CT TEST REPORT

DATE 27/05/2023 PAGE 1

96.836
AMBIENT TEMP. °C JOB # 01

SUBSTATION Adigala 230/33kv Substation HUMIDITY 55 % ASSET ID 33KV CT

POSITION 33kv Phase S core 2 TEST STATUS

EQUIPMENT LOCATION

NAMEPLATE DATA CT: CT1X Core2 Protection

MANUFACTURER ALCE SERIAL NO. 2012-100025901 S Phase PHASE Phase S Core 2

ASSET ID 33kv CT ACCURACY CLASS 5P20 SATURATION STD ANSI 45

BURDEN 10 VA 10

Secondary Voltage Injection


Tap X1-X2
R Nameplate 300:1
A
T Measured 299.714:1
I % Error 0.095
O
Test V (V) 102.75
Test I (A) 0.0094
Prim V (V) 0.3428
Phase Dev. 179°59'
Polarity Incorrect
Knee Volt.(V) 158.22
Cur.(A) 0.0138
Resist. (Ohms) 2.184
Resist. at 75°C 2.499

Insulation Primary To Secondary Primary To Ground Secondary To Ground


Resistance 500V 13.7M 1KV 7.99M 500V 8.90M

X1-X2

TEST EQUIPMENT USED: 201601050019 TESTED BY: Girma Dechasa ,Ashenaf ,Bitew Ayalew,Yewalashet W

COPYRIGHT © 2002-2023 POWERDB, INC. www.powerdb.com Form Schema 4


CT TEST REPORT

PAGE 2

Ratio and Phase Error X1-X2


Ratio Error (%) at % of Rated Current
VA / PF
1 5 10 20 50 100 120 200
10.0 VA/ 0.50 -0.573 -0.340 -0.266 -0.205 -0.139 -0.098 -0.088 -0.064
5.0 VA/ 0.50 -0.346 -0.192 -0.144 -0.104 -0.061 -0.035 -0.029 -0.013
2.5 VA/ 0.50 -0.212 -0.105 -0.071 -0.043 -0.014 0.0022 0.0061 0.0169
1.3 VA/ 0.50 -0.134 -0.054 -0.029 -0.008 0.0126 0.0249 0.0277 0.0348

Phase Displacement (minute) at % of Rated Current


VA / PF
1 5 10 20 50 100 120 200
10.0 VA/ 0.50 1.2713 0.6488 0.3535 -0.014 -0.734 -0.889 -0.929 -1.042
5.0 VA/ 0.50 3.1308 1.9669 1.5624 1.1792 0.6426 0.2104 0.1606 0.0133
2.5 VA/ 0.50 4.4190 2.8401 2.3258 1.8768 1.3387 0.9299 0.8153 0.6142
1.3 VA/ 0.50 5.2305 3.3799 2.7877 2.2834 1.7112 1.3152 1.2114 0.9463

10.0 VA/ 0.50

5.0 VA/ 0.50

2.5 VA/ 0.50

1.3 VA/ 0.50