The document provides earth resistance values from various standards for different electrical equipment and installations. In general, the standards specify lower earth resistance values for equipment requiring higher levels of protection such as generating stations, substations, and electronic equipment. Earth resistance values should not exceed 1 ohm for most critical equipment, with some standards allowing up to 5 ohms for industrial installations and 10 ohms for conventional signaling equipment. Higher values of up to 25 ohms are permitted by some standards for single electrodes or when additional electrodes are added to reduce the overall earth resistance.
The document provides earth resistance values from various standards for different electrical equipment and installations. In general, the standards specify lower earth resistance values for equipment requiring higher levels of protection such as generating stations, substations, and electronic equipment. Earth resistance values should not exceed 1 ohm for most critical equipment, with some standards allowing up to 5 ohms for industrial installations and 10 ohms for conventional signaling equipment. Higher values of up to 25 ohms are permitted by some standards for single electrodes or when additional electrodes are added to reduce the overall earth resistance.
The document provides earth resistance values from various standards for different electrical equipment and installations. In general, the standards specify lower earth resistance values for equipment requiring higher levels of protection such as generating stations, substations, and electronic equipment. Earth resistance values should not exceed 1 ohm for most critical equipment, with some standards allowing up to 5 ohms for industrial installations and 10 ohms for conventional signaling equipment. Higher values of up to 25 ohms are permitted by some standards for single electrodes or when additional electrodes are added to reduce the overall earth resistance.
b) EHT Sub-station 1.0 ohms c) 33 KV Stations 2.0 ohms d) D/t Structure 5.0 ohms e) Tower Foot resistance 10.0 ohms IEEE STANDARD 142 Chapter: 4.1.3 , page 164 For industrial plant substations and buildings and large commercial 1Ω to 5 Ω installations. Resistances of less than 1 ohm may be obtained using a number of individual electrodes connected together. Such a low resistance is only required for large substations, transmission lines, or generating stations. National Electric code (NEC) 2011, (IS SP30 Chapter 14 -India) Chapter: 3.0.9 unless otherwise specified ,It is recommended that the value of any earth 5Ω system resistance shall not be more than IS 3043 (India) Chapter: 22.2.3 The continuity resistance of the earth return path through the earth grid should be maintained as low as possible and in no 1Ω case greater than This applicable for main earth grid connected with the transformer/return path Oil Industry Safety Directorate Government of India (OISD STANDARD – 137) Chapter: (7. ii. b) Allowable earth-Resistance Values Allowable earth-Resistance Values The resistance value of an earthing system to general mass of the earth should not exceed. For electrical systems and metallic structures. 4Ω For storage tanks. 7Ω for main earth grid, and bonding connections between joints in pipelines 1Ω and associated facilities. for each electrode to the general mass of the earth 2Ω
IS 2309 (india) / BS 7430:1998
Clause:12.3.1 Page 32,Resistance to Earth Lightning arrestors ground resistance for Protection of buildings and allied 10Ω structures is An earth electrode should be connected to each down conductor. Each of these earths should have a resistance not exceeding the product given by 10 a multiplied by the number of earth electrodes to be provided. The whole of the lightning protective system, including any ring earth, should have a combined resistance to earth not exceeding 10 Ω without taking account of any bonding. If the value obtained for the whole of the lightning protective systems exceeds 10 Ω, a reduction can be achieved by extending or adding to the electrodes or by interconnecting the individual earth terminations of the down conductors by a conductor installed below ground, sometimes referred to as a ring conductor IS 2689:1989 Table 4 page 28 (Reaffirmed March 2010) Lightning arrestors ground resistance for Protection of buildings and allied 10Ω structures is NEC 250.56 Clause: 250.53 Grounding Electrode System Installation. The maximum resistance for a single electrode consisting of a rod, pipe, or 25Ω plate. If a higher resistance is obtained for a single electrode, a second electrode of any of the types specified in the NEC is required. This should not be interpreted to mean that 25 ohm is a satisfactory resistance value for a grounding system. IEEE Std 80-2000 (Revision of IEEE Std 80-1986) the evaluation of ground resistance for the most transmission and other large substations, the ground resistance is 1Ω or less usually about In smaller distribution substations, the usually acceptable range is 1Ω to 5Ω
NFC 17-102, July 1995
that the resistance value measured using conventional equipment should be 1Ω or less This resistance should be measured on the earthing termination insulated from any other conductive component. IEC 62305-1 edition 2.0 – 2010-12 the conventional earthing impedance related to the earth termination system is (*for the soil resistivity less than or equal 4Ω to 100 Ω) Ministry of Railways- Government of India
The acceptable Earth Resistance at earth MEEB bus bar shall not be more than 1Ω For achieving this value more than one earth pits can be installed if necessary depending upon the soil resistivity. In places where space is not available to provide parallel earth pits then longer earth rods may be provided. The longer earth rods thus provided should be in multiples of three meters. The combined resistance of the earthing system shall be not more than the following values Traction substation 0.5Ω Switching station 2Ω Booster transformer station 10Ω Auxiliary transformer station 10Ω Maximum values of earth resistances specified for earthing of Signaling and Telecommunication equipment’s are as under Telegraph and Block Instrument using earth return circuit 10 Ω Earths for surge arrestors/ lightening dischargers 10Ω Earthing of Signalling equipment 10Ω Earthing of signalling cable screen in AC electrified areas 10Ω Earthing of Telephone Exchange 5Ω Earthing of aluminum sheathed telecom cable in AC electrified area 1Ω Earthing of equipment in VF repeater stations and cable huts. 5Ω Axle counter cable screened in AC electrified area 1Ω Electronic Interlocking installation 1Ω Integrated Power Supply System & its individual modules 2Ω Digital Axle Counter EJB and its apparatus case connected to same earth 1Ω All cable armors connected to same earth. Reset box of Digital Axle Counter connected to earth (indoor) near SM’s 1Ω Room. Railway Vikas Nigam Limited RVNL/Elect/GS/11 The earth continuity test of metallic envelopes shall be done for electrical continuity. Electrical resistance of the same, along with the earthing lead, excluding any added resistance of earth 1Ω leakage circuit breaker, measured from the connection with the earth electrode to any point in the earth conductor in the completed installation, shall not exceed No earth electrode shall have resistance greater than 5Ω In rocky soil, the resistance may be up to 8Ω Locations having more than one electrode shall be connected in parallel to reduce the resistance. MANUAL OF STANDARDS & SPECIFICATIONS FOR RAILWAY ELECTRIFICATION RDSO/SPN/197/2008 Equipment’s with solid state components which are more susceptible to damage due to surges, transients and over voltages being encountered in the system due to lightning, sub-station switching such as 1Ω Electronic Interlocking, Integrated Power supply equipment, Digital Axle counter, Data logger etc. shall Value of earth resistance shall not be more than For conventional signaling equipment’s the earth resistance shall not be more than 10Ω
DHASHIN HARYANA BIJALI VITRAN NIGAM
(DHBVN) Specification no CSC-140 / DH/UH/P&D Hose hold Earthing (3KA) <8Ω Commercial / Industrial Buildings (5KA) <2Ω Transformer / LT Line Earthing (15KA) 1Ω to 2Ω Transformer / Substation /HT Line ,HT Switchgear (40KA) <1Ω Lighting Arrester /Extra High Current appliances (50KA) <1Ω UPS / Data center / ATM <0.5 Ω *Earthing may be Single or Multiple Electrode. Earthing Value Earthing Condition Earthing Value Best 0.1Ω to 2Ω Good 2.1Ω to 5Ω Need to be Maintenance 5.1Ω to 10Ω Need to be Replacement >10Ω