Before handling the product

DATA SHEET Read this data sheet carefully prior to any operation, mounting, installation or ❏ Wiring Precautions
start-up of the product. 3. Performance Specifications
CAUTION
LG Programmable Logic Controller
Model
FieldBus Network Module Materials for MASTER-K
Drive the terminal screws firmly to the defined torque. If loosely driven, it
K3F-FUEA
MASTER-K K3F-FUEA Name Code
can cause short circuit, fire or malfunction. Item

Be careful that any foreign matter like wire scraps should not enter into Dropout Tolerance 20ms
MASTER-K KGL-WIN (Programming software) 702005036
the module. It can cause a fire, disorder or malfunction. Transfer rate 1Mbps
MASTER-K (Instructions & Programming) 702006539
MASTER-K CPU User’s Manual 702006391 Comm. Method Half duplex bit serial method
MASTER-K K7F-FUEA/K4F-FUEA/K3F-FUEA
702006415 Synchronization Frame synchronous method
Manual

❏ Test RUN and Maintenance Precautions Transmission method Bus type

Name Code Max. cable length 750m


WARNING
MASTER-K K3F-FUEA Data Sheet 702006200
No. of station Up to 64 stations
Do not contact the terminals while the power is applied. It can cause
Modulation Manchester Biphase-L
malfunction.
When cleaning or driving terminal screws, perform them after the power Error detect CRC-CCITT and Time Over
has been turned off.
❏ Safety Precautions Connector type 9 pin plug type
Do not perform works while the power is applied. It can cause disorder or
Be sure to read carefully the safety precautions given in data sheet and user’s Cable type Twisted pair cable
malfunction.
manual before operating the module and follow them.
Max. link points 3,840 Word
The precautions explained here only apply to the MASTER-K K3F-FUEA
module. CAUTION Max. transfer points 1,920 Word

For safety precautions on the PLC system, please see the MASTER-K CPU Max. No. of block 64 blocks
Do not separate the PCB from the case of module, or do not remodel the
user’s manual.
module. They can cause disorder, malfunction, damage of the module or Max. points per 1 block 60 Word
A precaution is given with a hazard alert triangular symbol to call your attention,
a fire.
and precautions are represented as follows according to the degree of hazard. Current consumption 182 mA

LG Industrial Systems If not provided with proper prevention, it can cause ❏ Waste Disposal Precautions
Weight 102 g

! WARNING
death, fatal injury or considerable loss or property
CAUTION
If not properly observed, it can cause a hazard situation
! CAUTION to result in severe or slight injury or a loss of property. When disposing the module, do it as an industrial waste. 4. Cable Specifications

However, a precaution followed with CAUTION can also result in Twisted pair cable
serious condition. Both of two symbols indicate that an important content
LIREV-AMESB
● Beijing Branch ● Bangkok Branch is mentioned, therefore, be sure to observe it.
LG Industrial Systems LG Industrial Systems (Thailand) Type 2*1.0mm Structure
Keep this manual handy for your quick reference in necessary.
Elevator Co., Ltd. Co., Ltd 1. Introduction 18AWG
T : +86-10-6462-3256 T : +66-2-381-8443
Manufacturer LG Cable Conductor
F : +86-10-6462-3255 F : +66-2-381-8445 This data sheet contains the brief information about the characteristics,
● Bogota Branch ● Chicago Branch Cable type Twisted pair shielded Insulator
❏ Design Precaution configurations, and operating of MASTER-K PLC Fnet (K3F-FUEA) module.
LG Industrial Systems de LG Industrial Systems Co., Ltd. cable
Colombia S.A. Chicago Office
T : +57-1-310-6077 T : +1-708-692-4500 CAUTION Impedance 21.8Ω /㎞
2. General Specifications
F : +57-1-310-5831 F : +1-708-692-4501 Withstanding voltage 500 V/Min (DC)
● Dalian Branch ● Hanoi Branch Do not run I/O signal lines near to high voltage line or power line. 1,000 ㏁/㎞ or more
No. Item Specification Standard Insulation resistance
Dalian LG Industrial Systems LG Industrial Systems Co., Ltd. Separate them as 100mm or more as possible. Otherwise, noise can 1 Operating temperature 0 ~ 55℃ Capacity 45 ㎊/m or less (1 ㏀)
Co., Ltd. Hanoi Office
cause module malfunction 2 Storage temperature -25 ~ 70℃
T : +86-411-281-2579 T : +64-4-821-0388 Characteristic impedance 120± 12Ω (10 ㎒)
3 Operating Humidity 5 ~ 95%RH, non-condensing
F : +86-411-281-2578 F : +64-4-821-0399 Ground line
4 Storage humidity 5 ~ 95%RH, non-condensing Core 2 Cores
● Hong Kong Branch ● Shanghai Branch
Occasional vibration IEC 1131-2
LG Industrial Systems (HK) Ltd. Shanghai LG Industrial Systems Co., Ltd.
Frequency Acceleration Amplitude Sweep count
T : +852-2598-6615 T : +86-21-6248-2710 10≤ f∠57 Hz - 0.075 mm
F : +852-2598-7105 F : +86-216248-3236 ❏ Installation Precaution 57 ≤ f≤ 150 Hz 9.8 ㎨ {1G} - 10 times in
5 Vibration
● Singapore Branch ● Taipei Branch Continuos vibration each direction IEC 1131-2 5. Connection of Communication Cable
LG Industrial Systems Co., Ltd. LG Industrial Systems (Taiwan) Co. Ltd. CAUTION Frequency Acceleration Amplitude for
10≤ f∠57 Hz X, Y, Z
- 0.035 mm
T : +65-323-7361 T : +886-2-516-5010 57≤ f≤ 150 Hz 4.9 ㎨{0.5G} - Cable for electric network connection uses only No. 6 and No.7 of the connector
F : +65-323-7362 F : +886-2-516-5035 Operate the PLC in the environment conditions given in the general *Maximum shock acceleration: 147 ㎨ {15G}
pins. They should be connected with the pin has the same pin number. Each
● Tokyo Branch specifications 6 Shocks
*Duration time :11 ms
IEC 1131-2
*Pulse wave: half sine wave pulse( 3 times in each of X, Y and Z body of connector should be connected with shield wire.
LG Industrial Systems Co., Ltd. Tokyo Office directions )
If the PLC is operated in other environment not specified in the
T : +81-3-3589-6362 Square wave impulse ± 1,500 V Twisted pair cable
F : +81-3-3588-1810 general specification, it can cause an electric shock, a fire, malfunction noise
Electrostatic IEC 1131-2
or damage or degradation of the module. Voltage :4kV(contact discharge)
discharge IEC 801-2

LG Industrial Systems Co., Ltd. Make sure the module fixing projections is inserted into the module Radiated
electromagnetic field
27 ~ 500 MHz, 10 V/m
IEC 1131-2
IEC 801-3
6 6
7 Noise immunity
7 7
● Head Office fixing hole and fixed. Digital Digital I/Os
All
Severity I/Os (Ue < 24 V) Analog
LG Mullae Building 9th F, 10, Mullae-dong 6-ga, Yongdungpo-gu, Seoul, KOREA Improper installation of the module can cause malfunction, disorder or Fast transient burst Level power
( Ue ≥ I/Os communication IEC 1131-2
noise modules IEC 801-4
24 V) I/Os Shield wire
Tel : +82-2-2006-3751~6 Fax : +82-2-2006-3951 falling.
Voltage 2 kV 1 kV 0.25 kV Module A Module B
Home page : http:www.lgis.lg.co.kr/fa 8 Atmosphere Free from corrosive gases and excessive dust
9 Altitude for use Up to 2,000m
10 Pollution degree 2 or lower
702006200
11 Cooling method Self-cooling
6. Terminal Resistance 8. LED Indication for Error Status ② Status values indicated by CPU 5) Improper cable connection (snarled cable, redundant connection, etc) can
Error No. cause communication error.
• Resistor : 110Ω, 1/2W Description
(Decimal)
• Connection : Pin 6 and 7 6) Do not place communication cable near power cable or inductive noise
Pin 7
16 Position error of communication module
Error type LED Status Description source.
① Attach 110Ω, 1/2W resistor of spare parts Resistor 17 Initialization error of communication module mounted in SLOT_NO
Pin Self diagnosis of internal memory 1 7) Make sure that shield wire is connected to the metal case of 9-pin
to the connectors of both end of network.
6 18 Input parameter setting error
② Connector case should not be connected During Power Self diagnosis of internal memory 2 connector.
with resistor. 19 Variable length error 8) Do not mount or dismount module while power is applied to the module.
is On Self diagnosis of communication
9pin socket type
20 Improper response is received from other station Therefore, turn off the module before repairing or replacement.
Diagnosis of interface with CPU

Normal Module is not LAS


21 No response during specified waiting time (Time our error) 9) Change of station number or mode switch setting will not take effect

7. Parts Name and Description Communication Module is LAS


before power is re-applied.

Error in self diagnosis of internal memory 1


K3F-FUEA
Error in self diagnosis of internal memory 2 10. Maintenance
RUN 12. Dimension
LAS Item Description Error in self diagnosis of communication
TOKEN Perform routine check and regular check to maintain the best status of the K3F-FUEA
① RUN : Indicates the status of Hardware Error in diagnosis of interface chip
TX/RX FAULT communication of PLC communication module.
Error
unit : mm
K3F-
K3F - FUEA ( Normal : ON) Error in diagnosis of interface RAM
LAS : Turn on when the module is Error 1 in diagnosis of CPU interface
MODE RUN

performing LAS function. ① Daily check LAS

② ① TOKEN
ON-LINE
TOKEN : Turn on when the module Error 2 in diagnosis of CPU interface TX/RX FAULT
K3F - FUEA
LED Check Item Contents Decision Criteria
TEST1 has token. × 10 × 1
Error 3 in diagnosis of CPU interface MODE
TEST2 TX/RX : Turn on when the module Cable connection Release of cable No released cable ON-LINE

is transmitting/receiving System TEST1

FAULT : Flickers when comm. error System error during operation Module connection Release of screw No released screw TEST2

Operation Error
CON1 occurred. Flickering (Off means interface with CPU is CON1
Error in network configuration status RUN LED Flicker check 110
② cut off)
0 : ON-LINE normal communication
Duplicated station No, abnormal terminal resistor
Mode 1 : Communication test mode 1 LED of only one module among modules of
Abnormal
setting 2 : Communication test mode 2 Cable cut off or short
③ entire network should be lighted. (It means CON2
Communi-
Specified length of cable is not proper or LAS LED Light on check
cation abnormal configuration of network that two or
③ CON1/2 : FieldBus cable connector hardware error of the module
(9-pin plug type) more LED is on.)
Connector K3F-FUEA
LED
Error of network configuration 38 35
CON2 Light off means abnormal (Duplicated station
TOKEN LED Flicker check
Interface Interface error (stopped) of LAS or cable error)
Error Interface error (stopped) of non LAS Light off means abnormal (Hardware error of
TX/RX LED Flicker check
module)
K3F-FUEA Unrecoverable Regular flickering : system error
Hardware error of communication module FAULT LED Light off check
Error Irregular flickering : communication error

※ LED position follows the sequence of RUN, LAS, TOKEN, TX/RX, and ② Regular check
FAULT from left side. Check following items once or twice per six months, and perform relevant action. 90

8. Station No. setting of Fnet LED On LED off


Check Item How to check Decision Criteria

Flickering with 1 second interval Temperature 0 ~ 55 °C


Ambient Thermometer/Hydrometer
Flickering with irregular interval or LED off Humidity 5 ~ 95 %RH
Flickering with irregular interval environment
Atmosphere Check corrosive gas No corrosive gas
Station No. setting
Release Shake the module No release
Switch Module
× 10 × 1
(inside of module) Dust or foreign
status Visual inspection No dust of foreign matter
matter

9. Status Code of Function Block (Error List) Release of screw Tighten with a driver No release

Connection Compression
Visual inspection Proper gap
① Error received from the communication module status terminals
Error No.
Description Connector Visual inspection No release
(Decimal)
Check voltage between AC 85 ~ 132 [V]
0 Normal (No error) Power voltage check
terminals AC 170 ~ 264 [V]
Physical layer error of link side (Tx/Rx is impossible)
1
- Self-station error, other station’s power off, station No. error, etc.

4 Data type mismatch


Station No. setting 11. Handling Instructions
switch Description 8 Access denied to remote object

10 Response waiting time over(Time out error)


(1) Station number (0~63), Set in decimal 1) Including self-station, all modules in the whole network must have
11 Structure error
(2) Station No. setting different high speed link station number. If there is any duplicated station
12 Abort (disconnected by serious error)
number, normal communication is impossible.
× 10 Switch Setting 13 Reject (type mismatch with MMS or error caused by noise) 2) Set mode switch at ‘On-Line’ mode during normal communication. If turn
× 10 Setting 10 unit of station No. 33 Variable identifier is not found (Access variable setting error) on the module with ‘Test 1’ mode while other stations of network are
Setting 1 unit of station No. 34 Address error communicating, it can cause serious problem on communication.
× 1 × 1
Response error (response is different with required format or other station’s 3) Use cable complied with specification of this data sheet. Otherwise, it can
50
CPU error cause serious communication error.
4) Make sure that communication cable connector fastened firmly.
Otherwise, it can cause serious communication error.