03 - Parametri Controler - Apetrei

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

Unitat

Setări
ea de Setări
Parametru Min Max modificat Descriere
măsu implicite
e
ra
ELECTRICAL PARAMETERS GROUP
Current
Se va seta valoare curentului din
Transformer
A 1 5000 500 .... primarul transformatoarelor de
Primary
curent
Mains Voltage Low
V-
Limit % V+100 V-20% V-10%
100
Mains Voltage High
V-
Limit % V+100 V+20% V+10%
100
Genset Overcurrent
Se va seta curentul nominal al
Limit A 0 50000 0 ....
generatorului
Genset Overcurrent
0: shutdown alarm
Action - 0 3 0 0
1: loaddump alarm
Genset Voltage Fail
sec 0 10 1 3
Timer
Genset Frequency
sec 0 10 1 3
Fail Timer
Low Battery
12V = 6
Voltage Warning V-DC 5.0 35.0 12
24V = 12
Limit
Low Battery
12V = 4
Voltage Shutdown V-DC 5.0 35.0 9
24V = 9
Limit
High Battery
12V = 14.5
Voltage Warning V-DC 5.0 35.0 29
24V = 29
Limit
High Battery
12V = 15
Voltage Shutdown V-DC 5.0 35.0 30
24V = 30
Limit
Battery Voltage Fail
sec 0 120 3 60
Timer
This is the connection topology of
mains voltages and CTs.
0: 2 phase, 3 wire L1-L2
1: 2 phase, 3 wire L1-L3
Mains Connection
2: 3 phase, 3 wire
Topology - 0 7 5 5
3: 3 phase, 3 wire, 2CTs L1-L2
4: 3 phase, 3 wire, 2CTs L1-L3
5: 3 phase, 4 wire star
6: 3 phase, 4 wire delta
7: single phase, 2 wire
This is the connection topology of
genset voltages and CTs.
0: 2 phase, 3 wire L1-L2
1: 2 phase, 3 wire L1-L3
Genset Connection
2: 3 phase, 3 wire
Topology - 0 7 5 5
3: 3 phase, 3 wire, 2CTs L1-L2
4: 3 phase, 3 wire, 2CTs L1-L3
5: 3 phase, 4 wire star
6: 3 phase, 4 wire delta
7: single phase, 2 wire
ENGINE PARAMETERS GROUP
Stop Solenoid
sec 0 90 10 15
Timer
Cooldown Timer sec 0 600 120 30

DIGITAL INPUT
Input
- 0 99 2 2 2:Low Oil Press. Switch
Function
0: shutdown alarm
1: loaddump alarm
Action - 0 3 0 0
2: warning
3: no fault condition from this input.
0: always
1: on engine running
Sampling - 0 3 2 2
2: after hold-off timer
3: reserved
0: non-latching. The fault disappears
DI
when cause is removed.
1
Latching - 0 1 1 1 1: latching. The fault persists even if
the cause is removed. Requires
manual reset.
0: Normally open
Contact type - 0 1 0 1
1: Normally closed
0: Battery negative
Switching - 0 1 0 0
1: Battery positive
0: No delay
Response 1: Delayed (1sec)
- 0 3 1 1
delay 2: Delayed (10sec)
3: Delayed (1800sec)
Input
- 0 99 6 6 6: Emergency Stop
Function
0: shutdown alarm
1: loaddump alarm
Action - 0 3 0 0
2: warning
3: no fault condition from this input.
0: always
1: on engine running
Sampling - 0 3 0 0
2: after hold-off timer
3: reserved
0: non-latching. The fault disappears
DI
when cause is removed.
3
Latching - 0 1 0 1 1: latching. The fault persists even if
the cause is removed. Requires
manual reset.
0: Normally open
Contact type - 0 1 1 1
1: Normally closed
0: Battery negative
Switching - 0 1 0 0
1: Battery positive
0: No delay
Response 1: Delayed (1sec)
- 0 3 0 0
delay 2: Delayed (10sec)
3: Delayed (1800sec)