Professional Documents
Culture Documents
1vap701071 DB - PSH 993
1vap701071 DB - PSH 993
1vap701071 DB - PSH 993
Type PSH-993
Indoor/outdoor current transformer
Application
The PSH-993 indoor/outdoor, window-type current transformer
is a 600 volt, 10 kV BIL rated unit. This unit can be applied
over higher rated system voltages provided sufficient insulation
is available on the point of application. Primary current
ratios are available from 50:5 to 12000:5 at 60 Hertz, with a
rating factor of up to 4.0. This unit is ideal for old electrical
substation equipment with no internal space for bushing current
transformers. This dry-type, solid-cast current transformer will
operate with high accuracy for metering or relay applications.
Mechanical description
The core and coil assembly is wound and encapsulated in a
molded cast resin with various window sizes from 5" up to
14". The secondary terminals are ¼"-20 copper studs with
associated hardware. An optional removable terminal box with
two (2) 1" NPT conduit hubs can be provided for outdoor use.
Accuracy performance
The PSH-993 can provide 0.3 class accuracy for metering
with burdens of B-0.1 up to B-1.8, and up to C800 for some
relay applications (see ratings specific to each ratio). Upon
request, 0.15 class metering accuracy is available with burdens
of B-0.1 up to B-1.8 (see ratings specific to each ratio). The
transformer is accurate through its rating factor, and can be
used continuously to this level.
Mounting
The PSH-993 is designed for mounting in the upright position
only. Open end slots are provided on the aluminum base.
Testing
This unit can be tested to all applicable IEEE, CSA, or IEC
standards as requested.
Options
The PSH-993 is available with a secondary terminal box for
outdoor use. The unit is offered in single, dual, or multiple
core designs. Through careful calculation, steel selection, and
testing, existing current transformer characteristics can be
matched. Existing characteristic curves are required. Contact
factory for other needs.
Selection guide
Digits 13-14
Accuracy
Digits 6-7 Digits 9-11
Height Ratio Relaying: Metering (0.3 type) Non-5A secondary:
Digits 1-3 02 = C25 01 = B-0.1 01 = 2.5 VA
52 = 5.25" 500 = 50 102 = 1000
(Fixed) 22 = 2.25" 05 = C50 02 = B-0.2 02 = 5 VA
55 = 5.50" 750 = 75 122 = 1200
25 = 2.50" 10 = C100 05 = B-0.5 05 = 12.5 VA
PSH-993 57 = 5.75" 101 = 100 103 = 10000
37 = 3.75" 20 = C200 09 = B-0.9 10 = 25 VA
85 = 8.50" 151 = 150 123 = 12000
18" fixed O.D 40 = 4.00" 40 = C400 18 = B-1.8 20 = 50VA
42 = 4.25" 87 = 8.75" 201 = 200
80 = C800
PSH
H1
N/P
X1 X2 X3 X4 X5 DIM A HT
14.0 [356]
0.88 X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5
15.75 [400] [22]
TYP. Dual core winding diagram
18.0 [457] MAX
6.75 [171] H1
X1 X2 Y1 Y2 Z1 Z2
Three core winding diagram
Note:
Note: metric dimensions are displayed in [mm]. The information contained in this document is for general information purposes
only. While ABB strives to keep the information up to date and correct, it makes
no representations or warranties of any kind, express or implied, about the
ID (in.) [mm] HT (in.) [mm] Dim A (in.) [mm]
completeness, accuracy, reliability, suitability, or availability with respect to the
5.0 to 14.0 4.0 [102] 2.5 [64] information, products, services, or related graphics contained in the document for
[127 to 355] 5.5 [140] 4.0 [102] any purpose. Any reliance placed on such information is therefore strictly at your
own risk. ABB reserves the right to discontinue any product or service at any time.
H1
Copyright 2012 ABB.
All rights reserved.
X1 X2 X3 X4 X5
Single core winding diagram