G2206070002 0001 Test Report
G2206070002 0001 Test Report
Page No: 1 of 12
CIN: U74220JK2013PTC003789
TEST REPORT
Test Report Issue To: Test Report No : G2206070002-0001
POWER GRID CORPORATION OF INDIA LIMITED Date of Issue: 23/07/2022
(LADDAKH)
RURAL ELECTRIFICATION WORKS AT
KARGIL J&K.
Sample Booking/Receipt : 07/06/2022
Date of Start of Testing: 08/06/2022
Date of Completion of Test: 19/07/2022
Sample Description :
DESIGN MIX OF CONCRETE M-25
Sample Condition : Ok
Sample Size (Approx):
Sample Quantity (Approx): 1
This is Digitally Signed Report and hence doesn't require Physical Signature
Geotech International Analytical Lab Pvt. Ltd,
6-B, 2nd Rotary EPIP, Bari Brahmana,Jammu-181133(India)
Phone : +911913507089, +911913507090 || Web: www.geotechanalytical.com || Email: jammu@geotechanalytical.com
ISO 9001:2015, ISO 14001:2015 & ISO 45001:2018 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 2 of 12
Report No: G2206070002-0001
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 3 of 12
Report No: G2206070002-0001
As per IS :2386
3 Water Absorption (%) 0.30 0.36 1.40 5 Max.
pt-3
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 4 of 12
Report No: G2206070002-0001
Particle sizeUpper
Lower Limit
distribution
limit Mid limit % Passing
150
100
% Passing
50
0
0.1 1 Particle size in mm 10 100
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 5 of 12
Report No: G2206070002-0001
Adopted water cement ratio =0.46, 0.46 < 0.50, Hence OK.
8. SELECTION OF WATER CONTENT
From Table 4 of IS 10262-2019, maximum water content for 20 mm Aggregate =186 litre
Estimated water content for 100-150mm slump = 186 + (186 x 3/100) = 191.58 Liter
Based on trial with admixture dose @0.7% water content reduction of 18.4% has been achieved.
f) Mass of coarse aggregate = e x Volume coarse aggregate x combine Sp. Gravity of coarse aggregate x 1000
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 6 of 12
Report No: G2206070002-0001
578.6 579.0
Ratio of mix Proportioning
Water : Cement : Admixture : Fine Aggregate : Coarse Aggregate
Actual Quantities Reqd. for the mix per 1 Bag of Cement in dry condition W/C = 0.46
Water (kg) Cement (kg) Admixture(kg) Sand (kg) Coarse Aggregate
10 mm (kg) (50%) 20 mm (kg) (50%)
25.23 50.0 0.35 117.0
85.09 85.09
NOTE:-
1 It is advised to check the silt content of sand at frequent intervals during the supply. If the silt Content in sand is higher than the permissible limit the sand
may require washing.
2
The mix design can be adopted at the site after carrying out trials, as usual.
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 7 of 12
Report No: G2206070002-0001
Adopted water cement ratio =0.45, 0.45 < 0.50, Hence OK.
13. SELECTION OF WATER CONTENT
From Table 4 of IS 10262-2019, maximum water content for 20 mm Aggregate =186 litre
Estimated water content for 100-150mm slump = 186 + (186 x 3/100) = 191.58 Liter
Based on trial with admixture dose @0.8% water content reduction of 15.44% has been achieved.
f) Mass of coarse aggregate = e x Volume coarse aggregate x combine Sp. Gravity of coarse aggregate x 1000
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 8 of 12
Report No: G2206070002-0001
568.8 569.2
Ratio of mix Proportioning
Water : Cement : Admixture : Fine Aggregate : Coarse Aggregate
Actual Quantities Reqd. for the mix per 1 Bag of Cement in dry condition W/C = 0.45
Water (kg) Cement (kg) Admixture(kg) Sand (kg) Coarse Aggregate
10 mm (kg) (50%) 20 mm (kg) (50%)
24.57 50.0 0.40 108.67
79.0 79.1
NOTE:-
1 It is advised to check the silt content of sand at frequent intervals during the supply. If the silt Content in sand is higher than the permissible limit the sand
may require washing.
2
The mix design can be adopted at the site after carrying out trials, as usual.
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 9 of 12
Report No: G2206070002-0001
Adopted water cement ratio =0.44, 0.44 < 0.50, Hence OK.
18. SELECTION OF WATER CONTENT
From Table 4 of IS 10262-2019, maximum water content for 20 mm Aggregate =186 litre
Estimated water content for 100-150mm slump = 186 + (186 x 3/100) = 191.58 Liter
Based on trial with admixture dose @0.8% water content reduction of 12.73% has been achieved.
f) Mass of coarse aggregate = e x Volume coarse aggregate x combine Sp. Gravity of coarse aggregate x 1000
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 10 of 12
Report No: G2206070002-0001
559.7 560.0
Ratio of mix Proportioning
Water : Cement : Admixture : Fine Aggregate : Coarse Aggregate
Actual Quantities Reqd. for the mix per 1 Bag of Cement in dry condition W/C = 0.44
Water (kg) Cement (kg) Admixture(kg) Sand (kg) Coarse Aggregate
10 mm (kg) (50%) 20 mm (kg) (50%)
23.92 50.0 0.38 101.29
73.64 73.68
NOTE:-
1 It is advised to check the silt content of sand at frequent intervals during the supply. If the silt Content in sand is higher than the permissible limit the sand
may require washing.
2
The mix design can be adopted at the site after carrying out trials, as usual.
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
TEST REPORT Page No: 11 of 12
Report No: G2206070002-0001
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory
Format No: GIAL/TRF/GEN
Issue No: 01, Issue Date: 02.11.2020
CIN: U74220JK2013PTC003789
2. Total Liability of our Laboratory is limited to the invoiced Amount. No Liability will be accepted
after Sample is taken back
3. The Sample Description is given “As desired by the customers”. Sample not drawn by us &
Analysis Conducted on Received sample unless specified otherwise.
4. Retained sample will be destroyed after 30 days from the date of issue of the test report unless
instructed otherwise.
5. Any Complaints or Retest request should be communicated within 15 days from the issue of the
Test report.
6. Test Report shall not be reproduced except in full, without Written approval of the Laboratory
7. The Test report is not to be reproduced wholly or in parts & cannot be used as an evidence in a
court of law & shall not be used in advertising media without our permission in writing.
Geotech International Analytical Lab Pvt Ltd; 6-B, 2nd Rotary EPIP, Bari Brahmana, Jammu-181133(J&K)
Phone- 01923-220615 II Web: www.geotechanalytical.com II Email: jammu@geotechanalytical.com
ISO: 9001-2015 Certified Laboratory