Equipment Submittal Index

Item Description Submittal No


Mist System Equipment

1 misting nozzle BFP-2995-001


2 Stainless steel piping BFP-2995-002
3 exstinguisher panel BFP-2995-003
Sample No

BFP-039
BFP-040
BFP-041
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-001

To Spoormaker & Partners Rev No 1

Sub.Date 27/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Protection - Mist System

Equipment Misting Nozzle

Manufacturer Enviro mist

Supplier Brigit

Address Ridge Road


Laser Park

Contact Person Deon Van Zyl

Tel No +27 11 794 2217

Email deon@brigit.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Misting System

Function of the System Fire Protection System - Misting

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout

Drawing Numbers DWG-ENV-MP-DFS-001-4

Drawing type Submission

(i) Shop Drawing Mechanical Layout Yes

(ii) Shop Drawing Electrical Layout N/A

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout N/A

(iii) As Built Drawing Controls Layout N/A

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification except


wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator N/A

(ii) Equipment checked for remote control or BMS interfacing compatibility N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-002

To Spoormaker & Partners Rev No 1

Sub.Date 27/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Protection - Mist System

Equipment Stainless steel piping

Manufacturer NDE

Supplier Brigit

Address Ridge Road


Laser Park

Contact Person Deon Van Zyl

Tel No +27 11 794 2217

Email deon@brigit.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Misting System

Function of the System Fire Protection System - misting

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout

Drawing Numbers DWG-ENV-MP-DFS-001-4

Drawing type Submission

(i) Shop Drawing Mechanical Layout Yes

(ii) Shop Drawing Electrical Layout N/A

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout N/A

(iii) As Built Drawing Controls Layout N/A

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification except


wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator N/A

(ii) Equipment checked for remote control or BMS interfacing compatibility N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-003

To Spoormaker & Partners Rev No 1

Sub.Date 27/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Protection - Mist System

Equipment Exstinguisher Panel

Manufacturer C-TEC

Supplier Brigit

Address Ridge road


Laser Park

Contact Person Deon Van Zyl

Tel No +27 11 794 2217

Email deon@brigit.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibil
B
Tel No Approved with Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Misting system

Function of the System Fire Protection System - Misting

Non Conformance to Specificat Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D Ground floor deluge Layout

Drawing Numbers DWG-ENV-MP-DFS-001-4

Drawing type Submission

(i) Shop Drawing Mechanical Layout Yes

(ii) Shop Drawing Electrical Layout N/A

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout N/A

(iii) As Built Drawing Controls Layout N/A

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator N/A

(ii) Equipment checked for remote control or BMS interfacing compatibility N/A
(ii) Specified the allowed fault Level for the Electrical Controllers N/A

Remarks (Note: If the area is inadequate add remarks as an addendum)


BFP-SMA2995-003

27/1/2022

Morne van der Merwe

MWP Eskom