ACTRON CONNECT MODULE

INSTALLATION & COMMISSIONING GUIDE

ActronConnect Module
ACM-1

Please Read This Guide


Congratulations on your purchase of an
ActronConnect Module. This unit has been
designed and manufactured with the highest
quality standard in mind.

Please read this guide thoroughly and keep it


in a safe place for future reference.

Copyright © 2013 Actron Engineering Pty. Ltd. All rights reserved.


This manual is a controlled document which contains confidential and proprietary information.
Distribution, modification, copying and/or reproduction are prohibited without written consent from ActronAir.
TABLE OF CONTENTS
ITEMS TO CONSIDER
Introduction .................................................................... 3
Kit Contents List ............................................................ 3 • Carefully unpack the ActronConnect Module from its
Items to Consider .......................................................... 3 packaging and ensure that all parts are included.
Safety Instructions ......................................................... 3 • Fully check the contents of your ActronConnect
Codes, Regulations & Standards .................................. 3 Module kit against the content list upon receiving
Specifications ................................................................ 4 your shipment. Inspect the module, components and
accessories for any sign of shipping damage. If there
Installation Instructions
is any damage to the contents, contact ActronAir
Power Supply Installation Procedures ........................... 5 Customer Care Department immediately on:
ActronConnect Module Installation Procedures ............ 8 1300 135 995.
Requirements for ACM Optimum Signal Performance... 9
• Make certain that the ActronConnect module is
Commissioning Instructions
compatible with the ActronAir air conditioning system
ActronConnect Commissioning ..................................... 12 you plan to install it on. (See FAQs about the product).
Wiring Diagram .............................................................. 20
• Take time to thoroughly read the installation &
commissioning instructions before proceeding with the
installation.

INTRODUCTION
SAFETY INSTRUCTIONS
CONGRATULATIONS on your purchase of an
ActronConnect Module! This has been designed and
Safety instructions and warnings provided on this
engineered to give you total control of your ActronAir
installation manual are in-exhaustive and given as
ducted air conditioner, whether you are at home or
a guide only. Prevailing WH&S regulations must
away. By using either the ActronConnect App on your
be observed and will take precedence to the safety
Apple iOS devise or through supported web browsers
instructions contained in this manual. Safe work
from any smart phone, tablet or PC / Mac, you can now
practices and environment must be of paramount
monitor and control your air conditioner from wherever
importance in the performance of all service
you have internet connectivity.
procedures.
The procedures outlined in this guide are provided • Ensure that all safety work procedures & Instructions
to correctly & safely install the ActronConnect are adhered to at all times in order to prevent personal
Module (ACM) to an appropriate ActronAir ducted air injury or damage to the equipment.
conditioning system. Failure to follow these procedures
may result in personal injury, damage to the air • Only licensed service persons are allowed to perform
conditioner, damage to the ActronConnect module or the procedures described in this manual.
incorrect operation of the air conditioning system. Such • The indoor (evaporator) unit electrical panel has
failure could render your warranty null and void. 230VAC electrical components inside. PLEASE
ISOLATE THE INCOMING POWER SUPPLY BEFORE
COMMENCING WORK. Supply can be isolated at the
Main Isolator located near the Air Conditioner (if fitted)
KIT CONTENTS LIST or at the Main Supply Circuit Breaker in the Distribution
Board supplying the Air Conditioner. Correct Lock Out
1 Pc - ActronConnect Wi-Fi Module & Tag Out procedures should be followed to ensure
(ActronAir Part No. ACM-1) Power Supply is not re-energized accidently.
1 Pc - ActronConnect Antenna • The ActronConnect Module is IP20 Rated - NOT
1 Pc - Power Supply pre-wired with FOR OUTDOOR USE. Install your ACM away from
Power & Data cables - Sold as Spare Part Kit excessive dust, heat and moisture.
(ActronAir Part No. 2020-200K)
1 Pc - Adhesive Back Wiring Diagram label • The ActronConnect Module is not a toy, keep away
(ActronAir Document No. WD0904) from children and ensure that they are not allowed to
1 Pc - Installation & Commissioning Guide play or tamper with the device.
(ActronAir Document No. 9590-1000) • The air conditioning electrical panel & the Actron
1 Pc - Quick Start Guide Connect module / kit contain static sensitive electronic
1 Pc - Double Sided Tape (50 x 30 x 2mm) components. Careful handling & correct anti-static
2 Pcs - M3 x 4mm Pan Head Screws procedures must be followed to prevent damage of the
2 Pcs - #6 x 30mm Pan Head Needle Point Screws equipment. Failure to protect the electronic components
1 Pc - Shipping Carton from static electricity may cause unrepairable damage,
which is NOT COVERED for replacement under
Warranty.

2 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
• The instructions herein refer to work involving a Computer CPU
Chip & Electronic CPU Board, please ensure all Instructions are
followed accurately so as to prevent damage to these fragile & delicate
components.

CODES, REGULATIONS & STANDARDS

The installer and/or contractor assumes responsibility to ensure that


ActronConnect Module installation and commissioning comply with the
relevant council, state / federal codes, regulations and building code
standards. All electrical wiring must be in accordance with current
electrical authority regulations and all wiring connections to be as
per electrical diagram provided with the unit.

SPECIFICATIONS

ActronConnect Module Part No. ACM-1


Wi-Fi Protocol 802.11b/g/n
Operating System Requirement IOS 6.1.3 or later version
Security Protocol Web-128, WPA-PSK, WPA2-PSK
Hardware Voltage 9VDC - 15 VDC
Max. Operating Temperature 60oC
IP Rating IP20
Max Cable Length from ACM to
10 metres
Power Supply Kit
Access Point Distance * 15 metres
Wi-Fi Range 70m line of sight
* The maximum distance that can be established between ACM and mobile device
(i.e. iphone, ipad, laptop) if the mobile device is acting as an access point.

Power Supply Part No. 2020-200K


Output Ratings 12VDC 1.3A 15.6W
Input Ratings 85~264VAC 120~370VDC
- Frequency Range 47~63Hz
- Inrush Current Cold Start 65A / 230VAC
- Efficiency (Typical) 81%
- AC Current (Typical) 0.35A / 115VAC
0.25A / 230VAC
Working Temperature -20~+70oC
Working Humidity 20-90% RH
non-condensing
Overload Protection Above 105% Rated Power
O/L Protection Type Hiccup mode, auto recovery after
fault condition is removed
Over Voltage Protection 13.8-16.2V
O/V Protection Type Shut-Off o/p voltage, clamping by
zener diode

3 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
INSTALLATION INSTRUCTIONS

1.0 ActronConnect Power Supply & Module Installation Procedures:

1.1 Power Supply Installation Procedures:


Step 1.1.1. Isolate electrical power to the air conditioner at isolator or main switchboard.

Step 1.1.2. Remove lid from indoor unit electrical panel.

Lid- Electrical
Panel

Indoor Unit

Step 1.1.3. Mount the ActronConnect power supply kit, using either of the two options below, to the base of
the electrical panel as shown below:

Option 1 (Using the 2x4mm M3 screws):

“PLUG C” (RJ45 Data) & Cable


to ActronConnect Module

Power Supply Kit


(Pre-wired Supplied) Ensure that the earth ring terminal is pointing towards
the right side (looking at the electrical panel)

Ensure the power supply ventilation


holes are NOT covered by the excess
cables or other foreign matter.
2x4mm M3
Mounting Screws

NOTE: Use mounting screws when holes


are existing in Electrical Panel base.

Option 2 (Using the Double Sided Tape):

“PLUG C” (RJ45 Data) & Cable


to ActronConnect Module

Power Supply Kit


(Pre-wired Supplied) Ensure that the earth ring terminal is pointing towards
the right side (looking at the electrical panel)

Ensure the power supply ventilation


holes are NOT covered by the excess
cables or other foreign matter.

Double Sided
Tape NOTES: Use double sided tape where there are no holes in the Electrical Panel base.
Make sure that the base of the electrical panel and the power supply are
clean and free of dirt or dust in order to provide a strong tape adhesion.

4 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 1.1.4. Refer to the wiring diagram for the cable connections on pages 29 - 33.

Step 1.1.5A. Step 1.1.5B.


(Classic, ESP Plus & ESP Platinum Plus Models) (ESP Ultima & ESP Platinum Ultima Only)

“PLUG A” P1
2 Pin Power 2 Pin Socket
Connector Ultima Power
Auxiliary Power Connector
Socket

“PLUG A” 2 Pin Power


Connector

P1
2 Pin Socket

Connect “PLUG A” (2 Pin Power Connector) for the Unplug Ultima 2 Pin Power Connector from “P1”
230VAC of the power supply into the corresponding and connect “PLUG A” as in Step 5A above.
2 Pin Socket labelled “P1 (240VAC)” on the Indoor Then, plug the Ultima power connector into the
PCB AMIB. (This plug only goes in one way, ensure auxiliary power socket.
it is in correct orientation before pushing it all the
way in).

Step 1.1.6. Connect “EARTH RING LUG” to the earthing bolt of the indoor unit electrical panel. Unscrew
the nut, remove the washer & slide the EARTH RING LUG over the bolt making sure all of the existing
earthing lugs remain connected. Replace earthing washer & nut and tighten the nut securely.

Earthing Bolt
& Washer

Existing
Earth Wires

ACM
Earth Wire

Step 1.1.7. Connect “PLUG B” (4 Pin JST) for the data of ActronAir Connect Module into the
corresponding 4 Pin Socket labelled “J4 DATA” on the Indoor PCB AMIB. (This plug only goes in one
way, ensure it is in correct orientation before pushing it all the way in).

Indoor ACM
PCB AMIB “PLUG B”
(4 Pin JST)

J4 DATA
(4 Pin Socket)
DATA

DATA

5 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 1.1.8. Take the “PLUG C” (RJ45 Data) for the ActronConnect Module & run it out from the indoor
electrical panel via the large cable gland on the right side of the electrical panel. Feed the data cable all
of the way out so that only a minimum cable length remains inside the panel. Using cable ties, secure the
cable to the electrical panel and into the zone cables exiting from the same cable gland.

Run the ACM data


cable out from the
electrical panel

Large
Cable Gland

NOTE: For optimum performance & module communication integrity, keep the ActronConnect
Module data cable as far as possible from the 230VAC mains.

Step 1.1.9. Take the wiring diagram with adhesive back, peel off adhesive protection strip & stick the wiring
diagram unto the front the electrical panel lid.

Wiring Diagram Electrical Panel

Indoor Unit

Lid- Electrical
Panel

Step 1.1.10. Check all connections and screw lid back onto indoor electrical panel.

6 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
1.2 ActronConnect Module Installation Procedures:
IMPORTANT NOTE: ActronConnect Module CANNOT be installed on the sheet metal
part of the indoor unit (particularly at the top) as the performance & integrity of the
wireless signal will be greatly reduced.

Step 1.2.1. Install the ActronConnect Module to a suitable secure location, like a roof joist or similar using
the supplied screws. Keep the module at least 0.5m away from the roof line and 1m from the indoor
unit, large metal objects or other sources of interference (e.g. antennas, exhaust fans, duct work, etc.).
Also ensure it is kept away from potential sources of dust, heat & moisture (i.e. light fixtures, heaters,
bathroom exhaust fan outlets, etc.)

Install the ActronConnect Module 0.5m


Do Not Install the ActronConnect away (or greater) from the roof line.
Module on top of the indoor unit

ActronConnect Module
Roof 0.5
m> Manhole

Indoor Unit A

1m> See notes 3 & 4 for


Return ActronConnect Module
Air Grille location requirements.
w.i.r

Install the ActronConnect Module 1m


away (or greater) from the Indoor unit .

ACTRONCONNECT MODULE INSTALLATION DIAGRAM

ActronConnect Roof Joist


Module

Securely run cables along the roof


joist and at least 300mm away from Secure the ActronConnect
any other installed cable (i.e. power, Module to the roof joist using
lights, PC data, TV antenna, etc.) the supplied screws.

DETAIL - “A”

NOTES:
1. Maximum Allowable Cable Length between the indoor unit and the ActronConnect module is 10m. This can be
achieved with the use of a 2-Way Joiner PN: 2045-121 (Sold Separately) and a 7m ACM extension cable PN: 4070-027
(Sold Separately). The Actron Power Supply kit comes pre-wired with 3m cable. Do not run ACM cable in parallel with the
240V power supply cable and keep 300mm minimum distance from other cables (mains, data, antenna, etc).
2. DO NOT USE Actron CAT5E zone cables to extend ACM cables.
3. Locate the ActronConnect Module as close as possible to the ceiling and the manhole for ease of access, ensuring that
LED is facing towards the manhole and that the roof insulation does not come into contact with the module.
4. Do not install ActronConnect Module in roof cavities where temperature can exceed 60oC. In the event where you require
to install the Actron Connect Module below the ceiling line (Eg. Storage cabinet), please ensure you use an appropriate
plastic enclosure (supplied by others) that complies with all relevant safety codes, regulations and standards.

7 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Requirements for ActronConnect Module Optimum Signal Performance:
The ACM optimum signal performance depends on the mounting orientation of the unit and the positioning of the
antenna in relation to the Wi-Fi router.

Mounting Orientation
As much as possible, install the module in a direct line of sight with the router and keep the antennas parallel.

BEST ACCEPTABLE POOR WORST

Location / Positioning
Do not locate the module where the signal will be blocked by any large metal, concrete structure or objects
with high water content. People, animals and plants are composed mostly of water. Make sure that these do
not interfere with the module signal. Maintain at least 0.5m distance between the ACM & router antennas.
Avoid getting the antenna in direct contact with any metal or near power supply.

NO BLOCKING OBJECTS ALLOWED

Typical Home Installation Examples:

Single Level Dwelling


As much as possible, install the ACM
with the antenna parallel and in direct
line of sight with the router antenna

Two Level or Multi-Level Dwelling

As much as possible, install the


ACM with the antenna parallel
and in direct line of sight with
the router antenna.

8 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 1.2.2. Do not place the ActronConnect module where it can be easily damaged by accidentally
stepping on it or where it can be covered by ceiling insulation.

Step 1.2.3. Refer to the module mounting diagram - Requirements for ACM Optimum Signal Performance,
for the best mounting direction of the module based on your particular installation requirement.

Step 1.2.4. Refer to the wiring diagram for the cable connections on pages 29 - 33.

Step 1.2.5. Take the ActronConnect module 3m Grey Data Cable running from the indoor electrical panel
& run it to the installed module, ensuring it is in a position where it cannot be easily damaged and it is at
least 300mm away from any other installed cables (i.e. power, lights, PC data, TV antenna, etc.). If it is
impossible to avoid running the ACM data cable close to the other cables, run it across the other cables
at 90 degree (do not run in parallel).

3m ACM
Data Cable from the
Indoor Unit

ActronConnect
Module

Run the ACM data


cable from the Indoor
Unit to the ACM

Step 1.2.6. Secure the 3m Grey Data Cable to the timber roof joist or similar with the cable ties or other
suitable cable fixing fasteners. Do not loop any excess cable in a tight loop. Leave it loose.

NOT RECOMMENDED RECOMMENDED

RUN data cable as straight


Do NOT loop excess cable and short as possible

Strong possibility of communication problems. No electro-magnetic interference.


The “loops” can cause an electro-magnetic Keep communication cable at least 300mm
interference, upsetting data communication. from high voltage cables.

9 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 1.2.7. Connect “PLUG C” (RJ45 Data Plug) into ACM “Socket C” (labelled communication to indoor
board). This plug only goes in one way, ensure it is in correct orientation before pushing it all the way to
“lock” it in. Ensure there is an adequate slack on the cable so that no undue strain is placed on the RJ45
plug. Then screw Antenna into ACM socket and align as per instructions on Appendix A - Requirements
for ACM Optimum Signal Performance.

Antenna ACM
Data Socket

Label - ACM
Data Socket

Antenna

“PLUG C”
(RJ45 Data Plug)

ACM
ACM ACM Data Socket
Antenna Socket Data Socket

Step 1.2.8. Check all connections & cables to ensure correct connections and cables are secured properly.

Step 1.2.9. Power-up the air conditioner by turning-On the main isolator or at the Main Supply Circuit
Breaker in the Distribution Board. Ensure that the air conditioner powers up and operates correctly.

Step 1.2.10. Perform ActronConnect Module commissioning.

10 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
COMMISSIONING INSTRUCTIONS

2.0 ActronConnect Commissioning


Ensure that your home Wi-Fi network is switched-on and there is power to your air conditioner
before setting up your ActronConnect system,

Step 2.1. Download the ActronConnect “App” from the Apple app store.

Step 2.2. Open the “App” in order to create your account with ActronAir.

11 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 2.3. Create your ActronAir account by touching the “no account? create one” icon.

Step 2.4. Terms & Conditions* page will appear, read through it and accept:

* Visit www.actronair.com.au/privacy for


the updated Privacy Policy.

SCROLL DOWN
to read the
Terms & Conditions
and Accept

NOTE:
• Ensure that you read the Terms &
Conditions and if you are happy, press
“Accept” to proceed with commissioning.

12 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 2.5. Fill-in the details in the required fields of the registration page (i.e. your email address, password
& post code). Note: You may also enter your details on the optional fields to help troubleshooting in the
event you need to contact our Technical Support team in the future.

NOTE:
• You can chose any password, which is not necessarily the one you use for your email
access. It is also advisable to create a different password for your ActronConnect
account, for your extra security.

Step 2.6. Set up your air conditioning type & number of zones. Then press the “next” button and the
“Welcome” page will appear. Close the “App”.

4
Do not press “next”

13 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 2.7. Now close the ActronConnect “App” and go to your iOS device (iphone, ipad, ipod etc...)
“Setting” menu, click on “Wi-Fi” and search for Wi-Fi connection:

NOTE:
• You may need to Turn-On your Wi-Fi, if it is Turned-Off.

Step 2.8. Select the “ActronConnect” Wi-Fi network for your air conditioner:

NOTE:
• You are now connected to ActronConnect network.
• You must be within 15 meters between the installed
ActronConnect Module and the configuration device
(iphone, ipod, PC...), to ensure optimum communication
signals.

14 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
IMPORTANT INFORMATION ON iOS 7 AND LATER VERSIONS

Wi-Fi signal

wait for approximate


1 minute

IMPORTANT:
iOS 6 - the Wi-Fi signal ( ) will appear almost instantaneous after
selecting ActronConnect in the list of Network.
iOS 7 and later - wait for the Wi-Fi signal ( ) to appear (approximately
1 minute). If it hasn’t appear for 1 minute, continue with
the set up process.

Step 2.9. After establishing your air conditioner’s Wi-Fi network (after connecting to ActronConnect),
re-open the ActronConnect “App” and click “next”:

15 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 2.10. “App” will search and try to connect to your air conditioner Wi-Fi network. Once connected,
press “next”.

Step 2.11. Set up your air conditioner network connection to your router by selecting your SSID (your
Wi-Fi network name) and typing your Pass Phrase (your Wi-Fi network password).

Illustrations below show how to selecting your SSID:

Scroll Up/Down to select your


Wi-Fi network name.
(Example “Your Network Name”)

16 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Illustration below shows typing your Pass Phrase:

NOTES:
• SSID - Service Set Identifier, the name of the wireless
network. All of the wireless devices on a wireless local
area network (WLAN) must employ the same SSID in
order to communicate with each other.
3 • Pass Phrase - Password for your Wi-Fi network.

Enter your Pass Phrase

Step 2.12. Wait for the system to finish encrypting your air conditioner for access:

Once your air conditioner Wi-Fi access is


established, the screen above will be displayed

17 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
Step 2.13. Close the “App” and go to “Settings” and connect to your router:

Step 2.14. Re-open the “App” and press the “home” button:

After you established the air conditioner and iOS network


connectivity, the ActronConnect home page (as shown above)
will appear and you are now set to remotely operate and
control your air conditioner by using your iOS device.

18 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
WIRING DIAGRAM
Base Variation Code: Variation:
R
Model No:
SRG/V/M ACTRON CONNECT
Description:
M-SERIES INDOOR BOARD WITH ACTRON CONNECT
ACM MODULE & AUX POWER SUPPLY
Drawn: MJH Date: 14-07-2013 Drawing No: Revision Size:
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent. Approved: MJH Date: 20-07-2013 WD0904 B A5

IMPORTANT:
IMPORTANT :
DONOT
DO NOTMOUNT
MOUNT ACM
ACM DIRECTLY
DIRECTLY ON INDOOR
ON INDOOR UNIT
UNIT.
- FOR OPTIMUM PERFORMANCE OF Wi-Fi
- FOR OPTIMUM PERFORMANCE OF
SIGNAL MOUNT 1 METRE AWAY (OR GREATER)
WIFI SIGNAL MOUNT MINUMUM OF
AND NOT ABOVE THE INDOOR UNIT.
1 METRE AWAY & NOT ABOVE
EVAPORATOR
- MOUNT MINIMUM 0.5 METRE BELOW ROOF
LINE.
- MOUNT MINIMUM 1 METRE BELOW ROOF

ACTRON
CONNECT
ACM POWER SUPPLY MODULE
(240VAC - 12VDC 1.3A) (ACM)

ANTENNA

P1
E2
3G LPW WIFI ETH

AC IN DC OUT ADJ

A N -V +V RST MODE
BROWN

GREEN / YELLOW
BLUE

ETH AC PWR
BRN / WHITE (GREEN)

BROWN

EXV
BLUE
BROWN

COIL IN
EC CONTROL

SENSOR

COIL OUT
SENSOR
EARTH

SCRN
DATA
NEUT

COM

PWR
COM
KEY
ACT

B MINOR NOTE REVISIONS N/A MJH 31-10-13


Rev. Description PCR By Date
A ORIGINAL

19 ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
20
LEGEND
AMZ-24V
ACM
IMPORTANT :
ACM POWER SUPPLY IMPORTANT: AMIB
(240VAC - 12VDC 1.3A) DO NOT MOUNT ACM
DO NOT DIRECTLY
MOUNT ON INDOOR
WIFI MODULE UNIT.
DIRECTLY ON EVAPORATOR UNIT EMC
FIELD WIRING FOR M-SERIES - FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL
- FOR OPTIMUM
MOUNT 1 METRE AWAYPERFORMANCE
(OR GREATER)OF AND EXV
CONTROLS ONLY WIFI SIGNAL MOUNT 1 METRE AWAY
NOT ABOVE THE
& NOT INDOOR
ABOVE UNIT.
EVAPORATOR F
RJ45 SOCKETS FOR ACTRON AIR - MOUNT MINIMUM 0.5 METRE
- MOUNT MINIMUM BELOW
1 METRE ROOF LINE.
BELOW
CAT5E ZONE CABLES IF
ROOF
F1
TX ZONE 1 ZONE 2 ZONE 3 ZONE 4 IFRC
2A AC IN DC OUT ADJ
20VA
A N -V +V TX

BLUE
WC

BROWN
BROWN
NEUT ACT RLY

GREEN / YELLOW
BRN / WHITE (GREEN)
WIRING DIAGRAM

WIFI
MODULE

BLUE

BROWN
ECM
IF-1 CONTROL
1 EC MODULE ANTENNA

EXV

EXV
IF FITTED
INDOOR FAN (IF) INDOOR (DEPENDANT ON

P1

E2
COIL IN
INTERNAL AUTO RESET SENSOR MODEL VARIANTS)
OVERLOAD PROTECTION FERRITE

RST MODE

3G LPW WIFI ETH


ETH AC PWR

EC CONTROL
SEE JUMPER PIN POSITION
INDOOR
COIL OUT TABLES ON UNIT WIRING DIAGRAM
SENSOR FOR CORRECT POSITION

N
A
ACT
NEUT
EARTH
DATA
COM
KEY
PWR
COM
SCRN
EMC-1
SCREEN
E WIRES
N
A

DO NOT
CONNECT
SENSOR SCREEN SENSOR
AT WALL
KEY CONTROL KEY
COM COM
POWER POWER

FIELD WIRING BY
INSTALLER

TO OUTDOOR UNIT
OPTIONAL OPTIONAL SENSOR WIRING
SENSOR 1 SENSOR 2

FIELD WIRING BY INSTALLER -


CABLE MUST BE 2 CORE SHIELDED CABLE WITH SHIELD WIRE
CONNECTED TO THE SCREEN / COMMON TERMINAL
(EITHER 2C 14/0.20 SHIELDED OR 2C TWISTED PAIR 7/0.30 SHIELDED CABLE ACCEPTABLE)

R
Base Variation Code: Variation:
Model No:
Description: SRG/V EVAPORATOR WITH EC FAN MOTOR
B LAYOUT CHANGES, ADDED SRV DETAILS N/A MJH 05-11-13 & OPTIONAL ACM WIFI MODULE & POWER SUPPLY

Description PCR By Date This drawing remains the intellectual property of Actron Engineering Drawn: Date: Drawing No: Revision Size:
Rev. MH 02-07-2013
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved: Date: WD0903 B A4
A ORIGINAL without written consent. MJH 05-11-2013

ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
21
LEGEND
8Z-VAV
ACM
IMPORTANT :

ZONE
CONTROL 1
ULTIMA 8Z-VAV MODULE CONNECTIONS & ACCESSORIES ACM POWER SUPPLY AMIB
(SRM MODELS ONLY) IMPORTANT:

ZONE
SENSOR 1
(240VAC - 12VDC 1.3A) DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
AM-ZC DO NOT MOUNT WIFI MODULE
DIRECTLY ON EVAPORATOR UNIT
EMC

ZONE
- FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL

AM-ZS
MOTOR
TO ZONE 2 - 8 - FOR OPTIMUM
MOUNT 1 METRE PERFORMANCE
AWAY (OR GREATER)OF AND EXV
WIFI SIGNAL MOUNT 1 METRE AWAY
NOT ABOVE& THE INDOOR
NOT ABOVE UNIT.
EVAPORATOR F
ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE
8 7 6 5 4 3 2 1 - MOUNT MINIMUM METRE BELOW ROOF LINE.
- MOUNT0.5
MINIMUM 1 METRE BELOW IF
ROOF
ULTIMA MODULE
(8Z-VAV) AC IN DC OUT ADJ
IFRC
240V AMIB TX
MAINS DATA LOG A N -V +V

BLUE
WC

BROWN
BROWN

GREEN / YELLOW

BLUE

BROWN
BRN / WHITE (GREEN)
WIRING DIAGRAM

WIFI
MODULE

BLUE

BROWN
ECM
IF-1 CONTROL
1 EC MODULE ANTENNA

EXV

EXV
INDOOR FAN (IF) INDOOR

P1

E2
COIL IN
INTERNAL AUTO RESET SENSOR
OVERLOAD PROTECTION FERRITE

RST MODE

3G LPW WIFI ETH


ETH AC PWR

EC CONTROL
INDOOR
COIL OUT
SENSOR

N
A
ACT
NEUT
EARTH
DATA
COM
KEY
PWR
COM
SCRN
EMC-1
SCREEN
E WIRES
N
A

DO NOT
CONNECT
SENSOR SCREEN SENSOR
AT WALL
KEY CONTROL KEY
COM COM
POWER POWER

FIELD WIRING BY
INSTALLER

TO OUTDOOR UNIT
FIELD WIRING BY INSTALLER -
CABLE MUST BE 2 CORE SHIELDED CABLE WITH SHIELD WIRE
CONNECTED TO THE SCREEN / COMMON TERMINAL
(EITHER 2C 14/0.20 SHIELDED OR 2C TWISTED PAIR 7/0.30 SHIELDED CABLE ACCEPTABLE)

R
Base Variation Code: Variation:
Model No:
Description: SRM
EVAPORATOR WITH EC FAN MOTOR, 8Z-VAV ULTIMA
MODULE & OPTIONAL ACM WIFI MODULE & POWER SUPPLY

Description PCR By Date This drawing remains the intellectual property of Actron Engineering Drawn: Date: Drawing No: Revision Size:
Rev. MH 05-11-2013
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved: Date: WD0907 B A4
A ORIGINAL without written consent. MJH 05-11-2013

ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
22
LEGEND
IMPORTANT :
FIELD WIRING 8Z-VAV
RJ45 SOCKETS FOR ACTRON AIR ACM POWER SUPPLY DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
(240VAC - 12VDC 1.3A) IMPORTANT: ACM
CAT5E SPEC CABLES ONLY DO NOT MOUNT WIFI MODULE
ZONE - FOR OPTIMUM PERFORMANCE OF Wi-Fi SIGNAL
DIRECTLY ON EVAPORATOR UNIT
SENSOR 1 AMIB
MOUNT 1 METRE AWAY (OR GREATER) AND
TO ZONE 2 - 8 - FOR OPTIMUM PERFORMANCE OF
INDOOR
NOT ABOVE THEWIFI UNIT.
SIGNAL MOUNT 1 METRE AWAY EMC
& NOT ABOVE EVAPORATOR
INDOOR FAN (IF)
- MOUNT MINIMUM 0.5 METRE BELOW ROOF LINE.
- MOUNT MINIMUM 1 METRE BELOW EXV
INTERNAL AUTO RESET ZONE ZONE ZONE ZONE ZONE ZONE ZONE ZONE
8 7 6 5 4 3 2 1 ROOF
OVERLOAD PROTECTION
ZONE AC IN DC OUT ADJ F
ECM ULTIMA MODULE MOTOR
IF-1 A N -V +V
CONTROL (8Z-VAV) IF
MODULE 1 EC

BLUE

BROWN
AMIB

BROWN
240V
MAINS DATA LOG IFRC

GREEN / YELLOW
ZONE TX

BRN / WHITE (GREEN)


CONTROL 1
WIFI WC
FERRITE
FERRITE
MODULE
(IF FITTED)
WIRING DIAGRAM

MAINTAIN TWISTED PAIR

BLUE
ANTENNA

BROWN
UNTIL TERMINAL ON AMIB

B (-)

A
N
OUTDOOR
P1

E2

(+) A
EMC-1
RST MODE

DATA

BLUE
3G LPW WIFI ETH
E ETH AC PWR

BROWN
N
A INDOOR
COIL IN
SENSOR

SEE JUMPER PIN POSITION


TABLES FOR CORRECT SETTING

EC CONTROL
CB-1
10 A
DATA CABLE SCREEN WIRE -
KEEP AS SHORT AS POSSIBLE

ACT
NEUT
EARTH
DATA
COM
KEY
PWR
COM
SCRN

ACT

NEUT
NEUT

LINE 1
SENSOR
SCREEN
WIRES KEY
COM
POWER

PCB JUMPER PIN


DO NOT POSITION TABLES
CONNECT
SCREEN
AND SENSOR PCB Model: AMIB-PVVM
AT WALL
CONTROL Jumper Pin
Position A/C Model

FIELD WIRING BY SENSOR ERM2-14AS


A
INSTALLER
KEY
COM
B ERM3-17AS
FIELD WIRING BY INSTALLER - POWER C ERM4-19AS
CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO THE SCREEN TERMINAL ON INDOOR UNIT D N/A
& SCREEN FOIL CLAMPED TO P-CLIP ON OUTDOOR UNIT
E N/A

R
Base Variation Code: Variation:
Model No:
Description: ERM EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY

Description PCR By Date This drawing remains the intellectual property of Actron Engineering Drawn: Date: Drawing No: Revision Size:
Rev. MH 05-11-2013
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved: Date: WD2004 A A4
A ORIGINAL without written consent. MJH 05-11-2013

ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
23
LEGEND
IMPORTANT :
AMZ-24V
ACM POWER SUPPLY DO NOT MOUNT ACM DIRECTLY ON INDOOR UNIT.
(240VAC - 12VDC 1.3A) IMPORTANT: ACM
- FOR OPTIMUMDO NOT MOUNT WIFI MODULE
PERFORMANCE OF Wi-Fi SIGNAL
DIRECTLY ON EVAPORATOR UNIT
MOUNT 1 METRE AWAY (OR GREATER) AND AMIB
- FOR OPTIMUM PERFORMANCE OF
FIELD WIRING FOR M-SERIES NOT ABOVE THE
WIFI INDOOR UNIT.
SIGNAL MOUNT 1 METRE AWAY EMC
CONTROLS ONLY & NOT ABOVE EVAPORATOR
INDOOR FAN (IF)
- MOUNT MINIMUM 0.5 METRE BELOW ROOF LINE.
- MOUNT MINIMUM 1 METRE BELOW EXV
INTERNAL AUTO RESET
OVERLOAD PROTECTION ROOF
RJ45 SOCKETS FOR ACTRON AIR AC IN DC OUT ADJ F
ECM CAT5E ZONE CABLES
IF-1 A N -V +V
CONTROL F1 IF
MODULE 1 EC TX 2A ZONE 1 ZONE 2 ZONE 3 ZONE 4

BLUE
20VA

BROWN
BROWN
IFRC

GREEN / YELLOW
TX

BRN / WHITE (GREEN)


WIFI WC
FERRITE NEUT ACT RLY

FERRITE
MODULE
(IF FITTED)
WIRING DIAGRAM

MAINTAIN TWISTED PAIR ANTENNA


UNTIL TERMINAL ON AMIB

B (-)

A
N
OUTDOOR
P1

E2

(+) A
EMC-1
RST MODE

DATA

BLUE
3G LPW WIFI ETH
E ETH AC PWR

BROWN
N
A INDOOR
COIL IN
SENSOR

SEE JUMPER PIN POSITION


TABLES FOR CORRECT SETTING

EC CONTROL
CB-1
10 A
DATA CABLE SCREEN WIRE -
KEEP AS SHORT AS POSSIBLE

ACT
NEUT
EARTH
DATA
COM
KEY
PWR
COM
SCRN
SENSOR
KEY

ACT

NEUT
NEUT

LINE 1
COM
SCREEN POWER
WIRES

DO NOT
CONNECT
SCREEN
AND SENSOR
AT WALL
CONTROL
PCB JUMPER PIN
SENSOR POSITION TABLES
KEY
PCB Model: AMIB-P1VV
COM
POWER Jumper Pin
FIELD WIRING BY A/C Model
Position
INSTALLER
OPTIONAL
SENSOR 2 A ERV2-14AS
FIELD WIRING BY INSTALLER - B ERV3-17AS
CABLE MUST BE 2 CORE 7/0.30 SHIELDED TWISTED PAIR DATA CABLE
WITH SCREEN WIRE CONNECTED TO THE SCREEN TERMINAL ON INDOOR UNIT C ERV4-19AS
& SCREEN FOIL CLAMPED TO P-CLIP ON OUTDOOR UNIT
OPTIONAL D N/A
SENSOR 1
E N/A

R
Base Variation Code: Variation:
Model No:
Description: ERV EVAPORATOR WITH EC FAN MOTOR
& OPTIONAL ACM WIFI MODULE & POWER SUPPLY

Description PCR By Date This drawing remains the intellectual property of Actron Engineering Drawn: Date: Drawing No: Revision Size:
Rev. MH 05-11-2013
Pty Ltd. Reproduction, modification and/or distribution are prohibited
Approved: Date: WD2005 A A4
A ORIGINAL without written consent. MJH 05-11-2013

ActronConnect Installation & Commissioning Guide - Website


Doc. No.9590-1001 Version No.2.0 131111C
1800 119 229
actronair.com.au

MAC
Address

Serial
Number

Actron Engineering Pty Ltd Part No. 9590-1001 Version 2.0