Hvac HCL Banjara Hills

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

OPTION - 1 HCL AC

Sr LOCATION B L Sq.Ft FCFM SCFM TR TR TYPE TR QTY


1 RECEPTION SHOWROOM AREA 25.3 22.2 561.66 225 2515.42 5.40
2 MR1 9.8 8.5 83.3 17 508 0.98
3 MR2 9.8 8.7 85.26 17 371 0.73
12.28 DUCTABLE 17.00 1NOS
4 MR3 7.9 8.5 67.15 14 306 0.61
5 WORKSTATION 21.1 8.3 175.13 70 1033 2.31
6 LIVING & KITCHEN 13.9 22.6 314.14 63 1109 2.25
7 MBR 11.7 10.7 125.19 25 525 1.05 1.05 HI-WALL 1.50 1NOS
8 SERVER & UPS HI-WALL 2.00 1NOS
TOTAL: 1411.83 430.40 6366.91 13.32

Page 1 of 9
OPTION - 02 HCL AC
Sr LOCATION B L Sq.Ft FCFM SCFM TR TR TYPE TR QTY
1 RECEPTION SHOWROOM AREA 25.3 22.2 561.66 225 2515.42 5.40 6.00 CASSETTE 3.00 2NOS
2 MR1 9.8 8.5 83.3 17 508 0.98 1.00 HI-WALL 1.00 1NOS
3 MR2 9.8 8.7 85.26 17 371 0.73 1.00 HI-WALL 1.00 1NOS
4 MR3 7.9 8.5 67.15 14 306 0.61 1.00 HI-WALL 1.00 1NOS
5 WORKSTATION 21.1 8.3 175.13 70 1033 2.31 3.00 HI-WALL 1.50 2NOS
6 LIVING & KITCHEN 13.9 22.6 314.14 63 1109 2.25 3.00 HI-WALL 1.50 2NOS
7 MBR 11.7 10.7 125.19 25 525 1.05 1.50 HI-WALL 1.50 1NOS
8 SERVER & UPS 2.00 HI-WALL 2.00 1NOS
TOTAL: 1411.83 430.40 6366.91 13.32 18.50

Page 2 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE RECEPTION SHOWROOM AREA
CLIENT EC AREA ( SqFt) 562
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 6744
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S 267. SqFt x 12 x 1 x 0.65 2083. 611. Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 7.5 = 68
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.12 = 67
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 2.00 = 225
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 225
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N SqFt x 29.0 F x 1 x 0.45 . . Occupancy (Nos.) = 9.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.68
Wall - E 304. SqFt x 31.0 F x 1 x 0.45 4241. 1244. Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 0.5
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.95
Wall - W 304. SqFt x 45.0 F x 1 x 0.45 6156. 1805. Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.9
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass 267. SqFt x 31 F x 1.13 9353. 2743. Dehumidified Rise
Partition 250. SqFt x 26 F x 0.32 2080. 610. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 562. SqFt x 26 F x 0.48 7014. 2057. Effective Room Sensible Heat
= 2515 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 225. CFM x 31. F x BF x 1.08 903. 265. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 9. Nos. x 245 Btu/Hour Per Person 2205. 647. Air Quantity
Lighting 944. SqFt x 1.68 W/SqFt x 1.25 x 3.41 6761. 1983. Supply Air CFM RSH / 1.08 X ⁰ F = 2515
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 0.50 kW x 3410 1705. 500. Resulting ENT & LVT Conditions at Apparatus
Sub Total 42500. 12463. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 78
Factor 12.5% 5313. 1558. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 75
Effective Room Sensible Heat 47813. 14021. From Psych. Chart: TEWB 64 ⁰ F TLWDB 62.9 ⁰ F
ROOM LATENT HEAT
Ventillation 225. CFM x 35. Gr/Lb x BF x 0.63 633. 186.
People 9. Nos. x 205. Btu/Hour Per Person 1845. 541. TOTAL HEAT CAPACITY
Sub Total 2478. 727. Grand Total Heat = 5.40 TR
Factor 5.0% 124. 36. 12000 = 64.76 MBH
Effective Room Latent Heat 2602. 763. = 18.99 kW
EFFECTIVE ROOM TOTAL HEAT 50415. 14784. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 4.76 TR
Sensible 225 CFM x 31 F x CF x 1.08 6623. 1942. 12000 = 57.16 MBH
Latent 225 CFM x 34.5 Gr/Lb x CF x 0.68 4641. 1361. = 16.76 kW
OUTSIDE AIR TOTAL HEAT 11264. 3303. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 104
Sub Total 61679. 18088. Btu/Hour Per SqFt = 115
Factor 5.0% 3084. 904. Dehumidified CFM Per SqFt = 4.48
GRAND TOTAL HEAT 64763. 18992. Dehumidified CFM Per TR = 466

Page 3 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE MR1
CLIENT EC AREA ( SqFt) 84
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 1008
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 5.0 = 15
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.06 = 5
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 17
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 17
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N SqFt x 29.0 F x 1 x 0.45 . . Occupancy (Nos.) = 3.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.50
Wall - E SqFt x 31.0 F x 1 x 0.45 . . Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 0.5
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.93
Wall - W 118. SqFt x 45.0 F x 1 x 0.45 2390. 701. Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.8
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition 220. SqFt x 26 F x 0.32 1830. 537. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 84. SqFt x 26 F x 0.48 1048. 307. Effective Room Sensible Heat
= 508 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 17. CFM x 31. F x BF x 1.08 67. 20. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 3. Nos. x 245 Btu/Hour Per Person 735. 216. Air Quantity
Lighting 126. SqFt x 1.50 W/SqFt x 1.25 x 3.41 806. 236. Supply Air CFM RSH / 1.08 X ⁰ F = 508
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 0.50 kW x 3410 1705. 500. Resulting ENT & LVT Conditions at Apparatus
Sub Total 8581. 2517. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 76
Factor 12.5% 1073. 315. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 9654. 2831. From Psych. Chart: TEWB 63.1 ⁰ F TLWDB 62.1 ⁰ F
ROOM LATENT HEAT
Ventillation 17. CFM x 35. Gr/Lb x BF x 0.63 47. 14.
People 3. Nos. x 205. Btu/Hour Per Person 615. 180. TOTAL HEAT CAPACITY
Sub Total 662. 194. Grand Total Heat = 0.98 TR
Factor 5.0% 33. 10. 12000 = 11.75 MBH
Effective Room Latent Heat 695. 204. = 3.45 kW
EFFECTIVE ROOM TOTAL HEAT 10349. 3035. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 0.89 TR
Sensible 17 CFM x 31 F x CF x 1.08 495. 145. 12000 = 10.66 MBH
Latent 17 CFM x 34.5 Gr/Lb x CF x 0.68 347. 102. = 3.13 kW
OUTSIDE AIR TOTAL HEAT 842. 247. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 86
Sub Total 11191. 3282. Btu/Hour Per SqFt = 140
Factor 5.0% 560. 164. Dehumidified CFM Per SqFt = 6.05
GRAND TOTAL HEAT 11751. 3446. Dehumidified CFM Per TR = 519

Page 4 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE MR2
CLIENT EC AREA ( SqFt) 86
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 1032
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 5.0 = 10
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.06 = 5
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 17
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 17
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N SqFt x 29.0 F x 1 x 0.45 . . Occupancy (Nos.) = 2.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.10
Wall - E 118. SqFt x 31.0 F x 1 x 0.45 1646. 483. Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 0.2
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.94
Wall - W SqFt x 45.0 F x 1 x 0.45 . . Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.8
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition 224. SqFt x 26 F x 0.32 1864. 547. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 86. SqFt x 26 F x 0.48 1073. 315. Effective Room Sensible Heat
= 371 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 17. CFM x 31. F x BF x 1.08 69. 20. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 2. Nos. x 245 Btu/Hour Per Person 490. 144. Air Quantity
Lighting 95. SqFt x 1.10 W/SqFt x 1.25 x 3.41 444. 130. Supply Air CFM RSH / 1.08 X ⁰ F = 371
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 0.20 kW x 3410 682. 200. Resulting ENT & LVT Conditions at Apparatus
Sub Total 6268. 1838. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 76
Factor 12.5% 783. 230. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 7051. 2068. From Psych. Chart: TEWB 63.3 ⁰ F TLWDB 62.3 ⁰ F
ROOM LATENT HEAT
Ventillation 17. CFM x 35. Gr/Lb x BF x 0.63 48. 14.
People 2. Nos. x 205. Btu/Hour Per Person 410. 120. TOTAL HEAT CAPACITY
Sub Total 458. 134. Grand Total Heat = 0.73 TR
Factor 5.0% 23. 7. 12000 = 8.81 MBH
Effective Room Latent Heat 481. 141. = 2.58 kW
EFFECTIVE ROOM TOTAL HEAT 7533. 2209. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 0.66 TR
Sensible 17 CFM x 31 F x CF x 1.08 507. 149. 12000 = 7.94 MBH
Latent 17 CFM x 34.5 Gr/Lb x CF x 0.68 355. 104. = 2.33 kW
OUTSIDE AIR TOTAL HEAT 862. 253. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 117
Sub Total 8394. 2462. Btu/Hour Per SqFt = 102
Factor 5.0% 420. 123. Dehumidified CFM Per SqFt = 4.31
GRAND TOTAL HEAT 8814. 2585. Dehumidified CFM Per TR = 505

Page 5 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE MR3
CLIENT EC AREA ( SqFt) 68
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 816
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 5.0 = 10
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.06 = 4
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 14
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 14
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N SqFt x 29.0 F x 1 x 0.45 . . Occupancy (Nos.) = 2.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.10
Wall - E SqFt x 31.0 F x 1 x 0.45 . . Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 0.2
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.93
Wall - W 95. SqFt x 45.0 F x 1 x 0.45 1924. 564. Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.7
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition 98. SqFt x 26 F x 0.32 815. 239. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 68. SqFt x 26 F x 0.48 849. 249. Effective Room Sensible Heat
= 306 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 14. CFM x 31. F x BF x 1.08 55. 16. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 2. Nos. x 245 Btu/Hour Per Person 490. 144. Air Quantity
Lighting 75. SqFt x 1.10 W/SqFt x 1.25 x 3.41 351. 103. Supply Air CFM RSH / 1.08 X ⁰ F = 306
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 0.20 kW x 3410 682. 200. Resulting ENT & LVT Conditions at Apparatus
Sub Total 5165. 1515. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 76
Factor 12.5% 646. 189. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 5811. 1704. From Psych. Chart: TEWB 63.3 ⁰ F TLWDB 62.3 ⁰ F
ROOM LATENT HEAT
Ventillation 14. CFM x 35. Gr/Lb x BF x 0.63 38. 11.
People 2. Nos. x 205. Btu/Hour Per Person 410. 120. TOTAL HEAT CAPACITY
Sub Total 448. 131. Grand Total Heat = 0.61 TR
Factor 5.0% 22. 7. 12000 = 7.31 MBH
Effective Room Latent Heat 471. 138. = 2.14 kW
EFFECTIVE ROOM TOTAL HEAT 6281. 1842. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 0.54 TR
Sensible 14 CFM x 31 F x CF x 1.08 401. 118. 12000 = 6.52 MBH
Latent 14 CFM x 34.5 Gr/Lb x CF x 0.68 281. 82. = 1.91 kW
OUTSIDE AIR TOTAL HEAT 681. 200. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 112
Sub Total 6963. 2042. Btu/Hour Per SqFt = 108
Factor 5.0% 348. 102. Dehumidified CFM Per SqFt = 4.50
GRAND TOTAL HEAT 7311. 2144. Dehumidified CFM Per TR = 502

Page 6 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE WORKSTATION
CLIENT EC AREA ( SqFt) 176
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 2112
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 5.0 = 70
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.06 = 11
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 35
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 70
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N SqFt x 29.0 F x 1 x 0.45 . . Occupancy (Nos.) = 14.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.10
Wall - E SqFt x 31.0 F x 1 x 0.45 . . Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 1.0
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.86
Wall - W 254. SqFt x 45.0 F x 1 x 0.45 5144. 1508. Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.3
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition 250. SqFt x 26 F x 0.32 2080. 610. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 176. SqFt x 26 F x 0.48 2196. 644. Effective Room Sensible Heat
= 1033 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 70. CFM x 31. F x BF x 1.08 281. 82. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 14. Nos. x 245 Btu/Hour Per Person 3430. 1006. Air Quantity
Lighting 194. SqFt x 1.10 W/SqFt x 1.25 x 3.41 908. 266. Supply Air CFM RSH / 1.08 X ⁰ F = 1033
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 1.00 kW x 3410 3410. 1000. Resulting ENT & LVT Conditions at Apparatus
Sub Total 17449. 5117. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 77
Factor 12.5% 2181. 640. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 19630. 5757. From Psych. Chart: TEWB 63.6 ⁰ F TLWDB 62.6 ⁰ F
ROOM LATENT HEAT
Ventillation 70. CFM x 35. Gr/Lb x BF x 0.63 197. 58.
People 14. Nos. x 205. Btu/Hour Per Person 2870. 842. TOTAL HEAT CAPACITY
Sub Total 3067. 899. Grand Total Heat = 2.31 TR
Factor 5.0% 153. 45. 12000 = 27.68 MBH
Effective Room Latent Heat 3220. 944. = 8.12 kW
EFFECTIVE ROOM TOTAL HEAT 22850. 6701. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 1.90 TR
Sensible 70 CFM x 31 F x CF x 1.08 2062. 605. 12000 = 22.78 MBH
Latent 70 CFM x 34.5 Gr/Lb x CF x 0.68 1445. 424. = 6.68 kW
OUTSIDE AIR TOTAL HEAT 3508. 1029. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 76
Sub Total 26358. 7730. Btu/Hour Per SqFt = 157
Factor 5.0% 1318. 386. Dehumidified CFM Per SqFt = 5.87
GRAND TOTAL HEAT 27676. 8116. Dehumidified CFM Per TR = 448

Page 7 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE LIVING & KITCHEN
CLIENT EC AREA ( SqFt) 315
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 3780
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 7.5 = 45
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.12 = 38
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 63
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 63
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N 167. SqFt x 29.0 F x 1 x 0.45 2179. 639. Occupancy (Nos.) = 6.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.10
Wall - E 272. SqFt x 31.0 F x 1 x 0.45 3794. 1113. Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 1.0
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.93
Wall - W SqFt x 45.0 F x 1 x 0.45 . . Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.8
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition 250. SqFt x 26 F x 0.32 2080. 610. (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 315. SqFt x 26 F x 0.48 3931. 1153. Effective Room Sensible Heat
= 1109 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 63. CFM x 31. F x BF x 1.08 253. 74. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 6. Nos. x 245 Btu/Hour Per Person 1470. 431. Air Quantity
Lighting 347. SqFt x 1.10 W/SqFt x 1.25 x 3.41 1625. 476. Supply Air CFM RSH / 1.08 X ⁰ F = 1109
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 1.00 kW x 3410 3410. 1000. Resulting ENT & LVT Conditions at Apparatus
Sub Total 18743. 5496. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 77
Factor 12.5% 2343. 687. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 21086. 6183. From Psych. Chart: TEWB 63.5 ⁰ F TLWDB 62.5 ⁰ F
ROOM LATENT HEAT
Ventillation 63. CFM x 35. Gr/Lb x BF x 0.63 177. 52.
People 6. Nos. x 205. Btu/Hour Per Person 1230. 361. TOTAL HEAT CAPACITY
Sub Total 1407. 413. Grand Total Heat = 2.25 TR
Factor 5.0% 70. 21. 12000 = 27.01 MBH
Effective Room Latent Heat 1478. 433. = 7.92 kW
EFFECTIVE ROOM TOTAL HEAT 22563. 6617. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 2.01 TR
Sensible 63 CFM x 31 F x CF x 1.08 1856. 544. 12000 = 24.09 MBH
Latent 63 CFM x 34.5 Gr/Lb x CF x 0.68 1301. 381. = 7.06 kW
OUTSIDE AIR TOTAL HEAT 3157. 926. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 140
Sub Total 25720. 7543. Btu/Hour Per SqFt = 86
Factor 5.0% 1286. 377. Dehumidified CFM Per SqFt = 3.52
GRAND TOTAL HEAT 27006. 7920. Dehumidified CFM Per TR = 493

Page 8 of 9
AC HEAT LOAD ESTIMATE

PROJECT HYDERABAD EC FLOOR GRD FLR


LOCATION HYDERABAD SPACE REFERENCE MRB
CLIENT EC AREA ( SqFt) 125
HCL BY ALFA AIR CONDITIONING Height (Ft) 12.0
DATE 05-01-2022 Volume (CuFt) 1500
Area or Sun Gain or Estimate for Summer
Item U-Factor Btu/Hr W
Quantity Temp. Diff. Design Conditions DB (F) WB (F) RH (%) Gr/Lb
INSIDE AREA HEAT Ambient 106 78 28 99.5
INSIDE AREA SENSIBLE HEAT Room 75 62.6 50 65
Solar Gain - Glass Difference 31 xxx xxx 34.5
Glass - N SqFt x 23 x 1 x 0.65 . . Daily Range (F) = 14
Glass - NE SqFt x 12 x 1 x 0.65 . . Correction for Temp. Diff. (F) = 19
Glass - E SqFt x 12 x 1 x 0.65 . . By Pass Factor (BF) = 0.12
Glass - SE SqFt x 12 x 1 x 0.65 . . Contact Factor (CF = 1 - BF) = 0.88
Glass - S SqFt x 12 x 1 x 0.65 . . Outside Air
Glass - SW SqFt x 85 x 1 x 0.65 . . CFM Per Person 5.0 = 15
Glass - W SqFt x 163 x 1 x 0.65 . . CFM Per SqFt 0.06 = 8
Glass - NW SqFt x 138 x 1 x 0.65 . . Air Change Per Hour (CFM) 1.00 = 25
Skylight SqFt x 118 x 1 x 0.65 . . Ventillation (CFM) - = 25
Solar & Transmission Gain - Walls & Roof Internal Loads
Wall - N 141. SqFt x 29.0 F x 1 x 0.45 1840. 540. Occupancy (Nos.) = 3.0
Wall - NE SqFt x 31.0 F x 1 x 0.45 . . Lighting (W/SqFt) = 1.50
Wall - E 124. SqFt x 31.0 F x 1 x 0.45 1730. 507. Lighting & Small Power (W/SqFt) = -
Wall - SE SqFt x 37.0 F x 1 x 0.45 . . Equipment Load (kW) = 0.5
Wall - S SqFt x 45.0 F x 1 x 0.45 . . Effective Room Sensible Heat Factor =
Wall - SW SqFt x 51.0 F x 1 x 0.45 . . Effective Room Sensible Heat = 0.93
Wall - W SqFt x 45.0 F x 1 x 0.45 . . Effective Room Total Heat
Wall - NW SqFt x 31.0 F x 1 x 0.45 . . Apparatus Dew Point (ADP)
Roof SqFt x 57.0 F x 1 x 0.48 . . Indicated ADP (F) = 54.8
Transmission Gain - Except Walls & Roof Selected ADP (F) = 55.0
All Glass . SqFt x 31 F x 1.13 . . Dehumidified Rise
Partition SqFt x 26 F x 0.32 . . (Room DB - ADP) x CF = 17.60
Ceiling SqFt x 26 F x 0.32 . . DEHUMIDIFIED AIR QUANTITY
Floor 125. SqFt x 26 F x 0.48 1560. 457. Effective Room Sensible Heat
= 525 CFM
Outside Air Dehumidified Rise x 1.08
Ventillation 25. CFM x 31. F x BF x 1.08 100. 29. Outlet Temp. Diff
Internal Heat RSH / 1.08 x Dehumidified CFM = 17.60
People 3. Nos. x 245 Btu/Hour Per Person 735. 216. Air Quantity
Lighting 188. SqFt x 1.50 W/SqFt x 1.25 x 3.41 1199. 352. Supply Air CFM RSH / 1.08 X ⁰ F = 525
Lighting & S. P. SqFt x 0.0 W/SqFt x 1 x 3.41 . . Bypass CFM CFMSA - CFMOA = 0
Equipment 0.50 kW x 3410 1705. 500. Resulting ENT & LVT Conditions at Apparatus
Sub Total 8869. 2601. EDB = TRM ⁰ F +( CFM OA / CFM+ X (TOA⁰ F - TRM⁰ F)) = 76
Factor 12.5% 1109. 325. LDB = TADP⁰F + (BF X (TEDB - TADP⁰F)) = 74
Effective Room Sensible Heat 9978. 2926. From Psych. Chart: TEWB 63.3 ⁰ F TLWDB 62.3 ⁰ F
ROOM LATENT HEAT
Ventillation 25. CFM x 35. Gr/Lb x BF x 0.63 70. 21.
People 3. Nos. x 205. Btu/Hour Per Person 615. 180. TOTAL HEAT CAPACITY
Sub Total 685. 201. Grand Total Heat = 1.05 TR
Factor 5.0% 34. 10. 12000 = 12.55 MBH
Effective Room Latent Heat 720. 211. = 3.68 kW
EFFECTIVE ROOM TOTAL HEAT 10697. 3137. SENSIBLE HEAT CAPACITY
OUTSIDE AIR HEAT Grand Sensible Heat = 0.94 TR
Sensible 25 CFM x 31 F x CF x 1.08 737. 216. 12000 = 11.25 MBH
Latent 25 CFM x 34.5 Gr/Lb x CF x 0.68 516. 151. = 3.30 kW
OUTSIDE AIR TOTAL HEAT 1253. 367. Check Figures:
GRAND TOTAL HEAT SqFt Per TR = 120
Sub Total 11950. 3504. Btu/Hour Per SqFt = 100
Factor 5.0% 598. 175. Dehumidified CFM Per SqFt = 4.20
GRAND TOTAL HEAT 12548. 3680. Dehumidified CFM Per TR = 502

Page 9 of 9