Object Flags

Flags indicate conditions or attributes of the reported data value. Table of Contents (/reference/
XX/help/373161C-01)
Applicable Object Flags
Data Point Applicable Object Flags (Binary Form) NI-Industrial Communicati
API 2.0 for LabVIEW Help
Binary Output 00000001: ONLINE
00000010: RESTART Edition Date: September 20
00000100: COMM_LOST
Part Number: 373161C-01
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED »View Product Info
00100000: Reserved, always 0 (http://sine.ni.com/nips/cd
01000000: Reserved, always 0 Download Help (Wind
10000000: STATE (http://www.ni.com/pd
Binary Input 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: CHATTER_FILTER
01000000: Reserved, always 0
10000000: STATE
Double Binary Input 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: CHATTER_FILTER
11000000: DOUBLE_BIT_STATE
Binary Counter 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: ROLLOVER
01000000: DISCONTINUITY
10000000: Reserved, always 0
Frozen Counter 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: ROLLOVER
01000000: DISCONTINUITY
10000000: Reserved, always 0
Analog Output 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: OVER_RANGE
01000000: REFERENCE_ERR
10000000: Reserved, always 0
Analog Input 00000001: ONLINE
00000010: RESTART
00000100: COMM_LOST
00001000: REMOTE_FORCED
00010000: LOCAL_FORCED
00100000: OVER_RANGE
01000000: REFERENCE_ERR
10000000: Reserved, always 0
Este sitio utiliza cookies para ofrecerle una mejor experiencia de búsqueda. Conozca nuestra política de privacidad.
(http://www.ni.com/legal/privacy/unitedstates/us/)
Functional Description
Refer to the latest DNP3 specification for detailed explanations.

Name Functional Description

http://zone.ni.com/reference/en-XX/help/373161C-01/nidnp3/objectflags/ 1/3
8/9/2018 Object Flags - NI-Industrial Communications for DNP3 API for LabVIEW Help - National Instruments

ONLINE (00000001) The point is inactive if this bit is clear.


RESTART Indicates that the point has not been updated from the field since device restarts.
(00000010)
COMM_LOST The bit indicates the communication between the device where the data originates and the
(00000100) reporting device is lost.
REMOTE_FORCED Indicates that either the REMOTE_FORCED or LOCAL_FORCED flags are set in some object
(00001000) received from a downstream device for this non-originating device.
LOCAL_FORCED The device is operating in some mode so the device overrides the reported data value locally.
(00010000)
CHATTER_FILTER The single-bit binary input or double-bit input is changing between states at a very high rate to
(00100000) report a chatter filter.
ROLLOVER The flag is obsolete and is listed here for historical reasons only.
(00100000)
OVER_RANGE If set, the data point's true value exceeds its valid measurement range.
(00100000)
DISCONTINUITY If set, you cannot compare the reported value against a previous value to gain the correct count
(01000000) difference.
REFERENCE_ERR Indicates that the measurement process determined that the data value may not be at the
(01000000) expected accuracy level.
STATE (10000000) The flag's state indicates the single-bit (double-bit) binary input or output point data value.
DOUBLE_BIT_STATE
(11000000)

WAS THIS ARTICLE HELPFUL?

Helpful Not Helpful

 

PRODUCTOS SOPORTE COMPAÑÍA

Estado del pedido e historial Enviar una solicitud de servicio Sobre sucursal de National Instruments
(http://www.ni.com/status/) (https://sine.ni.com/srm/app/myServiceRequests) (http://www.ni.com/company/esa/)

Comprar por número de parte Manuales (http://www.ni.com/manuals/esa/) Sobre sucursal de National Instruments
(http://sine.ni.com/apps/utf8/nios.store? Latin America
Controladores
action=purchase_form) (http://latam.ni.com/compania)
(http://www.ni.com/downloads/drivers/esa/)
Activar un producto Eventos (http://www.ni.com/es-
Alliance Partners
(http://sine.ni.com/myproducts/app/main.xhtml? cr/events.html)
(http://www.ni.com/alliance/esa/)
lang=en)
Carreras (http://www.ni.com/careers/)
Información de compra y pago
Comuníquese con NI
(http://www.ni.com/how-to-buy/esa/)
(http://www.ni.com/contact-us/)

AVANZANDO JUNTOS
NI prepara a ingenieros y científicos para que
resuelvan los desafíos de un mundo cada vez más
complejo.

(https://www.facebook.com/NationalInstruments)

(http://twitter.com/niglobal)
Este sitio utiliza cookies para ofrecerle una mejor experiencia de búsqueda. Conozca nuestra política de privacidad.
(http://www.ni.com/legal/privacy/unitedstates/us/)
(http://nifeeds.ni.com/f/news-es)

(http://www.youtube.com/nilatinoamerica)

http://zone.ni.com/reference/en-XX/help/373161C-01/nidnp3/objectflags/ 2/3
8/9/2018 Object Flags - NI-Industrial Communications for DNP3 API for LabVIEW Help - National Instruments

(http://linkedin.com/company/national-

instruments)

Legal | (http://www.ni.com/legal/) Privacidad (http://www.ni.com/legal/privacy/es/) | © 2018 National Instruments Corporation. Argentina 

Todos los derechos reservados.

Este sitio utiliza cookies para ofrecerle una mejor experiencia de búsqueda. Conozca nuestra política de privacidad.
(http://www.ni.com/legal/privacy/unitedstates/us/)

http://zone.ni.com/reference/en-XX/help/373161C-01/nidnp3/objectflags/ 3/3

You might also like