ULTRA Series
SERVICE MANUAL
All manuals and user guides at all-guides.com
All manuals and user guides at all-guides.com
TECHNICAL ENQUIRIES
Please contact Pulsar Process Measurement Limited for technical support.
COMMENTS AND SUGGESTIONS
If you have any comments or suggestions about this product, then please contact:
CONTENTS
m
P358 Log Time ...................................................................................................................................... 30
Pump Control ................................................................................................................................................ 31
P194 – P199 Pumping Rate .................................................................................................................. 31
P359 Maximum Pumps (From Software Version 6.3 to 6.4.5............................................................ 31
.co
P361 – P362 Max Pumps on (groups 1 & 2) (From S/W ver. 6.7.3).................................................. 31
Totalisers........................................................................................................................................................ 32
P798 Max Flow Cut Off (From Soft Revision 6.4.2 (6.7.3 released))................................................ 32
Display ........................................................................................................................................................... 32
P817 Auxiliary Display Offset (From Soft Rev 6.5 (6.7.3 released)) ................................................. 32
Temperature Calibration ............................................................................................................................... 33
P855 – P856 External Temp Scale (From Soft Rev 6.6.9).................................................................. 33
P857 – P858 Temp Cal (transducer 1 – transducer 2) ......................................................................... 33
es
P859 Temp Average.............................................................................................................................. 33
Sound Velocity Calibration........................................................................................................................... 34
P861 – P862 Calibrate Distance (xdr1 – xdr2) (From S/W rev 6.8.0) ................................................ 34
Filters...................................................................................................................................................... 34
P102 Material......................................................................................................................................... 34
uid
The following parameters can only be accessed via the following passcode
552621 and can be used to modify the DATEM Echo Processing Algorithms in
particularly arduous applications.
Further parameters allow changes to parameters specific to communications and
other hardware functions.
Care and caution should be exercised when changing any of these parameters
and any such changes should only be undertaken by, or under the guidance, of
an experienced Service Engineer.
Direct Access.
In order to access parameters directly use the following procedure.
Some parameters are not part of the menu system and can only be accessed
directly. To do this use the cancel key until there are no digits in the main
display then key in the parameter number and press enter.
Page 1
All manuals and user guides at all-guides.com
Page 2
All manuals and user guides at all-guides.com
DATEM overview
Fig 1 (above) is a typical echo profile showing all four traces from the unit, the
gate is wrapped around the echo with the blue marker indicating the distance. The
signal strength is good and there are no competing echoes in front of the true
echo.
Page 3
All manuals and user guides at all-guides.com
The shaded left hand side of the screen shows the near blanking and the shaded
right hand part of the screen the ‘far blanking’ the ultra unit will measure 20%
further than its programmed empty distance as a factory setting, this is known as
‘far blanking’. The near blanking is the area just in front of the transducer where
measurement is not possible.
Page 4
All manuals and user guides at all-guides.com
Ringdown
Echo
Secondary
Echo
m
.co
es
The red trace is the echo signal return, the horizontal scale is distance to target in
metres and the vertical scale is signal strength return in millivolts. The echo
uid
above is approx 3.8m from the transducer and has signal strength of 480mv.
-g
all
Page 5
All manuals and user guides at all-guides.com
Page 6
All manuals and user guides at all-guides.com
Transducer 1 Parameters
Default = 0
Option Description
0 = Quit Leave P020 without any change to the present
DATEM trace.
1 = Capture DATEM trace of entire visible range taken and
all echo returns referenced out.
2 = Default DATEM trace will assume default value.
3 = Def Reset Default DATEM to factory settings.
4 = Set Min DATEM When set, DATEM levels at this point will be
accepted as a minimum.
Page 7
All manuals and user guides at all-guides.com
The echo profiles below show the effect of Capture, the ‘Gate’ has been removed
for clarity.
Fig. 1.
Empty tank, the unit will pick up on the first echo after initial switch on.
Fig. 2.
Empty tank after a Capture. Unit will show Loss of Echo.
Page 8
All manuals and user guides at all-guides.com
Fig. 3.
Echo profile after product has entered tank.
Default = 0.000
Page 9
All manuals and user guides at all-guides.com
Default = 4
Determines the number of times the transducer is “pinged” in each “shot”, during
every processing cycle. In applications where there is a high level of noise or
attenuation due to dust or angles of repose, increasing the number of “pings” may
result in a larger “Average” trace and thereby increase echo processing reliability.
It should be noted that when increasing the number of “pings” processing times
will increase slightly and when reducing the number of “pings” per “shot”
m
slightly faster processing times will be obtained.
Options: Enter the Number of “pings” required to be taken during each
processing cycle.
.co
Values: Min. 1
Max. 32
es
uid
-g
all
Page 10
All manuals and user guides at all-guides.com
Transducer 2 Parameters
These parameters are identical to those for transducer 1 and are used to carry out
the same functions on units and applications utilising a second transducer.
P030 Set DATEM 2
See P020
P031 Set Dist 2
See P021
See P024
Page 11
All manuals and user guides at all-guides.com
Page 12
All manuals and user guides at all-guides.com
Echo Control
Default = 0
This parameter sets some internal values to enable the unit to operate at a faster
speed.
Options
0 = No
1 = Yes
Notes:
By setting various other parameters to their appropriate value for a quick moving
application, you can further increase the response time of the instrument.
These could include:
P24 (number of pings) = 1
P43 (gain breakpoint) = 90
P45 (number of averages) = 1
P71 (update datem) = 0
P79 (gate) = 0
P870 (fill damping) = 99999
P871 (empty damping) = 99999
Care should be undertaken when changing the above parameters as they could
affect the stability of the reading if applied incorrectly. Only adjust when advised
by a Pulsar Engineer.
Page 13
All manuals and user guides at all-guides.com
This parameter sets the threshold level in milli-volts within the the ringdown area
of the transducer. The echo must exceed this threshold above the DATEM trace,
before it is recognised as a valid echo. Typically this value will be applied to the
first 0.5m in front of the transducer.
Values Min = 0.00
Max = 99.99
Default = 8
This parameter determines the rate at which data is transferred from the unit to
the PC Ultra display when receiving echo traces (regular echo = yes). A lower
figure gives increased definition but is slower and visa-versa. Please seek advice
from Pulsar before carrying out any adjustment.
Values Min = 1
Max = 32
P043 Breakpoint
Page 14
All manuals and user guides at all-guides.com
P044 Slope
m
Default = 3
.co
Number of processing cycles or transducer ‘shots’ that are averaged prior to
processing of the echo trace.
Values Min = 1
Max = 50
es
P047 Outside Count
Default = 10
uid
Values Min = 1
Max = 5000
all
Page 15
All manuals and user guides at all-guides.com
Default = 0
This parameter should only be used under the direction of Pulsar. If ‘ON’ the gate
will remain ‘locked’ on the selected echo, regardless of the presence of any other
sized echo outside the gate, unless the selected echo falls below the value of the
loss limit.
Options 0 = No
1 = Yes
Default = 40%
When P067 = 1 Best, this parameter determines the amount of weighting applied
to the first valid echo above the Loss Limits, before comparing it to other
competing echoes, the resulting largest echo will then be processed as the correct
echo.
Values Min = -100%
Max = 100%
Page 16
All manuals and user guides at all-guides.com
Draw / Inflow
The Pump Inflow and Pump Draw parameters are only used when the unit is set
up to calculate Pump Efficiency (available in Ultra 5 and Zenith units only).
Default = 0.00
This is a read only parameter that displays the calculated inflow rate in m/min.
Default = 0.00
This parameter is the calculated initial draw in m/min of a calibrated pump. If
required this value can be entered manually.
P152 Pump 2 Initial Draw
P153 Pump 3 Initial Draw
P154 Pump 4 Initial Draw
P155 Pump 5 Initial Draw
P156 Pump 6 Initial Draw
P157 Pump 7 Initial Draw
P158 Pump 8 Initial Draw
P159 Pump 9 Initial Draw
P160 Pump 10 Initial Draw
Page 17
All manuals and user guides at all-guides.com
Page 18
All manuals and user guides at all-guides.com
DATEM Flags
Default = 0.2
This parameter used in conjunction with P65, is designed to prevent the echo
‘jumping’ to a false echo that is further away when the echo enters into the near
blanking area. As the echo approaches to within 0.2m from the transducer
blanking area and is then ‘lost’ it will not jump to any echo that is further than
0.5m (near jump) away from the blanking. Thus preventing the unit from reading
a low value when it is submerged and possibly switching off pumps.
Default = 0.5
See above.
Note. With reference to the above two parameters see P080 Lost Lock
Default = 0
This parameter is used to determine which echo is selected for processing. When
set to zero the echo with largest valid peak is chosen, when set to 1 the First valid
echo will be selected unless a larger echo is present beyond the Jump Cut Off
point (P84).
N.B. In software versions up to 2.7.2 Jump Cut Off is P83
Page 19
All manuals and user guides at all-guides.com
Default = 1
m
3 = First
.co
Best
The first echo that appears above DATEM, plus the Loss Limit, will be weighted
according to the factor set in P049 Scale First (Default =40%) the peak then
chosen for processing will be the echo with the highest resulting peak after first
weighting has been applied.
es
Largest
The echo with the highest peak will be selected for processing, when this option
is chosen no weighting is applied to the first valid echo.
First
uid
When selected, the First valid echo will be selected regardless of any other echoes
that are present.
Default = 1
selected DATEM will be used but will not be adaptive and will remain at its last
known value. If 1 = Yes is selected DATEM will continually update to the
conditions seen in the vessel and eliminate any echo returns from unwanted
sources.
Options: 0 = No
1 = Yes
Page 20
All manuals and user guides at all-guides.com
Default = 1
Default = 1
This parameter determines if the Gate is used. If set to 0 = No, then there will be
no agitator control, P47 Outside Count and P48 Echo Lock will be disabled, the
unit will process valid echoes which appear above the Loss Limit and in
accordance with the setting of P67 (choose Peak).
Options: 0 = No
1 = Yes
Default = 0
This parameter switches on P64 & P65 near band and near jump. Which are not
yet enabled.
Options: 0 = No
1 = Yes
Page 21
All manuals and user guides at all-guides.com
Page 22
All manuals and user guides at all-guides.com
Ultra Sound
This parameter sets the Near “threshold” above DATEM which an echo must
exceed, before it is recognised as a valid echo. The value of this parameter can be
increased to assist in the elimination of unwanted signals or decreased to improve
sensitivity in order that attenuated signals can be validated and processed. The
Near Loss distance starts from the end of the Ringdown Loss to a distance set via
P83, with a default value of 2m.
Values: Min. 0.00
Max. 99.99
This parameter sets the value of the Far Loss in the same way as P81 Near Loss
but is applied to distances beyond the Loss Change (P83).
Values: Min. 0.00
Max. 99.99
Default = 2.0m
This parameter sets the distance that the Near Loss and Far Loss are applied to.
When set at 2m the Near Loss, as determined by P81, will be applied for a
distance of 2m from the face of the transducer and then will change to the value
determined by P82 Far Loss.
Values: Min. 0.300
Max. 99.999
Page 23
All manuals and user guides at all-guides.com
Default = 40.0m
This parameter determines the distance, from the face of the transducer, that the
unit will process the First valid echo, providing that a Larger echo is not seen
beyond this point.
Values: Min. 0.300
Max. 99.999
This Parameter now determines the height in milli-volts of the point where the
near loss becomes the far loss i.e. the loss change point (P083)
Page 24
All manuals and user guides at all-guides.com
Debug Level
This parameter is used to delay the time between each ping in order to prevent the
risk of a second ping interfering with the initial return echo and causing
problematic readings. It delays the time between each ping.
m
P087 Fail Time 2
Default = 1 min
.co
This parameter determines the time after an event, such as “Loss of Echo”, that a
warning message will appear in the Auxiliary line of the display.
Values: Min. 0.1 min
Max. 9999 min
es
P088 Hard Default
uid
Default = 0
P88 allows both User and Service parameters to be reset to their Factory Default
values.
N.B. P930 Factory Defaults will allow the user to reset only those parameters
which are accessible via the User Passcode (Default 1997), but will not reset any
-g
parameters which are accessed via the Service Code 552621. Thus ensuring any
adjustments carried out by Service personnel are protected.
Options:
all
0 = No
1 = Yes
Page 25
All manuals and user guides at all-guides.com
P99 allows the system type of the unit to be changed. It is only available by direct
access (see ‘about service parameters’).
N.B. This will change the system type of the unit and will perform the equivalent
of a P88 default for the new system type.
Options:
Page 26
All manuals and user guides at all-guides.com
DATEM Custom
Default = 0.25m
This parameter determines the Distance at which the DATEM trace will start, or
stand off, from the Ring Down.
P107
Blanking
Distance
Default = 700mv
This parameter determines the height at which the angle of the DATEM trace will
start.
P110 Middle
milli volts
Page 27
All manuals and user guides at all-guides.com
Default = 0.8m
This parameter determines the Distance at which the DATEM trace will fall to
the value of Sensitivity (P905 Xducer 1) and (P915 Xducer 2).
P111 End
Point metres
Default = 1
Page 28
All manuals and user guides at all-guides.com
The following three parameters are only available when the Tariff Guard feature
is enabled (on Zenith as standard).
P113 Rate Sampling (from Soft Revision 4.6.3.1 (5.7.8 released))
Default = 1
This parameter sets the rate calculation interval for Tariff Guard in seconds.
Default = 4
The array count averages the rate readings before processing, an application with
a very slow rate of rise may benefit from an increase in the value as it will give a
smoother rate value reading.
Default = 1.0
The rate validate will adjust the calculated time to overflow. Increasing the value
will have the effect of bringing the pumps on later and visa-versa. This parameter
should only be adjusted by Pulsar personnel when commissioning a Tariff Guard
application.
Page 29
All manuals and user guides at all-guides.com
Default = 0
To allow RS232 communication with the integrated comms processor. This must
be set remotely via Ultra PC or Windows Terminal. The parameter will
m
automatically revert back to 0 = No when the RJ11 cable has been removed and
“updating” has been displayed on the LCD.
Options: 0 = No
1 = Yes
Options: 0 = No
uid
1 = Yes
The unit has 10 daily totals that start and end at midnight. This parameter can be
all
used to alter the start time at which logging begins for the 24 hour period.
Page 30
All manuals and user guides at all-guides.com
Pump Control
Default = 1.0
This parameter is a simulation parameter in units of metres/min that sets the rate
of pumping for any pump assigned the appropriate relay whilst in test mode.
Default = 0
This parameter will restrict the number of pumps that will run regardless of the
number of pumps set in the unit and the level shown on the display. This can be
used to ensure if a rising main can only take so much flow the limit is not
accidentally exceeded.
P361 – P362 Max Pumps on (groups 1 & 2) (From S/W ver. 6.7.3)
Default = 0
This parameter will restrict the number of pumps that will run regardless of the
number of pumps set in the unit and the level shown on the display. This can be
used to ensure that if a rising main can only take a certain amount of flow, the
limit is not accidentally exceeded.
Page 31
All manuals and user guides at all-guides.com
Totalisers
P798 Max Flow Cut Off (From Soft Revision 6.4.2 (6.7.3 released))
Default = 4
This parameter can be set to inhibit the flow totalisers to a maximum value of
4 times the maximum flow rate. So for example with a max flow of 20 l/s, set in
the P705, the totaliser will be stop totalling the flow when it reaches 80 l/s or
higher.
Options: Min = 1
Max = 9
Display
P817 Auxiliary Display Offset (From Soft Rev 6.5 (6.7.3 released))
Default = 0m
This parameter will allow the Auxiliary display to be offset to an appropriate value
in system units. It can be used to ensure a more operator friendly reading is seen in
the auxiliary display.
Page 32
All manuals and user guides at all-guides.com
Temperature Calibration
Default = 4
The parameter decides the amount of temperature averages taken before the
temperature reading is displayed.
Options: Min = 1
Max = 8
Page 33
All manuals and user guides at all-guides.com
P861 – P862 Calibrate Distance (xdr1 – xdr2) (From S/W rev 6.8.0)
This parameter is used to calibrate the sound velocity using a known fixed distance.
Enter the correct distance from the face of the transducer to the target and the unit
will automatically calculate P860 (Sound Velocity) to suit.
First added in software version 6.5.3 (closest released version 6.7.3) but doesn’t
change the sound velocity, it adds an offset to the measurement.
Filters
P102 Material.
Closed Tank = 3 when selected this will default certain parameters to values
more suitable for this type of application, please see Application 1, Enclosed
Tank for more details.
Default = 0
This parameter determines the operation of the gate that is established around the
processed echo and is used to track the echoes movement and update the display.
If set to Fixed (P880 = 0) then the width of the gate is determined by the value of
P881 Fixed Dist. When set to Calculated (P880=1) then the gate width is
automatically calculated and updated according to the values of P870 (fill
damping) P871 (empty damping), P874 (Rate Update), P875 (Rate Time), and
P876 (Rate Distance), see user manual for further details.
Page 34
All manuals and user guides at all-guides.com
Default = 0.2m
This parameter is used to set the width of the gate either side of the echo
measurement point (blue vertical line in Ultra PC) when P880 (Gate Mode) is set
to 0 = Fixed. The total gate width will be a maximum of twice this value.
m
0.4m
.co
es
uid
-g
all
Page 35
All manuals and user guides at all-guides.com
Default = 3
Determines the rate of process filtering. Setting to fast increases the response of the
unit but will also show more discrepancies or ‘spikes’ as the filtering is less
intensive. Changes the speed of unit response to level changes.
3 = Slow (P45 = 3)
Page 36
All manuals and user guides at all-guides.com
Default = 50
This parameter is used if you choose a solids application, P102 (Material) = 2
(Solids), where there may be angles of repose on the material. It can be used to
choose the point at which the measurement is taken within the returned echo.
The light blue line in the middle of the gate is the measurement point for the
unit. For liquid applications this occurs on the most vertical part of the leading
edge as the surface is generally quite flat giving an accurate measurement. For
solids applications the blue line appears in the centre of the echo as this is the
average point for a sloping surface, accuracy can vary on a sloping surface
depending on the ‘angle of repose’ of the material being measured.
Page 37
All manuals and user guides at all-guides.com
Reform
Note* This parameter is only available in versions 7.0.6 onwards and adjustments
should only be made when using PC Ultra to view echo traces.
You are advised to seek advice directly, from Pulsar, before making any changes.
P050 = Reform
Default = 0 (off) Options = 0 = Filter off
1 = Yes (Reform Filter On)
Page 38
All manuals and user guides at all-guides.com
It is recommended that if you do not change this parameter without the aid of Ultra
PC to observe the effect your parameter changes are having on the echo profile. If
echoes go under the line they will not be seen by the unit.
Sensitivity Line
Page 39
All manuals and user guides at all-guides.com
Default = 0.05m
This parameter sets the distance by which the yellow DATEM trace will be
separated from the red trace as the DATEM trace passes around an echo returned
from an obstruction.
m
.co
es
uid
-g
all
Page 40
All manuals and user guides at all-guides.com
Remote Communicator
Default = 1
This parameter determines whether or not an IR remote communicator needs to be
shown to the front of the unit before it can be used. Replaces P089 Kiss Enable.
Options:
0 = No
1 = Yes
P089 Kiss Enable (From Software Revision 6.4.1 to 6.9.1)
Default = 1
The kiss enabled parameter allows the unit to be accessed via a remote infra-red
communicator.
Options:
0 = No
1 = Yes
Page 41
All manuals and user guides at all-guides.com
Applications
This section of the manual deals with more difficult applications. And, service
parameters that may need changing under certain process conditions in order to
have the unit work to an acceptable level.
In order to apply these parameters correctly the user should have a good working
knowledge of Pulsar equipment.
Pulsar PC software should always be used to monitor the echo profile and record
the effect that the parameter changes are having.
2. Liquid applications in wet wells where the empty distance is close to the
end of the range of the transducer and the surface may be turbulent and/or
foamy.
3. Solids applications where the process is fast moving and the control is
required to be nearly instantaneous, i.e. crusher control.
4. Solids applications where the process is much slower moving and the
product surface may have difficult angles of repose, i.e. bulk solids silos.
Page 42
All manuals and user guides at all-guides.com
This could be the case in a liquid vessel with a domed top that can re-focus a
secondary echo magnifying it to a height that could cause problems. See
below.
If this is the case you may find the unit reading a level that is twice the actual
distance.
Software Version 7.1.8 0nwards, simply enter the programme Mode and go to
P102 (Material) and select option 3 = Closed Tank, the following parameters will
then be set, automatically, to the values detailed below:
Software Versions prior to 7.1.8 will need to have the following parameters
changed manually.
To manually change, enter the service code (552621) and change the following
parameters.
Page 43
All manuals and user guides at all-guides.com
P44 = Slope. Change to 0. This is the gain level parameter, changing it to zero
ensure that there is no gain applied anywhere on the echo profile. Thus reducing
the chance of larger multiples.
P47 = Outside Count. Change to 25. This is the parameter that controls the
movement of the gate. Increasing the value make the movement of the gate to
another echo that is further away less likely.
P49 = Scale First. Change to 50%. This parameter increases the amount of
‘weighting’ the unit will apply to the first echo increasing it makes the echo less
likely to go to a multiple.
P108 = Far End Blanking. Change to 5%. Reducing this value shortens the
effective range of the instrument giving less room for a multiple to appear within
the measured distance (+ far end blanking).
P871 = Empty Damping . Set the value to just above the max rate of emptying.
If the unit does decide to go to a multiple it will do so at the damping rate thus
giving the unit time to recover the true echo before the unit shows a large reading
change.
Page 44
All manuals and user guides at all-guides.com
m
.co
es
uid
When the level in a wet well gets low the surface can become less reflective for
ultrasound, there are several reasons for this.
The surface is further away, and, can become agitated due to the pumping action,
the inflow to the wet well falls further and so becomes more spread out leading to
increased surface movement and foam on the surface, in extreme instances the
noise of the falling water can lead to the transducer picking up acoustic noise
-g
from the well itself. The spread of the falling water can interfere with the beam
angle.
The solids matter and debris at the bottom of the well can be disturbed leading to
all
a more uneven surface, also, the benching can become exposed which is not a
good surface to reflect off.
Page 45
All manuals and user guides at all-guides.com
Enter the service code (552621) and change the following parameters.
P43 = Breakpoint. Change to a value that will enable you to apply gain to the
real echo whilst avoiding applying gain to a false echo (e.g. pump heads).
P44 = Slope. Change to a value that will enable the true echo to be
distinguishable from any other echoes.
Note: Care should be taken when employing the above two parameters, too much
gain may cause the unit to go to a multiple if the level in the well goes high. Also,
the gain is only a software multiplier it does not increase the raw signal strength.
If the echo is disappearing the transducer needs to be moved to a better position
or upgraded.
P47 = Outside Count. Change to 25. This is the parameter that controls the
movement of the gate. Increasing the value makes the movement of the gate to
another echo that is closer to the transducer less likely.
P82 = Far Loss. Change to 1. This enables smaller echoes to be ‘seen’ at the end
of the units programmed empty distance.
P870 = Fill Damping . Set the value to just above the max rate of filling. If the
unit does decide to go to a closer echo it will do so at the damping rate thus
giving the unit time to recover the true echo before the unit shows a large reading
change.
P871 = Empty Damping . Set the value to just above the max rate of emptying.
If the unit does decide to go to a multiple it will do so at the damping rate thus
giving the unit time to recover the true echo before the unit shows a large reading
change.
Page 46
All manuals and user guides at all-guides.com
For crusher control the unit needs to work at high speed to ensure that the bowl
does not overfill, the transducer needs to be positioned so that it avoids the inflow
to the bowl and is not liable to get damaged.
Page 47
All manuals and user guides at all-guides.com
Enter the service code (552621) and change the following parameters.
P44 = Breakpoint = 90. Changing this parameter will ensure no gain is applied
to the echo saving processing time.
Now Change the following parameters these are not adjusted by choosing Solids
in P102 or Fast Response in P882.
P67 = Echo Algorithm = 2 = Largest. The unit will measure on the largest echo
seen above the loss limit Threshhold.
P79 = Use Gate = 0. Not using the gate means that the unit will measure on the
largest echo seen above the loss limit Threshhold that is within the entire length
of the range. Ensuring that the level can be followed it if moves very quickly, and
might normally move outside the measuring window.
P870 = Fill Damping = 99999. Setting the empty and fill damping parameters to
the maximum value will mean the unit effectively has no measurement damping.
P20 enter 2 (Default Datem) This must be the last thing you do after entering
the above parameters.
Page 48
All manuals and user guides at all-guides.com
There are many potential problems associated with solids level monitoring in
Silos, depending on the type of material, the method of filling/emptying, the
varying process conditions and the customer expectations.
Changing the parameters as listed below is an endeavour to get a ‘best fit’ for
most applications but if in doubt contact your Pulsar representative for further
advice.
Page 49
All manuals and user guides at all-guides.com
Enter the service code (552621) and change the following parameters.
Now Change the following parameters these are not adjusted by choosing Solids
in P102.
m
P43 = Breakpoint. Change to a value that will enable you to apply gain to the
real echo whilst avoiding applying gain to a false echo.
.co
P44 = Slope. Change to a value that will enable the true echo to be
distinguishable from any other echoes.
Note: Care should be taken when employing the above two parameters, we are
attempting to increase signal size towards the bottom of the silo, (within the cone)
es
to make the measurement more reliable. The gain is only a software multiplier it
does not increase the raw signal strength.
If the echo is disappearing the transducer needs to be moved to a better position
or upgraded.
uid
P47 = Outside Count. Change to 25. This is the parameter that controls the
movement of the gate. Increasing the value makes the movement of the gate to a
false echo less likely.
P67 = Echo Algorithm = 2 = Largest. The unit will measure on the largest echo
-g
P870 = Fill Damping = ????. Set the value to just above the max rate of filling. If
the unit does decide to go to a closer echo it will do so at the damping rate thus
all
giving the unit time to recover the true echo before the unit shows a large reading
change.
P871 = Empty Damping = ????. Set the value to just above the max rate of
emptying. If the unit does decide to go to a multiple it will do so at the damping
rate thus giving the unit time to recover the true echo before the unit shows a
large reading change.
Page 50
All manuals and user guides at all-guides.com
Example.
The DATEM trace has been shaped around some close in noise and extended
outwards from the ringdown area, the unit is measuring the larger of two echoes
seen at the bottom of the application.
You can see from the above example that the loss limit values have been reset,
this is to enable the unit to pick up smaller echoes when the silo is filling and
picking up the echo is difficult, these parameters are application dependant and
should be used with the commission engineers discretion.
P809 = Failsafe Timer = ????. This value should be increased to suit the
application, for example, if the silo is filled from a tanker and this takes 45mins
then the failsafe timer should reflect the time taken to fill the silo and for the
reading to be re-established before going into a failed safe mode.
P906 = Side Clearance = ????. This parameter should be used as detailed in this
manual when the silos has obstructions between the transducer and the product,
prior to switching DATEM off as detailed below.
Page 51
All manuals and user guides at all-guides.com
P71 = Update Datem = 0. We are generally looking for the largest echo above
the loss limit thresholds so datem is not needed in most applications, if the silo
has obstructions then it should be emptied and Datem should be allowed to shape
around the false echoes before being switched off.
Page 52
All manuals and user guides at all-guides.com
Fault Finding
Initial Checks.
Check that the unit has been wired correctly, care must be taken to ensure that the
mains voltage and the transducer cables are connected in the right place.
Before initial switch on, the unit should be checked that it is set for the correct
voltage. If the unit is set for 110vac and is supplied 240vac then switching the unit
on may well damage the unit to an extent where it will need to be send back for
repair. If the unit is set for 240vac (which is how they leave Pulsar) and supplied
110vac then the unit may appear to work and display the correct distance (if the
product is close enough) but the relays will not operate and the unit will go LOE
when the level moves further away from the transducer.
Check that the transducer has been installed in the correct position and has a clear
as possible shot at the target, make sure any protective transit covering has been
removed.
If you are programming the unit for the first time or re-commissioning the unit it
would be good practice to default the unit back to factory settings so the instrument
would be as it was when it left here, (once you do this all your programmed
parameters will be lost).
If you are happy with the distance reading the unit is showing you can now program
your unit.
Page 53
All manuals and user guides at all-guides.com
No Xducer, Xducer Fault, L.O.E. or Failed Safe. Then we need to check the
transducer voltages and wiring.
Transducer
Cable Extension
Cable
18-24VDC
Transducer 5-7VDC
0VDC
Unit
Junction
Box
Shield
Twisted
Shielded Pair
The voltages shown above should be present at the unit and the junction box if
one is used.
The voltages come from the control unit to the transducer, the return signal is
current based and difficult to check in the field.
First remove the cable from the unit and check the voltages are there at the
terminals, use the manual for the particular type of unit you have to establish the
correct terminals.
If the voltages are ok without the cables attached but change when the wires are
connected then you have a wiring problem, connecting the wires incorrectly or
shorting them out should not damage the transducer. Often the transducer
extension cables are not the same colour as so the voltages need to be check at the
local junction box to ensure they are there and connected correctly.
Page 54
All manuals and user guides at all-guides.com
The 18-24 vdc (power) supply should be connected to the red cable coming from
the transducer.
The 5-7 vdc (signal) should be connected to the white cable coming from the
transducer.
The 0 vdc supply should be connected to the Black & Green cables coming from
the transducer.
The transducer will not operate correctly below 18vdc so on long cable runs the
extension cable should be of a sufficient size/quality to ensure this is the case.
m
If we are certain the unit is operational and working correctly, but not reading the
right level or distance then we need to follow the P21 procedure as listed below in
.co
order to obtain the correct reading.
The unit has unique DATEM (Digital Adaptive Tracking of Echo Movement)
software that can cover false echoes whilst maintaining a fix on the true echo.
The software will then adapt to any changes to the echo profile in front of the
moving target enabling Pulsar to keep the correct reading under constantly
es
changing process conditions.
In order to initially cover all the false echoes we need to get the level in the
application to its lowest measuring point and then tell the control unit where the
true echo is, it will then mask out all the false echoes in between the transducer
uid
Before starting this procedure you will need to establish the distance between the
-g
face of the transducer and the measured surface to within approx 10cm.
Key in the passcode 1997 (four dashes will appear in the display) and press
all
enter.
Display will show ‘wait’ then after a few seconds ‘Quick Set-up’.
Key in 21 and press enter.
Display shows 0.000 & Set Dist 1. Or ( Sel Peak) on some older units.
Key in the distance from the transducer face to the product (within 20cm)
and press enter.
Display shows ‘Capturing’ then after a few seconds ‘Enter If Sure’ press
enter.
Page 55
All manuals and user guides at all-guides.com
Display shows ‘ Setting’ then ‘Set’ then after a few seconds ‘System’.
Press ‘Cancel’ display will show ‘Run Mode’.
Press enter.
Display shows ‘Wait’ then after a few seconds the correct reading.
If the space between the transducer and the product is particularly cluttered and
the above procedure does not work initially you may try again until the unit is
reading correctly.
The above process and the Pulsar software is excellent at reading the correct echo
under difficult conditions, however it is still good practice to install the transducer
in the optimum position within the application.
If the unit is still not reading go to the self test parameter P990 and enter 1, the
unit should respond with – Clock ok, Eeprom ok.
If the self test responds with a failure, or, is ok but the unit is still not operational
then you should contact Pulsar for further assistance.
Page 56