Tankfarm - Types, Design Considerations, Plot Plan Arrangement, Dyke Enclosure

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Search...

Piping Engineering – Knowledge base

HOME INTRODUCTION CHECKLISTS VALVE COMPONENTS USED IN PIPING PDMS HOW TO PIPING LAYOUT

Tank farm: Types, Design Considerations, Plot Plan


Arrangement, Dyke Enclosure- Part 1

I. Introduction to tankfarm:
The use of tanks is common in all kinds of plants found in oil & gas industry.

1. Process Plant
1. Refineries
2. Petrochemicals
3. Specialty chemicals

2. Terminals
3. Administration buildings
4. Material Handling Plants

Storage tank are containers used for storage of fluids for the short or long term. Cluster of tanks together in
a same are termed as “Tank Farms”.

II.        Types of Tanks:


Types of Tanks in Process plant depend on the product to be stored, potential for fire, and capacity to be
handled.

Cone roof tank:


Used for countless products including Petroleum, Chemicals, Petrochemicals, Food products & Water

Floating roof tank:


The roof of tank rises and lowers with the stored contents thereby reducing vapour loss & minimizing fire
hazard. Commonly found in Oil refineries.

Low temperature storage tank:


Tanks stores liquefied gases at their boiling point. Products found in such tanks include Ammonia (-28
°F), Propane (-43.7 °F) and Methane (-258°F).

Horizontal pressure tank (Bullet):


Used to store products under high pressure.

Hortonsphere pressure tank:


Handles large capacity under high pressure.
:
Underground Tanks:
Commonly used for drain collection of the plant at atmospheric pressure.

FRP Tanks:
Commonly used for corrosive fluid at atmospheric pressure.

Cone roof, floating roof, horizontal pressure tanks

Low temperature storage tank, hortonsphere pressure tank


:
U/GTanks
UndergroundTanks ValvePit

U/Gpit

Underground tanks

III.        Design Considerations for Tankfarm


Layout:
Below considerations are to taken into account while designing a Tankfarm for Process plants:

General considerations:
Local codes and regulations
Client specification
Topography
Adjacent process units
Neighbouring commercial and residential property
Maintenance and operation

Detail design:
Identification of storage based on fluid stored.
Safety considerations/Statutory requirements
General / Plot plan arrangement
General piping layout
Material of Construction.

Statutory and Safety Requirements:


Following are the key statutory requirements (India). However these are to be relooked based on
geographical location:

1. OISD -118 ( Plant Layout )


2. OISD -116 / 117 (Fire Fighting )
3. Fire Hydrant Manual & Spray Manual.
4. Factory Act of State. If Any
5. Petroleum Act 1934 (Act N0.30 of 1934) Along with The Petroleum Rules.
6. Static and Mobile Pressure Vessel (SMPV).
7. National Fire Protection Act (NFPA).

Apart from this, local rules and regulations pertaining to State and local industrial requirement should be
taken into consideration.
Safety ensures proper protection and safe operation- Lifetime.
Insurance Premium.
:
IV.        Plot Plan Arrangement for Tankfarm
Hydrocarbon processing and handling plants are inherently hazardous involving large and complex
processes and substantial risk potential; hence a careful consideration shall be given while developing a
plot plan.
Plot plan is a spatial arrangement of equipment considering proper flow sequence, system grouping,
safety, statutory requirements, maintenance, operation, erection and construction with logistical
economy.
General classification of petroleum products for storage.

1. Class – A: Flash Point below 23 °C


2. Class – B: Flash Point of 23 °C & above but below 65 °C.
3. Class – C: Flash Point of 65 °C & above but below 93 °C.
4. Excluded Petroleum class: Flash Point of 930 °C & above.
5. LPG doesn’t fall under this classification but form separate category.

Grouping of petroleum products for storage shall be based on product classification.


Classification based on capacity and diameter:

1. Larger installations: Aggregate capacity of Class A and Class B petroleum product is more than 5000
cu.m or diameter of Class A or Class B product tank is more than 9m.
2. Smaller installations: Aggregate capacity of Class A and Class B petroleum product is less than 5000
cu.m or diameter of Class A or Class B product tank is less than 9m.

The storage tanks shall be located at lower elevation, wherever possible.


The storage tanks should be located downwind of process units.
Due to risk of failure of storage tanks and primary piping systems, means must be provided to contain
the spills. The containment for petroleum storage tanks is in the form of Dyked enclosures.

AINTENANCE

PRocl
ㅇ이

우유

RAILLORDI

Fig:OverallProcess&Off-SitePlotPlan
TankFarm

Tank farms in overall process off site plot plan

V.        Dyke Enclosure


Aggregate capacity in one dyke enclosure:

1. Group of Fixed roof tanks: Upto 60,000 m3


2. Group of Floating roof tanks: Upto 120,000 m3
3. Fixed cum floating roof tanks shall be treated as fixed roof tanks.
4. Group containing both Fixed roof tanks & Floating roof tanks, shall be treated as fixed roof tanks.

Class – A and / or Class – B petroleum products :- Same dyked enclosure


Class – C: – Preferably separate dyked enclosures.
Tanks shall be arranged in maximum two rows. Tanks having 50,000 m3 capacities and above shall be
:
laid in single row.
The tank height shall not exceed one and half times the diameter of the tank or 20 m whichever is less.
The minimum distance between a tank shell and the inside toe of the dyke wall shall not be less than
half the height of the tank.
Dyked enclosure for petroleum class shall be able to contain the complete contents of the largest tank in
the dyke in case of any emergency.

1. Height of Dyke (H): 1m < H < 2m


2. Width of Dyke (W): Minimum 0.6m (Earthen dyke) Not Specific (RCC dyke)

W
ABOVEINTERIOR
VARIES

EarthenDike

BRUIDED

ConcreteDike

Fig:EarthenDyke&ConcreteDyke

Earthen dyke and concrete dyke

Double containment dyke and earthern and concrete combination dyke

Separation distances between the nearest tanks located in separate dykes shall not be less than the
diameter of the larger of the two tanks or 30 meters, whichever is more.
All process units and dyked enclosures of storage tanks shall be planned in separate blocks with roads
all around for access and safety.
In a dyked enclosure where more than one tank is located, firewalls of minimum height 600mm shall be
provided to prevent spills from one tank endangering any other tank in the same enclosure.
:
Typical tank farm arrangement


For larger installation, minimum separation distances shall be as specified in following tables.

Table 1: Inter unit Distances for large installations (D>9m or Agg. Cap > 5000cu.m)
Tanks/Facility 123456?

StorageTankfor T4T415 151515815 0.5D


PetroleumClassA/Class
B.
Win20m

2 StorageTankfor T4x15x8x X 0.5D


PetroleumClassC
Min20m
3 Storage/FillingShedfor|15 15 07171T 15 15
petroleumClassAor
classB

Storage/FillingShedfor I*78787 8 10
PetroleumClassC
Tankvehicleloading/ 15 8 8 15 20
Unloadingforpetroleum
classAorclassB

б TankVehicleloading/ 15 15 10
unloadingforClassC

7 FlameproofElectric 8 8
Motor

8 Nonflameproofelectric 15 ※ 15 15X 8 X
Motor

9 Boundarywall 05D05D 15 10 20 10 X X
Min20Min20

Table T4: Tank to tank distance within same Dyke

Table T4: Tank to tank distance within same Dyke

Notes for Table 1:


:
Table 1 notes

Table 2: Interunit Distances for smaller installations (D<9m or Agg. Cap < 5000cu.m)

Table 2: Interunit Distances for smaller installations (D<9m or Agg. Cap < 5000cu.m)

Continue part 2 >>

6 COMMENTS

buildtrade
August 28, 2014 at 8:03 am

Hi,

How to decide the storage Tank design Pressure and Vacuum?

The following are given:

1. Temp.
2. Filling rate m3/min
3. Emptying rate m3/min
4. Service liquid properties, ex. Diesel

In the API std. 2.5 psig is mentioned but in the above datas, I believe that there is a formula of
deciding Press and Vac for the data sheet.

At API 2000, we can decide only the venting capacity but we are not sure yet the safety relief valve
Vendors the we cannot decide the Press and Vac to be used in our design.

Does, anybody an help me out?

Piping engineering
August 28, 2014 at 8:04 am

Hi there,

Please refer to some related articles here which may help-

http://www.piping-engineering.com/pressure-vacuum-relief-valves-part-1.html
:
http://www.piping-engineering.com/pressure-vacuum-relief-valves-part-2.html

Cheers
AJ

mohanrao.k
November 21, 2014 at 8:04 am

The
articles are given as very useful information
NIce.

Harshit
December 12, 2014 at 4:36 pm

Flash point temperature for fluid should be 23 65 and 93 C instead of 230 650 and 930C

Piping engineering
December 19, 2014 at 11:13 am

Hi Harshit,
Thank you for suggesting correction. I have updated the flash point temperatures.
Much appreciated.
Regards,
AJ

Gajendrasingh Rajput
March 17, 2015 at 7:23 pm

NFPA 30 and API 2030 shall be followed for tank farm fire protection system.

Copyright 2023
:

You might also like