ELECTRICAL SAFETY
BS EN 60950
The module can be easily Safety of Information Technology Equipment,
The TemTransfer 3 is an Various timing sequences are including Electrical Business Equipment
Automatic Transfer Switch available to prevent nuisance configured using the Configuration
Controller. The TemTransfer 3 will starting on minor supply breaks. Suite PC Software. Selected front TEMPERATURE
BS EN 60068-2-1
monitor the voltage and frequency panel editing is also available. Ab/Ae Cold Test -30 oC
of the incoming AC supply from The TemTransfer 3 supports many BS EN 60068-2-2
Configurable inputs and outputs Bb/Be Dry Heat +70 oC
two different sources, which could topologies and features include
be from both generator or mains mains (utility) rated volt-free relays, make the TemTransfer 3 fully VIBRATION
(utility), or a combination a clear back-lit LCD 4-line text flexible to suit a wide variety of BS EN 60068-2-6
Ten sweeps in each of three
of both. The module will monitor S1 display, showing system status and applications. major axes
(source 1) and in the event of a warnings and red and green LEDs 5 Hz to 8 Hz @ +/-7.5 mm,
When there is no DC supply, a 8 Hz to 500 Hz @ 2 gn
failure will issue a start command to indicating operational status.
S2 (source 2). compatible self-seeking power HUMIDITY
The module includes USB, RS232 supply is available (DSE160). BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 oC
Once S2 is available and producing and RS485 ports. @ 95% RH 48 Hours
an output within limits, the module BS EN 60068-2-78
will control the transfer device and
switch the load from S1 to S2. Cab Damp Heat Static 40 oC
@ 93% RH 48 Hours
Once the S1 supply returns to
within limits, the module will SHOCK
command a load return to S1 BS EN 60068-2-27
Three shocks in each of three major axes
and shut down S2. 15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
OTHER
S1 SENSING N/C VOLT FREE OUTPUT LOAD CURRENT N/O VOLT FREE OUTPUT S2 SENSING
VOLTS VOLTS
ISSUE 1
TemTransfer 3 SPECIFICATION
DC SUPPLY
AUTO TRANSFER SWITCH CONTROL MODULE CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
S1
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS A & E
Normally closed volt-free output
8 A AC at 250 V AC
OUTPUTS B & F
Normally open volt-free output
8 A AC at 250 V AC
OUTPUT C & D
Changeover volt-free output
8 A AC at 250 V AC
KEY FEATURES • Backed up real time clock • Configuration Suite PC AUXILIARY OUTPUTS G,H,I,J,K & L
• Configurable inputs (12) • Fully configurable via Software compatability for 2 A DC at supply voltage
• Configurable volt-free outputs (6) Configuration Suite PC software remote control and monitoring S2
• Configurable DC outputs (6) • Configurable display languages • 132 x 64 pixel ratio display for VOLTAGE RANGE
• 4-Line back-lit LCD text display • User selectable RS232 and clarity 15 V to 333 V AC (L-N)
• Five key menu navigation RS485 communications • Real-time clock provides FREQUENCY RANGE
• Front panel editing with PIN • Configurable Gencomm pages accurate event logging 3.5 Hz to 75 Hz
protection • Ethernet communications
DIMENSIONS
• LED and LCD alarm indication (additional option) provides OVERALL
• Check sync feature KEY BENEFITS advanced remote monitoring at 240 mm x 181 mm x 42 mm
• Remote monitoring • Source 1/Source 2 provides low cost 9.4” x 7.1” x 1.6”
• Source 1/Source 2 control total flexibility for the • Modules can be integrated into PANEL CUT-OUT
• Start inhibit application of the product building management systems 220 mm x 160 mm
• Load inhibit • Fully automatic and switch-over (BMS) 8.7” x 6.3”
• Manual restore to S1 control minimises the effects of • Licence-free PC software MAXIMUM PANEL THICKNESS
• Supports multiple topologies power disruptions • IP65 rating (with supplied 8 mm
• Automatic switch-over between • User friendly set-up and button gasket) offers increased 0.3”
supplies layout resistance to water ingress STORAGE TEMPERATURE RANGE
• Rotary ATS configuration • 3 phase display and check sync • PLC editor allows user -40 oC to +85 oC
• Configurable timers and alarms provide enhanced module configurable functions to meet
• Multiple date and time scheduler functionality specific application
• Power monitoring (kW h, kV Ar, requirements
kV A h, kV Ar h)
• Load switching (load shedding
outputs)
• USB connectivity
Terasaki maintains a policy of continuous development and reserves the right to change the details
shown on this data sheet without prior notice. The contents are intended for guidance only.
TT 3 2013