KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
LUXEDESIGN BUILDING CONTRACTING LLC.

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

EXISTING
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

TRIANGLE POWER SOLUTION

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:

EXISTING RCP
LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED LUXEDESIGN BUILDING CONTRACTING LLC.
FRIDGE

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

s 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR

s s WORKS.

s
5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

800

s
1689,21

PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

s s CLIENT:

TRIANGLE POWER SOLUTION


s WALL PAPER
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


s BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

s
s
CONTRACTOR:

s s

SHEET TITLE:

PROPOSED RCP
LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
LUXEDESIGN BUILDING CONTRACTING LLC.

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

EXISTING
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

TRIANGLE POWER SOLUTION

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:

EXISTING FIRE FIGHTING


LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED LUXEDESIGN BUILDING CONTRACTING LLC.
FRIDGE

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

800

1689,21

PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

WALL PAPER
TRIANGLE POWER SOLUTION
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:

PROPOSED FIRE FIGHTING


LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
SPRINKLER CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
LUXEDESIGN BUILDING CONTRACTING LLC.

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

EXISTING
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

TRIANGLE POWER SOLUTION

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:

EXISTING FIRE ALARM


LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED LUXEDESIGN BUILDING CONTRACTING LLC.
FRIDGE

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

s 4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR

s s WORKS.

s
5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

800

s
1689,21

PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

s s CLIENT:

TRIANGLE POWER SOLUTION


s
WALL PAPER
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.
s
DESIGNER:

CONSULTANT:

s
s
CONTRACTOR:

s s

SHEET TITLE:

PROPOSED FIRE ALARM


FIRE ALARM CONTROL PANEL LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05

S SMOKE DETECTOR CHECKED BY:

APPROVED BY:
ARCHITECT

STR. ENGR.
-

A.S. 114372245
-

DWG. NO.:
PLOT NO.: 3466801
SOUNDER SCALE:

PROJECT NO.:
NTS
PAPER SIZE:

TYPE:
A1
ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
LUXEDESIGN BUILDING CONTRACTING LLC.

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

EXISTING
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

TRIANGLE POWER SOLUTION

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:
EXISTING
EMERGENCY LIGHT
LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED LUXEDESIGN BUILDING CONTRACTING LLC.
FRIDGE

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

800

1689,21

PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

WALL PAPER
TRIANGLE POWER SOLUTION
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:
PROPOSED
EMERGENCY LIGHT
LAYOUT

EXIT LIGHT
DATE: (YYYY/MM/DD)

EXIT DRAWN BY:

CHECKED BY: ARCHITECT


ROK

-
2023/07/05
-

APPROVED BY: STR. ENGR. A.S. 114372245

EL EL EMERGENCY LIGHT PLOT NO.:


SCALE:
3466801
PAPER SIZE:
DWG. NO.:

NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
.29 MTS
NCE=21
KEY PLAN
A
ING DIST
TRAVELL
GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
TRAVELLIN NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED
G DISTAN LUXEDESIGN BUILDING CONTRACTING LLC.

CE=25.66
FRIDGE

MTS 2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

TS
M
19
2 3.
E=
C
N
A
800

IST
D
G
L LIN
VE
1689,21

A
TR
PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

WALL PAPER
TRIANGLE POWER SOLUTION
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:
PROPOSED
LIFE SAFETY
LAYOUT
DATE: (YYYY/MM/DD)
DRAWN BY: ROK 2023/07/05
CHECKED BY: ARCHITECT - -

APPROVED BY: STR. ENGR. A.S. 114372245


DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----
N
KEY PLAN

GENERAL NOTES:
1. THIS DRAWING & DESIGN ARE THE PROPERTY OF LUXEDESIGN BUILDING CONTRACTING LLC, DUBAI, U.A.E. AND SHOULD
NOT BE COPIED OR REPRODUCED PARTIALLY OR FULLY IN ANY FORM WITHOUT THE WRITTEN PERMISSION FROM
INTEGRATED LUXEDESIGN BUILDING CONTRACTING LLC.
FRIDGE

2. ALL DIMENSIONS AND INFORMATION ARE TO BE VERIFIED ON SITE, COORDINATED BY THE CONTRACTOR AND
APPROVED BY ARCHITECT-ENGINEER OF RECORD PRIOR TO COMMENCEMENT OF PHYSICAL WORKS.

3. ALL MATERIALS AND RELATIVE METHOD OF STATEMENT ARE TO BE APPROVED BY ARCHITECT-ENGINEER OF RECORDS
BEFORE USAGE OR INSTALLATION. ALL DISCREPANCIES ARE TO BE REPORTED TO AND RESOLVED BY THE ARCHITECTS
BEFORE WORKS ARE COMMENCED.

4. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ARCHITECTURAL, STRUCTURAL, MEP, SE
DETAIL AND ALL RELEVANT SECTIONS OF THE SPECIFICATIONS, CONTRACTOR AND SUB-CONTRACTOR SHALL
COORDINATE THESE DRAWINGS AND REPORT ANY DISCREPANCY FOR CLARIFICATION BEFORE PROCEEDING WITH THEIR
WORKS.

5. THIS DRAWING IS NOT MEANT TO BE SCALED OR MEASURED.

LEGEND:

800

1689,21

PROPOSE
- - -
ISSUE NO. PURPOSE OF ISSUE APPD. BY.

CLIENT:

WALL PAPER
TRIANGLE POWER SOLUTION
TECHNO GRAFICA
82427-2_CINDY-RUST_web
SUPPLIER CASAMIA

PROJECT:

UNIT 105 MODIFICATION


WORKS
LOCATION:

BAY SQUARE, BUILDING -7,


BUSINESS BAY , DUBAI, UAE.

DESIGNER:

CONSULTANT:

CONTRACTOR:

SHEET TITLE:
EXISTING FCU'S SCHEDULE PROPOSED
AC
COOLING CAPACITY LAYOUT
TOTAL SENSIBLE AIR FLOW AIR ON/OFF COIL CHILLED WATER QTY ELEC.DATA DRAWN BY: ROK
DATE: (YYYY/MM/DD)
FCU COOLING LOAD COOLING LOAD (CFM) TEMP INLET&OUTLET (KW / PH)
2023/07/05

REF.NO CHECKED BY: ARCHITECT - -


(TMBH) (SMBG) (PER UNIT) PEMP. (°C) PEMP. (°C)
APPROVED BY: STR. ENGR. A.S. 114372245
FCU-01 to 02 60.3 52.3 2125 23/12.5 5.5/14.4 2 0.55 / 1 DWG. NO.:
PLOT NO.: 3466801
SCALE: PAPER SIZE:
NTS A1
PROJECT NO.: TYPE: ISSUE NO.:
DAT-5512 AR -----