Detection ,Evaluation & Recommendations


1- Evaluation : Fault Codes

Results of analysis indicates ,according to IEC 60599-2007 &IEEE C57.104-2008 :

N Normal
PD Partial Discharge
D1 Discharges of low Energy
D2 Discharges of High Energy
T1 Thermal Fault ,t < 300 ° C
T2 Thermal Fault ,300 ° C< t < 700 < ° C
T3 Thermal Fault ,t > 700 ° C
DT Mix of thermal & electrical fault

2- Detection :TDCG Codes


As Per IEEE C57.104-2008,TDCG indicates :

Good ,Normal ,No action required ,


1
Continual normal operation
2 Greater Than Normal Level , Faults may be persent

3 High Level of Decomposition, Faults are Porbably Present

4 Excessive Decomposition, Immediate action

3- Recommended : Action Codes

A Annual Sample
S Repeat Sample
F Filtered Oil