Equipment Submittal Index

Item Description Submittal No


Fire Detection Equipment
1 ZP3 - Fire Detection Control Panel BFP-SMA2995-001
2 ZP730-2P Otical Smoke Detector BFP-SMA2995-002
3 ZP755HAV Addressable Sounder Beacon BFP-SMA2995-003
4 ZP785-3 Addressable Manual Call Point BFP-SMA2995-004
5 Cable - Fire Resistant PH30 BFP-SMA2995-005
6 Flame Detector – SHARPEYE™ Range BFP-SMA2995-006
7 BS127N Sealed Lead Acid Battery BFP-SMA2995-007
8 Bosal Conduit and Fittings BFP-SMA2995-008
9 A50E A Series Mini Relay Unit BFP-SMA2995-009
10 Surface Box for Mini Units BFP-SMA2995-010
11 Fire Panel Network Card BFP-SMA2995-011
Sample No

BFP-020
BFP-010
BFP-011
BFP-013
BFP-015
BFP-021
BFP-026
BFP-027 + 027A
BFP-028
BFP-029
BFP-030
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-001

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System

Equipment ZP3 - Fire Detection Control Panel

Manufacturer Carriers

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)

Author : JJ Havenga
Date : 07/21/2023 Page 3 of 63 Email :jhavengaj@tfmc.co.za
Contact : 082 4508497
System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Conforms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes

(ii) Freqency/Schedules of Routine Maintenance Yes

Author : JJ Havenga
Date : 07/21/2023 Page 4 of 63 Email :jhavengaj@tfmc.co.za
Contact : 082 4508497
(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow

(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)

Author : JJ Havenga
Date : 07/21/2023 Page 5 of 63 Email :jhavengaj@tfmc.co.za
Contact : 082 4508497
Author : JJ Havenga
Date : 07/21/2023 Page 6 of 63 Email :jhavengaj@tfmc.co.za
Contact : 082 4508497
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-002

To Spoormaker & Partners Rev No 1

Sub.Date 1/22/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-010 Optical Smoke Detector.pdf

Equipment ZP730-2P Otical Smoke Detector

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes
Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes

(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes


Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow

(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
al Smoke Detector.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-004

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-011 Beacon-Sounder incl Base.pdf

Equipment ZP755HAV Addressable Sounder Beacon

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
n-Sounder incl Base.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-004

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-013 Manual Call Point Red.pdf

Equipment ZP785-3 Addressable Manual Call Point

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
al Call Point Red.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-005

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-015 PH30 Cable.pdf

Equipment Cable - Fire Resistant PH30

Manufacturer Technoswith

Supplier Technoswitch

Address Cussonia Park, Ridge Road


Laser Park
Roodepoort
Johannesburg

Contact Person Deon Swart

Tel No +27 11 794 9144

Email deon@technoswitch.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-006

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System

Equipment Flame Detector – SHARPEYE™ Range

Manufacturer Spectrex

Supplier Technoswitch

Address Cussonia Park, Ridge Road


Laser Park
Roodepoort
Johannesburg

Contact Person Deon swart

Tel No +27 11 794 9144

Email deon@technoswitch.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-007

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-026 FR-BS127N Battery.pdf

Equipment BS127N Sealed Lead Acid Battery

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
127N Battery.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-008

To Spoormaker & Partners Rev No 1

Sub.Date 18/12/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-027 Bosal Conduit.pdf

Equipment Bosal Conduit and Fittings

Manufacturer Bosal

Supplier Bosal Afrika Industrial Division

Address Rooibok Ave


Koedoespoort Industrial Site
Pretoria
0186

Contact Person Zain Adam

Tel No +27 12 391 1000

Email zain.adam@bosal.co.za

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
Conduit.pdf Rooibok Avenue
Koedoespoort Industrial Sites
Pretoria
186
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-009

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-028 A50E Mini Relay Unit.pdf

Equipment A50 A Series Mini Relay Unit

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
Mini Relay Unit.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-010

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-029 Surface Mount Box.pdf

Equipment Surface Box for Inteface Units

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow
e Mount Box.pdf
EQUIPMENT SUBMITTAL FOR APPROVAL
Submittal No BFP-SMA2995-011

To Spoormaker & Partners Rev No 1

Sub.Date 18/1/2022

Prepared by Morne van der Merwe


Attention Jannie Havenga

Project MWP Eskom Project No MWP Eskom

Service Fire Detection System Brochures\BFP-030 Network Card.pdf

Equipment Fire Panel Network Card

Manufacturer Carries

Supplier UTC Climate, Controls and Security

Address 29 Angus Cresent, Londmeadows Business Park East


Edenvale
1609

Contact Person Victor Martins

Tel No +27 11 579 7324

Email victor.martins@carrier.com

For Client/Client Authorized Representative/Client Agent use only

Name Approve Status

Company A Approved

Responsibility
B Approved with
Tel No Remarks

Cell No C Not Approved

Email

Remarks (Note: If the area is inadequate add remarks as an addendum)


System & Fuction Description Addressable Fire Control Panel - ZP3

Function of the System Fire Detection System

Non Conformance to Specification Confirms to Specification

Equipment Technical Data Sheet

Manufactures Data

(i) Signed off Specification Yes

(ii) Technical Data & Design Capacities Yes

(iii) Warranty Yes

Descriptive Literature

(i) Catalogue & Brochures Yes

(ii) Dimentional Drawings Yes

(iii) Manufacturing Specification & Shop Drawing Yes

Operating Standards & Instructions

(i) First, Second & Final Fix Quality Inspection sheet Yes

(ii) Pre-start Checklist No

(iii) Start-Up & Stopping Procedures Yes

(iv) Inspection during Operation Yes

(v) Adjustment parameters Yes

(vi) Testing Procedures Yes

(vii) Operators Roles & Responsibilities Yes

(viii) Proper operation of the installation shall be demonstrated to the Engineer Yes

Maintenance Instructions & Procedures

(i) Preventative Maintetance Action Yes


(ii) Freqency/Schedules of Routine Maintenance Yes

(iii) MTTF & MTTR of Major Equipment To Follow

(iv) Critical Spares Yes

(v) Spares List No

(vi) Trouble Shooting Guidelines Yes

Drawings

Drawing Description Data Centre Phase 2- Block C & D

Drawing Numbers DWG-ENV-MP-M-SD-001-3

Drawing type Submission

(i) Shop Drawing Mechanical Layout N/A

(ii) Shop Drawing Electrical Layout Yes

(iii) Shop Drawing Controls Layout Yes

(iv) Builders Requirent N/A

(v) As Built Drawing Mechanical Layout To Follow

(vi) As Build Drawing Electrical Layout To Follow

(iii) As Built Drawing Controls Layout To Follow

Equipment Submittal Checklist

(i) Is index included, mark-up and all pages numbered No

(ii) Does the equipment/sub-system conform to specification


except wher noted on non conformance form Yes

(a) Access for equipment Yes

(b) Installation Instructions Yes

(c) Access for service or repair work Yes

Equipment/Component Interface

(i) Equipment checked for adequate power supply an local electrical isolator Yes

(ii) Equipment checked for remote control or BMS interfacing compatibility To Follow
(ii) Specified the allowed fault Level for the Electrical Controllers Yes

Remarks (Note: If the area is inadequate add remarks as an addendum)


Yes
No
N/A
To Follow