FIRE RATED DUCT COATING
WINDUCT® - FIRE RATED DUCTWORK SPECIFICATION
All fire rated ductwork system should be tested to BS 476 Part 24 for external
fire exposure (Duct A) and internal fire exposure (Duct B) for 120 minutes
stability, integrity, and insulation respectively. Fire test should be conducted
as per ISO standard fire curve (ISO 834).
Provide integral fire resisting supports for fire rated ductworks; support
system should be located at a maximum of 1500mm centers.
Hanger and bearers shall be designed to limit stress 10N/mm2 for 120
minutes fire rating.
Gaskets & Sealants: Any airtight gaskets can be used; WinCoat™ paint can
be used in place of fire sealant – as tested and approved by IFC.
Insulation: 100mm thick rockwool with 120Kg density for 120 minutes
insulation. (Optional based on project requirement)
Installation / Workmanship
All surface of the fabricated ductwork shall be clean from all stain, oil and
glue etc before applying the WinCoat™ intumescent paint.
All finished ductworks shall be checked visually to ensure that they are fully
completed together with all TDC joint and clip in place and WinCoat™
intumescent paint coated.