED WORK VOLTAGE 400V
22 2 RATED INSULATED VOLTAGE 1000V
23 3 NUMBER OF PHASES 3PH
24 4 RATED CURRENT MAJ-0066-FOC-01-ELE-DWG-0002
25 5 FREQUENCY 50Hz
26 6 GROUND SOLID GROUND
27 7 RATED SHORT DURATION CURRENT AND TIME 50kA FOR 1S
28 8 RATED PEAK DURATION CURRENT 150kA
29 9 TYPE WITHDRAWABLE
30 10 PROTECTION DEGREE OF ENCLOSURE IP41
31 11 DIRECTION OF BUSBAR INCOMING TOP
32 12 DIRECTION OF CABLE OUTGOING BOTTOM
33 13 DEVELOPMENT TERMINATER AT BOTH ENDS (DRILLED WITH HOLES)
34 14 BUS INSULATION REQUIRED
35 15 BUS MARK REQUIRED
36 16 SPARE SPACE 20% SPARE FEEDERS HAVING ONE OF EACH RATING
37 17 INSTALLATION PLATE OF CABLE GLAND REQUIRED
38 18 HEAT EMISSION / HEAT LOAD BY VENDOR
39 19 MAINTENANE ACCESSIBILITY REAR
40 20 BUSBAR COPPER
41 21 DISTRIBUTED NEUTRAL REQUIRED
42 22 MECHANICAL INTERLOCK REQUIRED
43 23 ELECTRICAL INTERLOCK REQUIRED
44 24 BODY MATERIAL AND THICKNESS GALVENIZED STEEL WITH MINIMUM THICKNESS OF 2mm
45 25 LIGHTING INSIDE EACH CUBICLE REQUIRED
46
47 F CONTROL / AUXILIARY SUPPLY
48 1 BREAKER
49 1.1 SPRING CHARGING MOTOR 230 V AC
50 1.2 CLOSING COIL 230 V AC
51 1.3 TRIPING COIL 230 V AC
52 1.4 CONTROL CIRCUITS 230 V AC
53 2 CONTACTOR COIL FOR MOTOR FEEDERS 230 V AC
54 3 POTENTIAL INDICATING LIGHTS 230 V AC
55 4 OTHER INDICATING LIGHTS 230 V AC
56 5 SPACE HEATER WITH THERMOSTAT REQUIRED
57 6 SCREW BOLT AND NUT STAINLESS STEEL
58 7 GLAND PLATE TOP AND REMOVABLE UNDRILLED
59
60
61
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 3 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 G CONSTRUCTION
3 1 TYPE COMPARTMENTAL FORM 3b / FORM 4a
4 2 TYPES OF FEEDERS
5 a) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT
6 b) ALL OTHER FEEDERS FULLY DRAWOUT (ALL OUTGOING FEEDERS)
7 3 ARRANGEMENT OF PMC AND MCC SINGLE FRONT
8 4 BASE FRAME REQUIRED CHANNEL FRAME
9 5 DIMENSION OF MAIN BUS MAJ-0066-FOC-01-ELE-DWG-0002
10 6 DIMENSION OF NEUTRAL BUS MAJ-0066-FOC-01-ELE-DWG-0002
11
12 H CIRCUIT OF INCOMING AND BUS-TIE
13 1 TYPE OF CIRCUIT BREAKER AIR CIRCUIT BREAKER
14 2 ISOLATED FUNCTION WITHDRAW TYPE
15 3 POLE 4 POLES
16 4 RATED CURRENT MAJ-0066-FOC-01-ELE-DWG-0002
17 5 MAKING CAPACITY 50kA
18 6 SYMMETRICAL BREAKING CAPACITY 50kA (RMS)
19 7 ASSYMETRICAL BREAKING CAPACITY BY VENDOR
20 8 SHORT TIME CURRENT RATING 50kA FOR 1S
21 9 INSULATION LEVEL F
22 10 FOR POWER FREQUENCY HV TEST 2.2 kV FOR 1 MINUTE
23 11 PROTECTED RELAY REQUIRED ON THE CIRCUIT BREAKER
24 12 OVER-CURRENT PROTECTION REQUIRED
25 13 DELAY OVER-CURRENT PROTECTION REQUIRED
26 14 OVER-LOAD PROTECTION REQUIRED
27 15 GROUND PROTECTION REQUIRED
28 16 INCOMING MEASURE METER REQUIRED
29 17 BUS-TIE MEASURE METER ■V (WITH SELECTOR) ■A(3NO.S) ■kWh ■kvarh
30 ■IEC 61850 FEED BACK TO PMS
31 18 COMMUNICATION PORT ■RJ45 REDUNDANCE
32 ■PROTOCOL IEC61850 GOOSE
33
34 I CIRCUIT OF FEEDER
35 1 TYPE OF CIRCUIT BREAKER MCCB
36 2 OVER-CURRENT PROTECTION REQUIRED
37 3 DELAY OVER-CURRENT PROTECTION REQUIRED
38 4 OVER-LOAD PROTECTION REQUIRED
39 5 MEASURE METER REQUIRED
40
41 J CIRCUIT OF MOTOR FEEDER
42 1 TYPE OF CIRCUIT BREAKER MCCB
43 2 OVER-LOAD PROTECTION REQUIRED
44 3 SINGLE PHASE GROUND PROTECTION REQUIRED FOR 30kW AND LARGER MOTORS
45 THROUGH ZERO SEQUENCE CT (CBCT)
46 DELAY OVER-CURRENT PROTECTION REQUIRED
47 4 TYPE OF CONTACTOR MAGNETIC AIR BREAK, AC-3, 1.2 TIMES MOTOR FULL
48 LOAD CURRENT
49 5 OVER-CURRENT PROTECTION REQUIRED
50 6 EMERGENCY STOP BUTTON ON THE CABINET REQUIRED
51 7 TYPE OF PUSH BUTTON SELF HOLDING PUSH BUTTON
52 8 TYPE OF THERMAL RELAY BIMETAL TYPE
53 9 PROTECTION RELAY REQUIRED FOR 100A AND LARGER MOTORS
54 10 MOTOR PROTECTION UNIT REQUIRED FOR 30kW AND LARGER MOTORS
55 11 MINIMUM SIZE FOR INTERNAL WIRING 2.5mm2 FOR CONTROL AND PROTECTION
56 1.5mm2 FOR SIGNAL WIRING
57 12 METERING APPARATUS SQUARE PATTERN TYPE
58 72mm x 72mm OR 96mm x 96mm
59 13 PROTECTION AND AUXILIARY RELAY DIGITAL INDICATOR
60 14 CABLE SUPPORTS FOR CABLES AND TERMINALS WITH BOLTS AND NUTS REQUIRED
61 15 SPARE TERMINAL AT LEAST 20%
62
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 4 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 K AUTOMATIC TRANSFER SWITCHING DEVICE
3 1 TRANSFER TIME 3 SECOND
4 2 PARALLEL OPERATING TIME 1 SECOND
5 3 CONTACT CAPACITY 20A
6 4 COMMUNICATION PORT RJ45
7 5 POWER SUPPLY 230V AC
8 MAJ-0066-FOC-01-ELE-DWG-0002
9
10 L CAPACITIVE COMPENSATOR
11 1 CAPACITY MAJ-0066-FOC-01-ELE-DWG-0002
12 2 VOLTAGE 400V
13 3 FREQUENCY 50Hz
14 4 INSULATION RESISTANCE BY VENDOR
15 5 LOSS ANGLE BY VENDOR
16 6 TEMPERATURE CHARACTERISTIC BY VENDOR
17 7 TEMPERATURE FACTOR BY VENDOR
18
19 M CURRENT TRANFORMER
20 1 INSULATED TYPE BY VENDOR
21 2 SECONDARY CURRENT
22 a) FOR PROTECTION & METERING ON PANEL 1A
23 b) FOR REMOTE MOUNTED INSTRUMENT 1A
24 3 PHASE NOS 3P
25 4 ACCURACY CLASS
26 a) FOR PROTECTION 5P
27 b) FOR METERING 1.0
28
29 N VOLTAGE TRANSFORMER
30 1 INSULATED TYPE BY VENDOR
31 2 SECONDARY VOLTAGE
32 a) FOR PROTECTION & METERING ON PANEL 110V
33 b) FOR REMOTE MOUNTED INSTRUMENT 110V (IF REQUIRED)
34 3 PHASE NOS 3P
35 4 ACCURACY CLASS
36 a) FOR PROTECTION 3P
37 b) FOR METERING 1.0
38 O MCCB AIR BREAK TYPE WITH BREAKING CAPACITY OF
39 50kA & SHORT TIME RATING OF 50 kA FOR 1S.
40 PROVISION OF PADLOCKING REQUIRED IN "OFF"
41 POSITION.
42
43 P OVERLOAD RELAYS BIMETALLIC THERMAL AND AMBIENT
44 TMPERATURE COMPENSATED, MANUAL RESET.
45
46 Q INCOMER RELAYS OVERCURRENT RELAY
47 RESTRICTED EARTH FAULT RELAY
48 STANDBY EARTH FAULT RELAY
49 AUXILIARY RELAYS
50 TRIP CIRCUIT SUPERVISION RELAY
51 MASTER TRIP RELAY
52
53 R TRANSFORMER ALARM WINDOW REQUIRED
54 S COMPONENTS
55 1 MAIN BUSBARS & RISERS
56 1.1 MATERIAL TINNED COPPER, FULLY INSULATED
57 1.2 RATING MAJ-0066-FOC-01-ELE-DWG-0002
58 1.3 MAIN BUSBAR POSITION TOP
59 2 EARTH BUS
60 2.1 MATERIAL COPPER
61 2.2 MINIMUM SIZE SUITABLE FOR FAULT CURRENT
62 3 CIRCUIT BREAKER OPERATING MECHANISM
63 a) CLOSING MANUAL
64 b) TRIPPING SHUNT TRIP
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 5 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1 INFORMATION
2 4 ACCURACY CLASS OF INSTRUMENTS
3 a) AMMETERS CLASS 1.5
4 b) kWH METERS / PF METERS CLASS 2.5
5 5 INDICATING INSTRUMENT - SIZES BY VENDOR
6 6 CABLE ENTRY FOR OUTGOING TOP
7 7 CABLE GLANDS REQUIRED
8
9 8 CABLE LUGS REQUIRED
10 9 PAINTING (TYPE & SHADE) EPOXY RAL7032
11 POWER SUPPLY 230 V
12
13 T DRAWINGS & OTHER INFORMATION MAJ-0066-FOC-01-ELE-SPC-0002
14 SPECIFICATION FOR LOW VOLTAGE MOTOR
15 CONTROL CENTRE
16 MAJ-0066-FOC-01-ELE-DWG-0002
17 LV SINGLE LINE DIAGRAM
18
19 U NAME PLATES
20 MATERIAL STASTAINLESS STEEL
21 TEXT TYPE BLABLACK TEXT ENGRAVED
22 APPLICABILITY FO FOR EQUIPMENT LABEL AND INDICATION
23 FIXED TYPE RIVRIVETED
24 THE INFORMATION GIVEN ON THESE GENERAL NAMEPLATES SHALL BE AS FOLLOWS:
25 1 NUMBER, APPLICABLE RATED VALUES AND NUMBER OF RELEVANT STANDARD
26 2 THE YEAR OF MANUFACTURE
27 3 THE MANUFACTURER NAME OR TRADE MARK
28 4 RATED OPERATIONAL VOLTAGE AND FREQUENCY
29 5 SHORT CIRCUIT STRENGTH AND TIME
30 6 DEGREE OF PROTECTION
31 7 DIMENSIONS: HEIGHT, WIDTH (LENGTH) AND DEPTH
32 8 WEIGHT
33
34 V TESTS & INSPECTION AS PER SPECIFICATION / IEC
35
36 W CIRCUIT DETAILS MAJ-0066-FOC-01-ELE-DWG-0002
37
38
39 X MAKE OF EQUIPMENT APPROVAL BY PURCHASER
40
41 Y FITTINGS & ACCESSORIES
42 1 LIFTING EYE(S) (TRANSPORTATION SECTION/CUBICLE)
43 2 CONNECTORS: COMPRESSION TYPE, SPACE FOR STRESS CONES
44 3 LABELS: BLACK LETTERS ON WHITE LAMACOID
45 4 RACKING CRANK ASSEMBLY
46 5 MANUAL CHARGING HANDLE
47 6 CIRCUIT BREAKER REMOVAL TRUCK
48 7 TEST JUMPERS
49 8 CUBICLE LIGHTS
50 9 LAMP TEST FACILITIES (WHITE COLOUR)
51 10 VOLTAGE PRESENT LIGHTS (CIRCUIT BREAKER DEAD SIDE)
52
53
54
55
56
57
58
59
60
61
62
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 6 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1
2 Notes:
3 1 THE AMMETER SHALL BE INSTALLED ON THE SWITCHGEAR IN THE CIRCUIT WHICH CURRENT IS ABOVE 100A.
4 2 THE ZERO SEQUENCE UNBALANCE CURRENT PROTECTION SHALL BE INSTALLED IN THE CIRCUIT FOR ABOVE MOTOR FEEDER 30kW.
5 3 VENDOR SHALL SUPPLY THE CTS FOR REF AS PER THE CT PARAMETER WHICH ARE PROVIDED BY TRANSFORMER VENDOR
6 AT TRANSFORMER SIDE.
7 4 THE SWITCHGEARS SHALL BE OF METAL ENCOLSED TYPE, FITTED WITH FULLY WITHDRAWABLE EQUIPMENT AND ARRANGED
8 IN MULTI-CUBICLE FORMATION. EACH INCOMING OR OUTGOING CIRCUIT SWITCHING DEVICE SHALL BE HOUSED IN ITS OWN
9 WITHDRAWABLE ENCLOSURE. THE SWITCHGEAR SHALL BE COMPLETELY COMPARTMENTALIZED AND METAL ENCLOSED IN
10 ACCORDANCE WITH FORM 3b / 4a SEPARATION.
11 5 ALL CUBICLE DOORS SHALL BE MECHANICALLY INTERLOCKED WITH ISOLATING DEVICES TO PREVENT ACCESS TO LIVE
12 EQUIPMENT. ALL COMPARTMENTS SHALL BE KEY-LOCKED CLOSED.
13 6 THE OPERATING HANDLES, INSTRUMENT AND PROTECTION DEVICES ARE TO BE LOCATED IN THE AREA 0.45 TO 1.8m FROM
14 THE FLOOR FOR EASE OF OPERATION. MAXIMUM HEIGHT OF THE SWITCHGEARS INCLUDING BASE CHANNEL SHALL BE 2.3m.
15 7 A MINIMUM OF 160mm SPACE BETWEEN THE BASE OF THE SWITCHGEAR AND THE UNDERSIDE OF LOWEST CUBICLE SHALL
16 BE CONSIDERED.
17 8 AUTOMATICALLY OPERATED SHUTTERS WITH PADLOCKING FACILITIES SHALL BE PROVIDED TO SCREEN BUSBARS AND
18 CABLE CONNECTIONS WHEN CIRCUIT BREAKER IS WITHDRAWN.
19 9 CIRCUIT BREAKER SHALL BE PROVIDED WITH 'SERVICE / TEST' AND 'ISOLATED' POSITIONS AND SUITABLE LOCKING DEVICES
20 SHALL BE PROVIDED FOR 'ISOLATED' AND 'TEST' POSITIONS.
21 10 FOLLOWING SAFETY INTERLOCK SHALL BE PROVIDED ON ALL AIR CIRCUIT BREAKERS:
22 i) IT WILL NOT BE POSSIBLE TO WITHDRAW OR INSERT AIR CIRCUIT BREAKER UNLESS THE BREAKER IS IN OPEN CONDITION.
23 ii) IT WILL NOT BE POSSIBLE TO OPEN THE BREAKER COMPARTMENT DOOR UNLESS THE BREAKER IS IN OPEN CONDITION.
24 HOWEVER, INTERLOCK DEFEAT MECHANISM SHALL BE PROVIDED FOR OPENING THE DOOR AFTER DEFEATING THE INTERLOCK.
25 iii) TROLLEY OF BREAKER SHALL BE EARTHED FIRST BEFORE DRAWOUT POWER CONTACT ENGAGES WITH FIXED POWER
26 CONTACTS ON BUSBARS. BREAKER SHALL BE PROVIDED WITH 4 'NO' + 4 'NC' SPARE BREAKER AUXILIARY CONTACTS FOR
27 PURCHASER'S USE.
28 11 ALL MOTOR CIRCUITS SHALL HAVE FACILITIES FOR REMOTE START / STOP OPERATION. THE MOTOR CAN BE OPERATED BY
29 LOCAL CONTROL STATION AND BY DCS SYSTEM IN CONTROL CENTER.
30 12 EARTH FAULT PROTECTION SHALL BE PROVIDED FOR ALL MOTOR CIRCUITS 30kW AND ABOVE. EARTH FAULT PROTECTION
31 SHALL BE CORE BALANCE EARTH FAULT RELAY INCORPARATION AN OPERATION DELAY TIMER AND SHALL HAVE A
32 SENSITIVITY NOT EXCEEDING 10% OF THE RATED MOTOR CURRENT.
33 13 EACH MOTOR SHALL BE FITTED WITH THE FOLLOWING CONTROL AND INDICATION DEVICES MOUNTED ON THE FRONT OF THE UNIT.
34 ● RED INDICATION LAMP FOR 'ON' POSITION OF CONTACTOR
35 ● GREEN INDICATON LAMP FOR 'OFF' POSITION OF CONTACTOR
36 ● AMBER INDICATION LAMP FOR 'TRIP' OF CONTACTOR ON OVERLOAD
37 ● WHITE INDICATION LAMP FOR 'CONTROL CIRCUIT FAULT ON/OFF'
38 ● STAY PUT TYPE 'STOP' PUSH BUTTON
39 ● OVERLOAD RESET' PUSH BUTTON
40 ● START PUSH BUTTONS FOR TESTING
41 ● CURRENT TRANSFORMER WITH 1A SECONDARY FOR OPERATING LOCAL AND REMOTE AMMETERS
42 ● LOCAL AMMETER
43 14 SAFETY SHUTTERS SHALL BE PROVIDED TO MAINTAIN. THEY SHALL AUTOMATICALLY COVER ALL BUSBARS AND CABLE
44 SPOUTS OR ISOLATING CONTACTS WHENEVER REMOVABLE OR WITHDRAWABLE UNITS ARE REMOVED. IT SHALL BE
45 AUTOMATICALLY OPENED AND CLOSED BY ACTION OF REMOVABLE OR WITHDRAWABLE UNIT MOVEMENT. A POSITIVE
46 DRIVE TO THE SHUTTERS SHALL BE PROVIDED IN BOTH DIRECTIONS. THEY SHALL BE CAPABLE OF BEING PADLOCKED IN
47 THE 'CLOSED' POSITION. THEY SHALL BE SO DESIGNED THAT ONLY THOSE SHUTTERS REQUIRED FOR THE PARTICULAR
48 OPERATION BEING CARRIED OUT ARE OPENED.
49 15 MARSHALLING FACILITIES SHALL BE PROVIDED FOR ALL OF SIGNALS IN MOTOR CIRCUITS AND FEEDER CIRCUITS.
50 16 A COMPLETE SET OF ALL SPECIAL TOOLS AND DEVICES NECESSARY FOR THE OPERATION AND MAINTENANCE OF THE
51 SWITCHGEAR SHALL BE PROVIDED.
52 17 ALL MOTOR FEEDER COMPONENT RATING SELECTION SHALL BE AS PER AC-3 CO-ORDINATION IEC 60947-4-1.
53 18 CIRCUIT BREAKER OPERATING MECHANISMS OF INCOMING AND BUS COUPLER SHALL BE OF THE MOTOR/MANUAL SPRING
54 CHARGE, STORED ENERGY, MANUAL/ELECTRICAL RELEASE TYPE.
55 19 WITHDRAWABLE CIRCUIT BREAKERS SHALL BE INTERCHANGEABLE WITH OTHERS OF THE SAME VOLTAGE AND CURRENT RATING.
56 20 VOLTAGE AND CURRENT TRANSFORMERS SHALL BE DRY TYPE WITH EPOXY-RESIN/BUTYL RUBBER MOULDED INSULATION.
57
58
59
60
61
62
STAGE DETAIL DESIGN
PROVISION OF EPC SERVICE FOR FIELD
PROJECT CONTROL CENTER FOR MAJNOON DOC.NO. FOCP-FCC-CJI-EA-2015-0002
OPERATION CENTER PROJECT
PAGE NO. 7 OF 7

DOCUMENT DATA SHEET FOR LOW VOLTAGE MOTOR CONTROL CENTRE REV.: 003

MANUFACTURER: SERVICE: EQUIPMENT NO.: QTY:

DESIGAN LIFE: SIZE:


1
2 21 FEEDER NUMBER AND DETAILS REFER TO RELAVENT SINGLE LINE DIAGRAM.
3 22 LM MOTOR CUBICAL, TEST MODE FACILITIES WILL BE PROVIDED.
4 23 INCOMING FEEDER AND ALL OUTGOING FEEDERS SHALL BE ABLE TO LINK TO THE PMS SYSTEM BY MEANS OF
5 SERIAL LINK COMMUNICATION.
6 24 MOTOR FEEDER SWITCHGEAR SHALL BE AS PER TYPE-2 COORDINATION CHART.
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62

You might also like