CEILING LEGEND TO SPRINKLER SYSTEM


TOR
AIR DEVICE OR
LIGHT FIXTURE GRV'D BELL
WIRE TO FIRE
SPEAKER OR ALARM PANEL
MC

Approved By: MC
SC

EQ EQ EQ EQ OTHER DEVICE PER NFPA 72


Checked By:

SPRINKLER SPARE

EQ
Drawn By:

EQ
SPRINKLERS
HYDRAULIC NAMEPLATE FOR
CABINET FLOW
SPARE SPRINKLERS CABINET THE MOST DEMANDING AREA

EQ

EQ
SWITCH
- A SUPPLY OF AT LEAST 6 SPARE SPRINKLERS SHALL BE
MAINTAINED ON THE PREMISES. A MINIMUM OF TWO ELECTRIC BELL GreshamSmith.com
SPRINKLERS OF EACH TYPE AND TEMPERATURE (OUTSIDE)
RATING SHOULD BE PROVIDED. GRV'D SWING
- THE STOCK OF SPARE SPRINKLERS SHALL INCLUDE CHECK VALVE
EQ EQ EQ EQ EQ EQ ALL TYPES AND RATINGS INSTALLED AND SHALL BE AS
FOLLOWS: GRV'D TEE Two Harbour Place
GRV'D ELL 302 Knights Run Avenue

EQ

EQ

EQ
* FOR PROTECTED FACILITIES HAVING: 8
1. UNDER 300 SPRINKLERS - MINIMUM 6 SPRINKLERS. Tampa, FL 33602
2. 300 TO 1000 SPRINKLERS - MINIMUM 12 SPRINKLERS. Suite 900

EQ

EQ

EQ
GRV'D RISER CHECK VALVE
3. OVER 1000 SPRINKLERS - MINIMUM 24 SPRINKLERS WITH 2" MAIN DRAIN & 1/4" 813-251-6838
GAUGE
GRV'D BUTTERFLY VALVE WITH FIRM'S FLORIDA CERT. NO.
TAMPER SWITCH AAP000034/CA3806
GRV'D CONCEN. REDUCER IB26000797/LC26000381
7 2 x 0-0 GALV. THRU WALL TO 2"
AMES IN-BUILDING RISER GALV 45. ABOVE GROUND WITH
SPRINKLERS IN GRID CEILING SYSTEMS SHALL BE LOCATED AT THE SUPPLY TO FDC OR
BOR SPLASH BOX.
MIDPOINT OR QUARTERPOINT OF THE FOUR FOOT (4') DIMENSION AND THE EQUAL
MIDPOINT OF THE TWO FOOT (2') DIMENSION. WHERE A CONFLICT OCCURS, AMES IN-BUILDING RISER (OR
SYMMETRY ABOUT THE AXIS SHALL BE MAINTAINED. EQUAL) SPRINKLER SYSTEM
SUPPLY

SPRINKLER MOUNTING FIRE RISER 9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
TEL (813) 995-0300 FLORIDA EB# 0027845
WWW.EMERALDMEP.COM

CORED HOLE FOR


FIREFILL CERAMIC
MASONRY WALLS SYSTEM RISER
FIBER

CEILING OR WALL
PROSEAL PLUG SPRINKLER CAST IRON FLANGE
AND SPIGOT PIECE

CERAMIC FIREFILL
20 GA. SPLIT WALL
SLEEVE TWO (2) INCH HIGH BLACK
LETTERING HELVETICA REGULAR
POURED OR SIMILAR STYLE. REPEAT
IN PLACE EVERY 6'-0" MAX. AROUND
STEEL SLEEVE PERIMETER OF STORAGE ROOM
FOR AND AT LEAST ONCE ON EACH FIRE SERVICE
WALL. MAIN
GYPSUM WALLS FIRESTOP COUPLING 18"

Jacksonville 8-bed Hospital


OSHA YELLOW STRIPE TO RUN
CONTINUOUSLY AROUND
PERIMETER OF ROOM AS
INDICATED. OMIT DOORS AND
WINDOWS.

SLEEVES & FIRESTOPPING CAST IRON BELL

23/960187
AND SIGN PIPE
USE PROSET "FIRESTOP PENETRATORS," U.L. CLASSIFIED IN THE BUILDING MATERIALS
DIRECTORY, TESTED BY ASTM E814. USE ALL APPLICABLE PIPE PENETRATIONS THROUGH

Beach Blvd & Kernan Blvd, Jacksonville, Florida


FIRE RATED WALLS OR FLOOR CEILING ASSEMBLIES IN ACCORDANCE WITH THE MANU- NO STORAGE ABOVE THIS LINE 4" RODS

101
FACTURERS INSTRUCTIONS.

Construction Documents
Florida AHCA Client Code / File No.:
Florida AHCA Project Submission No.:
FIRE RATED WALL SLEEVING SYSTEM STORAGE LIMITS LINE CONNECTION TO FIRE PROTECTION SYSTEM RISER

BRANCH TAKE-OFF FROM


BRASS UPRIGHT SPRINKLER TOP OF PIPE WITH SWING
JOINT
TEST/DRAIN LINE

12" x 12" x 3-1/2" DEEP RECESSED HANGER ROD TO


CABINET: 16 GA. BOX W/14 GA. TYPE 304 STRUCTURE
STAINLESS STEEL DOOR, PIANO HINGE,
CYLINDER LOCK EQUAL TO KARP #KRVB.
PAINT TO MATCH ADJACENT SURFACE.
GATE VALVE (N.C.) 1" x 1/2" REDUCER HANGER WITHIN 12"
OF SPRINKLER DROP
TEST/DRAIN ASSEMBLY: BALL VALVE WITH W/ UPLIFT RESTRAINT
RESTRICTED ORIFICE EQUAL TO FLOW OF
INSPECTORS ONE SPRINKLER HEAD AND SIGHT GLASS.
TEST
SIGNAGE ON OUTSIDE OF DOOR. 1" RISE NIPPLE SPRINKLER BRANCH
6'-6" MAX.

1" TEST/DRAIN LINE IN WALL


THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED
1" DROP NIPPLE
EXTERIOR BUILDING WALL HANGER ROD TO BY MICHAEL A. COSTELLO, PE USING A DIGITAL SIGNATURE
AND DATE. PRINTED COPIES OF THIS DOCUMENT ARE NOT
STRUCTURE CONSIDERED SIGNED AND SEALED AND THE SIGNATURE MUST
CHROME ESCUTCHEON PLATE BE VERIFIED ON ANY ELECTRONIC COPIES.
WITH SET SCREW
1" x 1/2" REDUCER
1" DISCHARGE @ 45° ANGLE HANGER WITHIN 3"
OF SPRINKLER CONCEALED SPRINKLER
PRECAST CONCRETE W/ SPLIT
12' SPLASHBLOCK
MAX. RESTRAINTS
Digitally signed by
CEILING Michael Costello
SPRINKLER BRANCH
CN=Michael Costello,
O=Michael Costello,
L=Tampa, S=Florida,
C=US

PROVIDE WITH HEAD GUARD AS REQUIRED.


OFF-WHITE COVER PLATE
ALL REQUIRED EXPOSED INSPECTOR'S TEST DRAIN ASSEMBLY LOCATION SHALL BE FULLY FLUSH WITH CEILING
COORDINATED WITH ARCHITECT. CONTRACTOR SHALL OBTAIN AN APPROVAL FROM
ARCHITECT PRIOR ITS INSTALLATION. MICHAEL A. COSTELLO
FL REG. NO. PE 81436
INSPECTOR'S TEST DRAIN TYPICAL UPRIGHT SPRINKLER TYPICAL CONCEALED SPRINKLER

CONCRETE
HANGER REQUIREMENTS Revision
STRUCTURAL INSERT
MEMBER (RED HEAD) 1. ON BRANCH LINES, THERE SHALL
BE NOT LESS THAN ONE HANGER FOR BRANCH TAKE-OFF FROM No. Date Description
EACH LENGTH OF PIPE. TOP OF PIPE WITH SWING
JOINT
2. THE DISTANCE BETWEEN THE
HANGER AND CENTERLINE OF AN
CONCRETE
UPRIGHT SPRINKLER SHALL NOT BE LESS
STRUCTURE THAN THREE INCHES (3"0.
TOP BEAM HANGER ROD TO
ROD ROD
CLAMP(ANVIL STAR STRUCTURE
3. THE UNSUPPORTED LENGTH
Autodesk Docs://MP_NUTEX HEALTH R22/45671.00 Mech.rvt

FIG. 92)
HANGER RING BETWEEN THE END SPRINKLER AND THE
HANGER RING (ANVIL STAR LAST HANGER SHALL BE NOT MORE THAN
(ANVIL STAR FIG. 69) 36 INCHES FOR 1-INCH PIPE, OR 48
INCHES FRO 1-1/4" PIPE AND 60 INCHES
HANGER WITHIN 12"
FIG. 69)
PIPE FOR 1-1/2" PIPE AND LARGER. WHEN OF SPRINKLER DROP
PIPE THESE LIMITS ARE EXCEEDED, THE PIPE W/ UP LIFT RESTRAINT
SHALL BE EXTENDED BEYOND THE END
SPRINKLER AND SUPPORTED BY AN
ADDITIONAL HANGER.

4. HANGERS ARE NOT REQUIRED ON


ONE INCH (1") ARM-OVERS LESS THAN
TWENTY-FOUR INCHES (24") LONG.

STRUCTURAL
MEMBER 1" DROP NIPPLE

TOP BEAM 1" x 1/2" REDUCER


CLAMP
ALL THREAD
ROD HANGER SPACING FOR
STEEL FIRE SPRINKLER PIPING
PIPE SIZE MAX. SUPPORT SPACING CEILING
1" 40 12'-0"
1-1/4" 40 12'-0"
1-1/2" 40 15'-0"
ANGLE IRON 2" 40
2-1/2" 10
15'-0"
15'-0"
DETAILS
TOP BEAM LOCKNUT & WASHER 3" 10 15'-0"
CLAMP(ANVIL STAR 4" 10 15'-0" PENDENT SPRINKLER
FIG. 92) 6" 10 15'-0"
WITH RECESSED
8/10/2022 2:24:33 PM

RING(ANVIL STAR FIG. 69) * INFORMATION PER :


1/2" THREADED

F501
NFPA 13 2013 - CHAPTER 9 ESCUTCHEON
ROD
PIPE MAX. DISTANCE BETWEEN HANGERS

HANGERS TYPICAL RECESSED SPRINKLER


45671.00
08.10.2022
This Line is 3 Inches When Printed Full Size