WWW - Burner.ir: Siemens Building Technologies HVAC Products 1
WWW - Burner.ir: Siemens Building Technologies HVAC Products 1
WWW - Burner.ir: Siemens Building Technologies HVAC Products 1
ﻛﺎﺭﺑﺮﺩﻫﺎ :
ﻛﻨﺘﺮﻝ ﻭ ﻧﻈﺎﺭﺕ ﺩﻗﻴﻖ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﺩﻣﻨﺪﻩ ﺩﺍﺭ ﺍﺯ ﻣﺮﺣﻠﻪ ﺗﺸﻜﻴﻞ ﺷﻌﻠﻪ ﭘﻴﻠﻮﺕ ﺗﺎ ﺯﻣﺎﻥ ﮔﺴﺘﺮﺵ ﻧﻬﺎﻳﻲ ﺷﻌﻠﻪ ﻭ ﺗﺸﻜﻴﻞ ﺷﻌﻠﻪ ﺍﺻﻠﻲ
ﻗﺎﺑﻞ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﺍﺯ ﻇﺮﻓﻴﺖ ﻣﺘﻮﺳﻂ ﺑﻪ ﺑﺎﻻ
ﻗﺎﺑﻞ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﺑﺎ ﻓﻌﺎﻟﻴﺘﻬﺎﻱ ﻣﺘﻨﺎﻭﺏ ) ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﺸﻌﻞ ﻣﻴﺒﺎﻳﺴﺖ ﺣﺪﺍﻗﻞ ﻳﻜﺒﺎﺭ ﺩﺭ 24ﺳﺎﻋﺖ Shut downﺷﻮﺩ(.
ﻗﺎﺑﻞ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﭼﻨﺪ ﻣﺮﺣﻠﻪ ﺍﻱ ﻭ ﻳﺎ ﺗﺪﺭﻳﺠﻲ
ﻗﺎﺑﻞ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﺩﻭﮔﺎﻧﻪ ﺳﻮﺯ
ﻗﺎﺑﻞ ﺍﺳﺘﻔﺎﺩﻩ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﻫﻮﺍﻱ ﮔﺮﻡ ﺍﻳﺴﺘﺎﺩﻩ
ﺗﻔﺎﻭﺕ ﺑﻴﻦ ﺭﻟﻪ ﻫﺎﻱ ﺳﺮﻱ 01ﻭ 02ﻣﺮﺑﻮﻁ ﺑﻪ ﺍﺧﺘﻼﻑ ﺯﻣﺎﻥ ﺍﻳﻤﻨﻲ ﭘﻴﻠﻮﺗﻬﺎ ﺩﺭ ﻣـﺸﻌﻠﻬﺎﻱ ﺩﺍﺭﺍﻱ ﺷـﻴﺮﻫﺎﻱ ﺑﺮﻗـﻲ ﻣﺠـﺰﺍﻱ ﺧـﻂ ﮔـﺎﺯ
ﭘﻴﻠﻮﺕ ﻣﻴﺒﺎﺷﺪ.
ﺑﺮﺍﻱ ﻣﺸﻌﻠﻬﺎﻱ ﺍﺗﻤﺴﻔﺮﻳﻚ ﺑﺎ ﻇﺮﻓﻴﺘﻬﺎﻱ ﺑﺎﻻ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺭﻟﻪ ﺗﻴﭗ LFL1.638ﺗﻮﺻﻴﻪ ﻣﻴﮕﺮﺩﺩ.
ﺑﺮﺍﻱ ﻛﻨﺘﺮﻝ ﻣﺸﻌﻠﻬﺎﻳﻲ ﺑﺎ ﻛﺎﺭﻛﺮﺩ ﻣﺪﺍﻭﻡ ﺑﻪ ﺩﻳﺘﺎﺷﻴﺖ ( LKG16… ) 7785ﻣﺮﺍﺟﻌﻪ ﮔﺮﺩﺩ .
ﺭﻳﺴﺖ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ) ﺭﻳﺴﺖ ﺍﺯ ﺭﻭﻱ ﺗﺎﺑﻠﻮ ﺑﺮﻕ ( -ﺯﻣﺎﻧﻲ ﻛﻪ ﺭﻳﺴﺖ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺗﻮﺳﻂ ﻛﻠﻴﺪ EK2ﺗﺤﺮﻳﻚ ﻣﻴﺸﻮﺩ:
ﺩﺭ ﺗﺮﻣﻴﻨﺎﻝ 3ﻓﻘﻂ ﺭﻳﺴﺖ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﻣﻘﺪﻭﺭ ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﺩﺭ ﺗﺮﻣﻴﻨﺎﻝ ،1ﻫﻢ ﺧﺎﻣﻮﺵ ﻧﻤﻮﺩﻥ ﺍﺿﻄﺮﺍﺭﻱ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﻭ ﻫﻢ ﺭﻳﺴﺖ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﻣﻘﺪﻭﺭ ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﻇﺮﻓﻴﺖ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺳﻮﺋﻴﭽﻴﻨﮓ:
ﻣﺮﺗﺒﻂ ﺑﺎ ﺗﺠﻬﻴﺰﻱ ﻛﻪ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ 12ﻭ 4ﻣﺘﺼﻞ ﺷﺪﻩ ﺍﺳﺖ ) .ﺑﻪ ﺩﻳﺘﺎ ﺷﻴﺖ ﻓﻨﻲ ﻣﺮﺍﺟﻌﻪ ﮔﺮﺩﺩ (
ﻣﺮﺗﺒﻂ ﺑﺎ ﺗﺠﻬﻴﺰﻱ ﻛﻪ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ 4ﻭ 14ﻣﺘﺼﻞ ﺷﺪﻩ ﺍﺳﺖ ) .ﺑﻪ ﺩﻳﺘﺎ ﺷﻴﺖ ﻓﻨﻲ ﻣﺮﺍﺟﻌﻪ ﮔﺮﺩﺩ (
ﻭﺍﺑﺴﺘﻪ ﺑﻪ ﻣﻴﺰﺍﻥ ﺑﺎﺭﻱ ﺍﺳﺖ ﻛﻪ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ ﻭ ﺍﺯ ﻃﺮﻳﻖ ﭘﺎﻳﻪ ﻫﺎﻱ 16ﺍﻟﻲ 19ﺑﺎﺭﮔﺬﺍﺭﻱ ﻣﻴﺸﻮﺩ ) .ﺑﻪ ﺩﻳﺘﺎ ﺷﻴﺖ ﻓﻨﻲ ﻣﺮﺍﺟﻌﻪ ﮔﺮﺩﺩ (
ﭘﺎﻳﺶ ﭘﺮﺷﺮ ﺳﻮﺋﻴﭻ ﻫﻮﺍ :
ﺩﺭ ﺻﻮﺭﺗﻴﻜﻪ ﻓﺸﺎﺭ ﻫﻮﺍ ﺗﻮﺳﻂ ﻫﻴﭽﮕﻮﻧﻪ ﺗﺠﻬﻴﺰﻱ ) ﻫﻤﭽﻮﻥ ﭘﺮﺷﺮ ﺳﻮﺋﻴﭻ ﻫﻮﺍ( ﻛﻨﺘﺮﻝ ﻧﻤﻴﺸﻮﺩ ،ﺗﺮﻣﻴﻨﺎﻝ 4ﻣﻴﺒﺎﻳﺴﺖ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ 12ﻣﺘﺼﻞ ﻭ ﺗﺮﻣﻴﻨﺎﻝ 6ﺑـﻪ 14ﻣﺘـﺼﻞ ﺷـﻮﺩ .ﺗﺮﻣﻴﻨـﺎﻝ 13ﺑـﻼ
ﺍﺳﺘﻔﺎﺩﻩ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ .
ﭘﺎﻳﻪ ﻫﺎﻱ ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﺑﺎﻗﻲ ﺗﺠﻬﻴﺰﺍﺕ ﻣﺸﻌﻞ ﻣﺘﺼﻞ ﺧﻮﺍﻫﺪ ﺷﺪ -ﺩﺭﺻﻮﺭﺗﻴﻜﻪ ﺑﺼﻮﺭﺕ ﺳﺮﻱ ﺑﻴﻜﺪﻳﮕﺮ ﻣﺘﺼﻞ ﺑﺎﺷﻨﺪ ،ﺑﺼﻮﺭﺕ ﺯﻳﺮ ﺑﻴﻜﺪﻳﮕﺮ ﻣﺘﺼﻞ ﺧﻮﺍﻫﻨﺪ ﮔﺮﺩﻳﺪ:
ﺑﻪ ﭘﺎﻳﻪ 4ﻳﺎ 5ﺍﺗﺼﺎﻻﺕ ﻣﻴﺒﺎﻳﺴﺖ ﺍﺯ ﺯﻣﺎﻥ ﺷﺮﻭﻉ ﺗﺎ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﻛﻨﺘﺮﻝ ﺷﺪﻩ ،ﺑﺴﺘﻪ ﺑﺎﺷﻨﺪ ﺩﺭ ﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ﻣﺸﻌﻞ ﺭﻭﺷﻦ ﻭ ﻳﺎ ﺧﺎﻣﻮﺵ ﻧﺨﻮﺍﻫﺪ ﺷﺪ.
ﺑﻪ ﭘﺎﻳﻪ 12ﺍﺗﺼﺎﻻﺕ ﻣﻴﺒﺎﻳﺴﺖ ﺩﺭ ﺯﻣﺎﻥ ﺷﺮﻭﻉ ﺑﺴﺘﻪ ﺑﺎﺷﻨﺪ ﺩﺭ ﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ﻣﺸﻌﻞ ﺭﻭﺷﻦ ﻧﺨﻮﺍﻫﺪ ﺷﺪ .
ﺑﻪ ﭘﺎﻳﻪ 14ﺍﺗﺼﺎﻻﺕ ﻣﻴﺒﺎﻳﺴﺖ ﺍﺯ ﺯﻣﺎﻥ ﭘﻴﺶ ﺟﺮﻗﻪ ﺑﺴﺘﻪ ﺑﺎﺷﻨﺪ ﻭ ﺗﺎ ﺯﻣﺎﻥ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﻛﻨﺘﺮﻝ ﺷﺪﻩ ﺩﺭ ﻫﻤﻴﻦ ﺣﺎﻟﺖ ﺑﺎﻗﻲ ﺑﻤﺎﻧﻨﺪ ﺩﺭ ﻏﻴـﺮ ﺍﻳﻨـﺼﻮﺭﺕ ﻓﺎﻟـﺖ Louck out
ﺍﺗﻔﺎﻕ ﺧﻮﺍﻫﺪ ﺍﻓﺘﺎﺩ.ﺍﻳﻦ ﻣﺴﺌﻠﻪ ﺩﺭ ﺧﺼﻮﺹ ﻫﺮ ﺩﻭﻱ ﭘﻴﺶ ﺟﺮﻗﻪ ﻫﺎﻱ ﺑﻠﻨﺪ ﻭ ﻛﻮﺗﺎﻩ ﺻﺎﺩﻕ ﻣﻴﺒﺎﺷﺪ.
ﺍﺗﺼﺎﻝ ﺷﻴﺮﻫﺎﻱ ﺳﻮﺧﺖ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ) .( expanding flame burnerﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﺩﻭ ﻣﺮﺣﻠﻪ ﺍﻱ ﺷﻴﺮ BV2ﺑﺠﺎﻱ BV3ﻣﺘﺼﻞ ﺧﻮﺍﻫﺪ ﺷﺪ.
ﺍﺗﺼﺎﻻﺕ ﺷﻴﺮﻫﺎﻱ ﺳﻮﺧﺖ ﺩﺭ ﻣﺸﻌﻠﻬﺎﻱ ﭘﻴﻠﻮﺕ ﻣﻨﻘﻄﻊ ) ( Interrupted pilot burner
ﺍﺗﺼﺎﻝ ﻣﺴﺘﻘﻴﻢ ﺷﻴﺮﻫﺎﻱ ﺳﻮﺧﺖ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ 20ﻓﻘﻂ ﺯﻣﺎﻧﻲ ﻣﺠﺎﺯ ﺍﺳﺖ ﻛﻪ:
ﺩﺭ ﻣﺸﻌﻠﻬﺎﻳﻲ ﻛﻪ ﺷﻴﺮ ﺍﺻﻠﻲ Shut off valveﺩﺭ ﺧﻂ ﺍﺻﻠﻲ ﻭﺟﻮﺩ ﺩﺍﺭﺩ ﻛﻪ ﺗﻮﺳﻂ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ 18ﻭ 19ﻛﻨﺘﺮﻝ ﻣﻴﺸﻮﺩ ﻭ
ﺍﮔﺮ ﺷﻴﺮﻫﺎﻱ ﺩﻭﻣﺮﺣﻠﻪ ﺍﻱ ﻣﻮﺭﺩ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻴﺒﺎﺷﺪ ،ﺑﻪ ﺷﺮﻁ ﺍﻳﻨﻜﻪ ﺁﻧﻬﺎ ﺩﺭ ﻣﺮﺣﻠﻪ ﺍﻭﻝ ﻛﺎﻣﻼ ﺑﺴﺘﻪ ﺑﺎﺷﻨﺪ،ﻭ ﺗﻮﺳﻂ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ 18ﻳﺎ 19ﻛﻨﺘﺮﻝ ﺷﻮﻧﺪ ،ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ.
ﺑﻌﻨﻮﺍﻥ ﻣﺜﺎﻝ ﺩﺭ ﻛﻨﺘﺮﻟﺮ ﺩﻣﭙﺮ ﻫﻮﺍ ،ﺩﺭ ﺻﻮﺭﺗﻴﻜﻪ ﺍﻛﭽﻮﻳﺘﻮﺭ Endswitchﻧﺪﺍﺷﺘﻪ ﺑﺎﺷﺪ)) (( Zﺑﺮﺍﻱ ﺣﺎﻟﺖ ﻛﺎﻣﻼ ﺑﺴﺘﻪ ﺩﻣﭙﺮﻫﻮﺍ ،ﺗﺮﻣﻴﻨﺎﻝ 11ﺑﺎﻳﺪ ﺑﻪ 10ﻣﺘﺼﻞ ﺑﺎﺷﺪ ﺩﺭﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ﻣﺸﻌﻞ ﻛﺎﺭ
ﻧﺨﻮﺍﻫﺪ ﻛﺮﺩ.
ﮔﻮﺍﻫﻴﻨﺎﻣﻪ :
ﻫﺮ ﺑﺎ ﺭ ﻛﻪ ﻗﺼﺪ ﺗﻌﻮﻳﺾ ﺟﻌﺒﻪ ﻛﻨﺘﺮﻝ ﻣﺸﻌﻞ ﺭﺍ ﺩﺍﺭﻳﺪ ﺍﺯ ﺻﺤﺖ ﺳﻴﻢ ﻛﺸﻲ ﻭ ﻣـﻨﻈﻢ ﺑـﻮﺩﻥ ﺁﻥ ﻣﻄـﺎﺑﻖ ﺑـﺎ ﻧﻘـﺸﻪ ﻫـﺎ ﺍﻃﻤﻴﻨـﺎﻥ ﺣﺎﺻـﻞ
ﻓﺮﻣﺎﺋﻴﺪ .ﻣﻮﺍﺭﺩ ﺍﻳﻤﻨﻲ ﺭﺍ ﺣﺘﻤﺎ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﺒﺤﺚ ) ﺍﻳﻤﻨﻲ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ( ﻣﺪ ﻧﻈﺮ ﻗﺮﺍﺭ ﺩﻫﻴﺪ .
ﺳﻔﺎﺭﺷﮕﺬﺍﺭﻱ :
ﻟﻄﻔﺎ ﺩﺭ ﺯﻣﺎﻥ ﺳﻔﺎﺭﺷﮕﺬﺍﺭﻱ ،ﺩﺭﺧﻮﺍﺳﺖ ﺧﻮﺩ ﺭﺍ ﺑﺮ ﺍﺳﺎﺱ ﻛﺪﻫﺎﻱ ﺍﺷﺎﺭﻩ ﺷﺪﻩ ﺩﺭ ﺑﺨﺶ ﻓﻮﻕ ﺗﻨﻈﻴﻢ ﻭ ﺍﺭﺳﺎﻝ ﻧﻤﺎﺋﻴﺪ.
ﻣﺘﻌﻠﻘﺎﺕ :
ﻃﺮﺍﺣﻲ ﺑﺮ ﭘﺎﻳﻪ ﻧﺼﺐ ﺳﻮﻛﺘﻲ
AGM410490550 ﺑﺎ ﺩﻧﺪﺍﻧﻪ ﻫﺎﻱ pg11ﺑﺮﺍﻱ ﮔﻠﻨﺪ ﻛﺎﺑﻠﻬﺎ
AGM14.1 ﺑﺎ ﺩﻧﺪﺍﻧﻪ ﻫﺎﻱ M16ﺑﺮﺍﻱ ﮔﻠﻨﺪ ﻛﺎﺑﻠﻬﺎ
ﺁﺷﻜﺎﺭﺳﺎﺯ ﺷﻌﻠﻪ ﺍﺯ ﻧﻮﻉ ﻣﻴﻠﻪ ﻳﻮﻧﻴﺰﺍﺳﻴﻮﻥ ﺑﺼﻮﺭﺕ ﻣﺴﺘﻘﻞ ﻭ ﺗﻮﺳﻂ ﺗﻮﻟﻴﺪ ﻛﻨﻨﺪﻩ ﻣﺠﺰﺍ ﺳﺎﺧﺘﻪ ﻣﻴﺸﻮﺩ.
ﻇﺮﻓﻴﺖ ﺳﻮﺋﻴﭽﻴﻨﮓ ﺍﺗﺼﺎﻻﺕ ﺩﺭ ﻛﻠﻴﻪ ﺍﺗﺼﺎﻻﺕ 1ﺁﻣﭙﺮ ﺑﺮﻕ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 250ﻭﻟﺖ
ﻇﺮﻓﻴﺖ ﺳﻮﺋﻴﭽﻴﻨﮓ ﺍﺗﺼﺎﻻﺕ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻝ 4ﻭ 5 1ﺁﻣﭙﺮ ﺑﺮﻕ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 250ﻭﻟﺖ
ﻇﺮﻓﻴﺖ ﺳﻮﺋﻴﭽﻴﻨﮓ ﺍﺗﺼﺎﻻﺕ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻝ 4ﻭ 12 ﻣﻴﻨﻴﻤﻢ 1ﺁﻣﭙﺮ ﺑﺮﻕ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 250ﻭﻟﺖ
ﻇﺮﻓﻴﺖ ﺳﻮﺋﻴﭽﻴﻨﮓ ﺍﺗﺼﺎﻻﺕ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻝ 4ﻭ14 ﺑﺴﺘﮕﻲ ﺑﻤﻴﺰﺍﻥ ﺟﺮﻳﺎﻥ ﺑﻴﻦ ﭘﺎﻳﻪ ﻫﺎﻱ 16ﺍﻟﻲ 19ﺩﺍﺭﺩ
ﺍﺗﺼﺎﻝ ﺳﻴﻤﻬﺎ
ﻣﺮﺑﻊ
ﻗﺮﺍﺭ ﮔﺮﻓﺘﻦ ﺗﺠﻬﻴﺰ ﺩﺭ ﻣﺠﺎﻭﺭﺕ ﺷﺮﺍﻳﻂ ﺷﺒﻨﻢ –ﻳﺦ ﺯﺩﮔﻲ ﻭ ﻭﺭﻭﺩ ﺁﺏ ﺑﻪ ﻫﻴﭻ ﻋﻨﻮﺍﻥ ﻣﺠﺎﺯ ﻧﻤﻴﺒﺎﺷﺪ .
ﻭﻟﺘﺎﮊ ﻣﻴﻠﻪ ﻳﻮﻧﻴﺰﺍﺳﻴﻮﻥ ﺩﺭ ﺯﻣﺎﻥ ﻋﻤﻠﻜﺮﺩ ﻭ ﺗﺴﺖ ﺟﺮﻳﺎﻥ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 330ﻭﻟﺖ ﺑﺎ +ـ ٪ 10ﺍﺧﺘﻼﻑ
ﻭﻟﺘﺎﮊ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺟﻬﺖ ﻋﻤﻠﻜﺮﺩ ﺟﺮﻳﺎﻥ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 330ﻭﻟﺖ ﺑﺎ +ـ ٪ 10ﺍﺧﺘﻼﻑ
ﻭﻟﺘﺎﮊ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺟﻬﺖ ﺗﺴﺖ ﺟﺮﻳﺎﻥ ﻣﺘﻨﺎﻭﺏ ﺑﺎ ﻭﻟﺘﺎﮊ 380ﻭﻟﺖ ﺑﺎ +ـ ٪ 10ﺍﺧﺘﻼﻑ
ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ
ﻣﺎﮔﺰﻳﻤﻢ 200ﻣﺘﺮ ) ﺑﺮﺍﻱ ﻣﺜﺎﻝ ﻛﺎﺑﻠﻬﺎﻱ ﻓﺮﻛﺎﻧﺲ ﺑﺎﻻ – ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﻴﺒﺎﻳﺴﺖ ﻃﻮﻝ ﻣﺠﺎﺯ ﻛﺎﺑﻠﻬﺎﻱ ﺣﺴﮕﺮ ﺩﺭﺻﻮﺭﺗﻲ ﻛﻪ ﺍﺯ ﻛﺎﺑﻠﻬﺎﻱ
ﺷﻴﻠﺪ ﺩﺍﺭ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ ﺷﻴﻠﺪﻫﺎ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ 22ﻣﺘﺼﻞ ﺷﻮﻧﺪ (
ﻋﻤﻠﻜﺮﺩ :
ﻣﺸﻌﻞ ﺩﻭ ﻣﺮﺣﻠﻪ ﺍﻱ ﭘﻴﻠﻮﺕ ﺩﺍﺋﻢ
ﺩﺭ ﻛﺎﺭ ﺑﺎ ﻣﺸﻌﻠﻬﺎﻱ ﺩﺍﺭﺍﻱ ﻛﻨﺘﺮﻟﺮ ﺳﺮﻱ 01ﻭ ﭘﻴﻠﻮﺕ ﺩﺍﺋﻢ ،ﺯﻣﺎﻥ ﺍﻳﻤﻨﻲ ﻣﻴﺘﻮﺍﻧﺪ ﺍﺯ 2.5ﺛﺎﻧﻴﻪ ﺑﻪ 5ﺛﺎﻧﻴـﻪ ﺍﺯ ﻃﺮﻳـﻖ ﺗﻐﻴﻴـﺮﺍﺕ ﺩﺭ ﻣـﺪﺍﺭ
ﺍﻟﻜﺘﺮﻳﻜﻲ ،ﺗﻐﻴﻴﺮ ﻧﻤﺎﻳﺪ ﻣﺸﺮﻭﻁ ﺑﺮ ﺍﻳﻨﻜﻪ ﺯﻣﺎﻥ ﺍﻳﻤﻨﻲ ﻃﻮﻻﻧﻲ ﺗﺮ ﻣﻄﺎﺑﻖ ﺑﺎ ﻗﻮﺍﻧﻴﻦ ﺍﻳﻤﻨﻲ ﻣﺤﻠﻲ ﺑﺎﺷﺪ .
ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ،ﺣﺮﻛﺖ ﺧﻮﺩ ﺭﺍ ﺟﻬﺖ ﺭﺳﻴﺪﻥ ﺑﻪ ﻧﻘﻄﻪ ﺍﺳﺘﺎﺭﺕ Aﺁﻏﺎﺯ ﻣﻴﻜﻨـﺪ ،ﭘـﺲ ﭘﺎﻛـﺴﺎﺯﻱ ﺩﺭ ﻃـﻮﻝ ﻣـﺪﺕ ﺧـﺎﻣﻮﺵ ﺑـﻮﺩﻥ C-D
ﻣﺸﻌﻞ ﺍﻧﺠﺎﻡ ﮔﺮﻓﺘﻪ ﻭ ﻓﻘﻂ ﭘﺎﻳﻪ ﻫﺎﻱ 11ﻭ 12ﺑﺮﻕ ﺩﺍﺭ ﺑﻮﺩﻩ ﻭ ﺩﻣﭙﺮ ﻫـﻮﺍ ﺩﺭ ﻭﺿـﻌﻴﺖ ﺑـﺴﺘﻪ ﻗـﺮﺍﺭ ﺩﺍﺭﺩ ﻛـﻪ ﺗﻮﺳـﻂ ﺳـﻮﺋﻴﭻ )) (( zﺍﻛﭽﻮﻳﺘـﻮﺭ
ﻣﺸﺨﺺ ﺷﺪﻩ ﺍﺳﺖ .ﻣﻄﺎﺑﻖ ﺑﺎ ﺗﻮﺿﻴﺤﺎﺕ ﻗﺒﻠﻲ ﻭ ﺑﺪﻟﻴﻞ ﻓﻌﺎﻟﻲ ﺷﺪﻥ ﺁﺷﻜﺎﺭ ﺳﺎﺯ ﺷﻌﻠﻪ ،ﻣـﺪﺍﺭ ﻣـﺮﺗﺒﻂ ﺑﺮﻗـﺪﺍﺭ ﺧﻮﺍﻫـﺪ ﺑـﻮﺩ ) ﺗﺮﻣﻴﻨـﺎﻝ 23/22ﻭ
( 24/22
ﻓﺮﻣﺎﻥ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺗﻮﺳﻂ ﻛﻠﻴﺪ ) Rﺗﺮﻣﻮﺳﺘﺎﺕ ﺩﻣﺎ ﻳﺎ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ (ﺻﺎﺩﺭ ﻣﻴﺸﻮﺩ ) .ﻛﻠﻴﺪ Rﻟﻮﭖ ﻛﻨﺘﺮﻟﻲ ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻟﻬـﺎﻱ 4ﻭ 5ﺭﺍ A
ﻣﻴﺒﻨﺪﺩ ( .
-ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ﺷﺮﻭﻉ ﺑﻪ ﭼﺮﺧﺶ ﻣﻴﻜﻨﺪ
---ﺑﺮﻕ ﻣﺮﺑﻮﻁ ﺑﻪ ﻓﻦ ﺑﻼﻓﺎﺻﻠﻪ ﻭ ﺍﺯ ﻃﺮﻳﻖ ﺗﺮﻣﻴﻨﺎﻝ ﺷﻤﺎﺭﻩ 6ﺗﺎﻣﻴﻦ ﻣﻴﮕﺮﺩﺩ ﻭ ﻓﻘﻂ ﭘﻴﺶ ﭘﺎﻛﺴﺎﺯﻱ ﺍﻧﺠﺎﻡ ﻣﻴﮕﺮﺩﺩ.
---ﭘﻴﺶ ﭘﺎﻛﺴﺎﺯﻱ ﻭ ﭘﺲ ﭘﺎﻛﺴﺎﺯﻱ :ﭘﺲ ﺍﺯ ﺍﺗﻤﺎﻡ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ t7ﺑﺮﻕ ﻓﻦ ﻣﻮﺗـﻮﺭ ﻭ ﻳـﺎ ﻓـﻦ ﻧـﺼﺐ ﺷـﺪﻩ ﺑـﺮ ﺭﻭﻱ ﺩﻭﺩﻛـﺶ ﺍﺯ ﻃﺮﻳـﻖ
ﺗﺮﻣﻴﻨﺎﻝ 7ﻭﺻﻞ ﻣﻴﺸﻮﺩ .
ﭘﺲ ﺍﺯ ﺗﻜﻤﻴﻞ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ t16ﺩﺳﺘﻮﺭ ﺑﺎﺯ ﺷﺪﻥ ﺩﻣﭙﺮ ﻫﻮﺍ ﺍﺯ ﻃﺮﻳﻖ ﺗﺮﻣﻴﻨﺎﻝ 9ﺩﺭﻳﺎﻓﺖ ﻣﻴﺸﻮﺩ .
ﺩﺭ ﻃﻮﻝ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﺗﺜﺒﻴﺖ ﻣﻮﻗﻌﻴﺘﻬﺎ ،ﺗﺮﻣﻴﻨﺎﻝ 8ﺑﺮﻗﺪﺍﺭ ﻧﻤﻴﺸﻮﺩ .
ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ﺣﺮﻛﺖ ﺧﻮﺩ ﺭﺍ ﺗﻨﻬﺎ ﺩﺭﺻﻮﺭﺗﻲ ﺍﺩﺍﻣﻪ ﻣﻴﺪﻫﺪ ﻛﻪ ﺩﻣﭙﺮ ﻫﻮﺍ ﺑﺼﻮﺭﺕ ﻛﺎﻣﻞ ﺑﺎﺯ ﮔﺮﺩﺩ .
ﺩﺭﻓﺎﺻﻠﻪ ﺯﻣﺎﻧﻲ ﻛﻮﺗﺎﻫﻲ ﺍﺯ ﺁﻏﺎﺯ ، t1ﭘﺮﺷﺮ ﺳﻮﺋﻴﭻ ﻫﻮﺍ ﻣﻴﺒﺎﻳﺴﺖ ﺍﺯ ﭘﺎﻳﻪ 13ﺗﺮﻣﻴﻨﺎﻝ ﺑﻪ ﭘﺎﻳﻪ 14ﺗﻐﻴﻴﺮ ﻭﺿﻌﻴﺖ ﺩﻫﺪ .ﺩﺭ ﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ﻛﻨﺘﺮﻟﺮ
ﻣﺸﻌﻞ ﻭﺿﻌﻴﺖ LOCKOUTﺭﺍ ﺍﻋﻼﻡ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ﻭ ﻣﺠﺪﺩﺍ ﺗﺴﺖ ﻓﺸﺎﺭ ﻫﻮﺍ ﺍﻧﺠﺎﻡ ﺧﻮﺍﻫﺪ ﮔﺮﺩﻳﺪ .
ﺑﻄﻮﺭ ﻫﻤﺰﻣﺎﻥ ﺗﺮﻣﻴﻨﺎﻝ 14ﻣﻴﺒﺎﻳﺴﺖ ﺑﺼﻮﺭﺕ ﺑﺮﻗﺪﺍﺭ ﺗﺎ ﺯﻣﺎﻧﻴﻜﻪ ﺗﺮﺍﻧﺲ ﺟﺮﻗﻪ ﺯﻥ ﻋﻤﻞ ﻧﻤﻮﺩﻩ ﻭ ﮔﺎﺯ ﭘﻴﻠﻮﺕ ﻭﺍﺭﺩ ﻣﺪﺍﺭ ﺷﻮﺩ ،ﺑﺎﻗﻲ ﺑﻤﺎﻧﺪ.
ﭘﺲ ﺍﺯ ﺍﺗﻤﺎﻡ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﭘﻴﺶ ﭘﺎﻛﺴﺎﺯﻱ ،ﻛﻨﺘﺮﻟﺮ ﻣﺸﻌﻞ ،ﺩﻣﭙﺮ ﻫﻮﺍ ﺭﺍ ﺩﺭ ﺍﺯ ﻃﺮﻳﻖ ﺗﺮﻣﻴﻨﺎﻝ 10ﻭ ﺗﻮﺳﻂ ﺳﻮﺋﻴﭻ ﺍﺿـﺎﻓﻲ ﻛﻨﺘﺮﻟـﺮ ﺩﻣﭙـﺮ ﻫـﻮﺍ ) m
(ﺩﺭ ﺣﺎﻟﺖ ﻣﻴﻨﻴﻢ ﺷﻌﻠﻪ ﻗﺮﺍﺭ ﻣﻴﺪﻫﺪ.
ﺩﺭ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﺗﺜﺒﻴﺖ ﻣﻮﻗﻌﻴﺘﻬﺎ ،ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ﻣﺠﺪﺩﺍ ﻣﻲ ﺍﻳﺴﺘﺪ .ﺑﻌﺪ ﺍﺯ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﻛﻮﺗـﺎﻫﻲ ﺳـﻜﻮﺋﻨﺲ ﺳـﻮﺋﻴﭻ ،ﺳـﻮﺋﻴﭻ ﻛﻨﺘـﺮﻝ ﻣـﺸﻌﻞ ﺭﺍ
ﺗﺤﺮﻳﻚ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ .ﺍﻳﻦ ﺑﺪﺍﻥ ﻣﻌﻨﻲ ﺍﺳﺖ ﻛﻪ ﺳﻴﮕﻨﺎﻟﻬﺎﻱ ﻣﺮﺗﺒﻂ ﺑﺎ ﻣﻮﻗﻌﻴﺘﻬﺎ ﻛﻪ ﺍﺯ ﻃﺮﻳﻖ ﺗﺮﻣﻴﻨﺎﻝ 8ﺍﺭﺳﺎﻝ ﻣﻴﮕﺮﺩﺩ،ﺗـﺎﺛﻴﺮﻱ ﺑـﺮ ﺭﻭﻱ ﻣﺮﺍﺣـﻞ
ﺍﺳﺘﺎﺭﺕ ﺑﻌﺪﻱ ﻣﺸﻌﻞ ﻧﺨﻮﺍﻫﺪ ﺩﺍﺷﺖ .
t5ﺯﻣﺎﻥ ﻭﻗﻔﻪ
ﭘﺲ ﺍﺯ ﺍﺗﻤﺎﻡ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ t5ﺑﺮﻕ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ 20ﻭﺻﻞ ﻣﻴﮕﺮﺩﺩ .ﺑﻄﻮﺭ ﻫﻤﺰﻣﺎﻥ ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﻛﻨﺘﺮﻟـﺮ 9ﺍﻟـﻲ 11ﻭ ﻭﺭﻭﺩﻱ 8ﺍﺯ ﺳـﺎﻳﺮ
ﺑﺨﺸﻬﺎﻱ ﺟﻌﺒﻪ ﻛﻨﺘﺮﻝ ﻣﺸﻌﻞ ﺑﺼﻮﺭﺕ ﮔﺎﻟﻮﺍﻧﻴﻜﻲ ﺍﻳﺰﻭﻟﻪ ﻣﻴﺸﻮﻧﺪ .ﺩﺭ ﭼﻨـﻴﻦ ﻭﺿـﻌﻴﺘﻲ … LFL1ﺩﺭ ﻣﻘﺎﺑـﻞ ﺑﺮﮔـﺸﺖ ﻭﻟﺘـﺎﮊ ﺍﺯ ﻟـﻮﭖ
ﻛﻨﺘﺮﻟﻲ ﺑﺮﻕ ﻣﺤﺎﻓﻈﺖ ﺧﻮﺍﻫﺪ ﺷﺪ .
ﺳﻜﻮﺋﻨﺲ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ … LFL1ﭘﺲ ﺍﺯ ﺍﺭﺳﺎﻝ ﺳﻴﮕﻨﺎﻝ ﻛﻨﺘﺮﻝ ﺑﺎﺭ ﺍﺯ ﺗﺮﻣﻴﻨﺎﻝ 20ﺑﻪ ﭘﺎﻳﺎﻥ ﻣﻴﺮﺳﺪ.
ﭘﺲ ﺍﺯ ﻣﺪﺕ ﺯﻣﺎﻥ ﻣﻌﻴﻦ ﻭ ﻃﻲ ﺯﻣﺎﻥ ﻭﻗﻔﻪ ) ﻛﻪ ﺩﺭ ﺍﻳﻦ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﺍﺗﺼﺎﻻﺕ ﻛﻨﺘﺮﻟﺮ ﺗﻐﻴﻴـﺮ ﻭﺿـﻌﻴﺖ ﻧـﺪﺍﺩﻩ ﺍﻧـﺪ ( ﺳـﻜﻮﺋﻨﺲ ﺳـﻮﻳﺌﭻ
ﺑﻄﻮﺭ ﺧﻮﺩ ﻛﺎﺭ ﺧﺎﻣﻮﺵ ﻣﻴﺸﻮﺩ.
ﺯﻣﺎﻥ ﭘﻴﺶ ﺍﺣﺘﺮﺍﻕ ) ﻓﻌﺎﻝ ﺷﺪﻥ ﺗﺮﺍﻧﺲ ﺟﺮﻗﻪ ﺯﻥ ( ﺳﻮﺧﺖ ﺑﻮﺍﺳﻄﻪ ﺳﻴﮕﻨﺎﻝ ﺩﺭﻳﺎﻓﺘﻲ ﺍﺯ ﺗﺮﻣﻴﻨﺎﻝ 18ﺗﻮﺳﻂ ﺷـﻴﺮ ﺑﺮﻗـﻲ ﻣﺮﺑﻮﻃـﻪ t3
ﻣﻨﺘﺸﺮ ﻣﻴﮕﺮﺩﺩ .
ﺯﻣﺎﻥ ﻭﻗﻔﻪ ﺑﻴﻦ ﻓﻌﺎﻝ ﺳﺎﺯﻱ ﺷﻴﺮ ﺑﺮﻗﻲ 1ﻭ ﺷﻴﺮ ﺑﺮﻗﻲ 2ﻳﺎ ﺯﻣﺎﻥ ﻭﻗﻔﻪ ﺑﻴﻦ ﻓﻌﺎﻟﻲ ﺳﺎﺯﻱ ﺷﻴﺮ ﺑﺮﻗﻲ 1ﻭ ﻛﻨﺘﺮﻟﺮ ﺑﺎﺭ t4
ﺩﺭ ﭘﺎﻳﺎﻥ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ t4ﺗﺮﻣﻴﻨﺎﻝ 19ﺑﺮﻗﺪﺍﺭ ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﺍﺗﺼﺎﻝ ﺑﺮﻕ ،ﺷﻴﺮ ﺑﺮﻗﻲ ﺷﻤﺎﺭﻩ 2ﺑﻪ ﺳﻮﺋﻴﭻ ﻛﻤﻜﻲ ﺍﻛﭽﻮﻳﺘﻮﺭ ) ( Vﻧﻴﺰ ﻣﺘﺼﻞ ﺷﺪﻩ ﺍﺳﺖ .
ﺯﻣﺎﻥ ﺁﺯﺍﺩ ﺳﺎﺯﻱ ﺳﻮﺧﺖ ﻭ ﺭﻭﺷﻦ ﺷﺪﻥ ﺷﻌﻠﻪ ﭘﻴﻠﻮﺕ ﺍﺯ ﻃﺮﻳﻖ ﺗﺮﻣﻴﻨﺎﻝ 17 't3
ﭘﺲ ﺍﺯ ﺍﺗﻤﺎﻡ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ TSAﺳﻴﮕﻨﺎﻝ ﺷـﻌﻠﻪ ﻣﻴﺒﺎﻳـﺴﺖ ﺩﺭ ﺗﺮﻣﻴﻨـﺎﻝ 22ﺩﺭﻳﺎﻓـﺖ ﮔـﺮﺩﺩ.ﺳـﻴﮕﻨﺎﻝ ﻣـﺬﻛﻮﺭ ﺗـﺎ ﺯﻣﺎﻧﻴﻜـﻪ ﻣـﺸﻌﻞ 'TSA
ﺑﺼﻮﺭﺕ ﻛﻨﺘﺮﻝ ﺷﺪﻩ ﺧﺎﻣﻮﺵ ﻣﻴﮕﺮﺩﺩ ،ﻧﺒﺎﻳﺪ ﻗﻄﻊ ﮔﺮﺩﺩ .ﺩﺭ ﻏﻴﺮ ﺍﻳﻨﺼﻮﺭﺕ ﻓﺎﻟﺖ LOCKOUTﺧﻮﺍﻫﻴﻢ ﺩﺍﺷﺖ
ﻭﻗﻔﻪ ﺯﻣﺎﻧﻲ ﺑﻴﻦ ﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ ﺑﺮﻗﻲ ﭘﻴﻠﻮﺕ ﻭ ﺷﻴﺮ ﺑﺮﻗﻲ ﺍﺻﻠﻲ t4
ﻣﺪﺕ ﺯﻣﺎﻥ ﻭﻗﻔﻪ ﺗﺎ ﺁﺯﺍﺩ ﺳﺎﺯﻱ ﺳﻮﺧﺖ ﺍﺯ ﻃﺮﻳﻖ ﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ ﺑﺮﻗﻲ ﺑﻮﺳﻴﻠﻪ ﺗﺮﻣﻴﻨﺎﻝ 19ﻭ ﺗﺸﻜﻴﻞ ﺷﻌﻠﻪ ﺍﺻﻠﻲ ﻣﺸﻌﻞ 't4
ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ﺣﺮﻛﺖ ﺧﻮﺩ ﺭﺍ ﺟﻬﺖ ﺭﺳﻴﺪﻥ ﺑﻪ ﻭﺿﻌﻴﺖ ﺍﺳﺘﺎﺭﺕ ) ﻧﻘﻄﻪ ( Aﺁﻏﺎﺯ ﻣﻴﻨﻤﺎﻳﺪ. C-D
ﺯﻣﺎﻥ ﻣﺠﺎﺯ ﭘﺲ ﺍﺯ ﺍﺣﺘﺮﺍﻕ ) ﺩﺭ ﻃﻮﻝ ﺍﻳﻦ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ، t13ﻭﺭﻭﺩﻱ ﺳﻴﮕﻨﺎﻝ ﺷﻌﻠﻪ ﻣﻴﺘﻮﺍﻧﺪ ﻛﻤﺎﻛﺎﻥ ﺳـﻴﮕﻨﺎﻝ ﻭﺟـﻮﺩ ﺷـﻌﻠﻪ ﺭﺍ ﺩﺭﻳﺎﻓـﺖ t13
ﻧﻤﺎﻳﺪ ﻭ ﻣﺸﻌﻞ ﺩﺭ ﺍﻳﻦ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﻓﺎﻟﺖ LOCKOUTﺻﺎﺩﺭ ﻧﺨﻮﺍﻫﺪ ﻧﻤﻮﺩ .
ﻳﻜﻲ ﺍﺯ ﻣﺪﺍﺭﻫﺎﻱ ﻛﻨﺘﺮﻟﻲ) ﻏﺎﻟﺒﺎ ﻣﻮﺍﺭﺩ ﭘﻴﺶ ﺷﺮﻁ ﺟﻬﺖ ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﺸﻌﻞ ( ﺑﺴﺘﻪ ﻧﺸﺪﻩ ﺍﺳﺖ.
ﻋﺪﻡ ﺣﺮﻛﺖ ﺑﺮﻭﺯ ﻓﺎﻟﺖ LOCKOUTﺩﺭ ﺧﻼﻝ ﻭ ﻳﺎ ﺑﻌﺪ ﺍﺯ ﺍﺗﻤﺎﻡ ﭘﺮﻭﺳﻪ ﻛﻨﺘﺮﻝ ﻣﺎﻧﻨﺪ :
ﺷﻌﻠﻪ ﺍﻱ ﻛﻪ ﻛﻤﺎﻛﺎﻥ ﭘﺲ ﺍﺯ ﺍﺗﻤﺎﻡ ﭘﺮﻭﺳﻪ ﺍﺣﺘﺮﺍﻕ ﺧﺎﻣﻮﺵ ﻧﺸﺪﻩ ﺑﺎﺷﺪ . -
ﻭﺟﻮﺩ ﻧﺸﺘﻲ ﺩﺭ ﺷﻴﺮﻫﺎﻱ ﺳﻮﺧﺖ -
ﻭﺟﻮﺩ ﺍﻳﺮﺍﺩ ﺩﺭ ﻣﺪﺍﺭ ﻛﻨﺘﺮﻟﻲ ﭘﺎﻳﺶ ﺷﻌﻠﻪ -
ﻭﻗﻔﻪ ﺩﺭ ﻣﺮﺣﻠﻪ ﺁﻏﺎﺯﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ 8ﻫﻨﻮﺯ ﺳﻴﮕﻨﺎﻝ ﺑﺎﺯ ﺑﻮﺩﻥ ﺩﻣﭙﺮ ﻫﻮﺍ ﺭﺍ ﺍﺯ ﺳﻮﺋﻴﭻ aﺩﺭﻳﺎﻓﺖ ﻧﮕﺮﺩﻩ ﺍﺳﺖ .
ﻓﻌﺎﻟﻴﺖ ﻛﻨﺘﺮﻟﺮ ﺗﺮﻣﻴﻨﺎﻝ 6ﻭ 7ﻭ 14ﻛﻤﺎﻛﺎﻥ ﺗﺎ ﺯﻣﺎﻥ ﺭﻓﻊ ﻛﺎﻣﻞ ﺍﻳﺮﺍﺩ ﺑﺮﻗﺪﺍﺭ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ
ﺳﻨﺴﻮﺭ ﭼﻚ ﻓﺸﺎﺭ ﻫﻮﺍ ) ﭘﺮﺷﺮ ﺳﻮﺋﻴﭻ ( ﻫﻴﭻ ﺳﻴﮕﻨﺎﻟﻲ ﺍﺭﺳﺎﻝ ﻧﻤﻴﻨﻤﺎﻳﺪ ) ﻓﺸﺎﺭ ﻫﻮﺍﻳﻲ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ (.
P LOCKOUT
ﺍﺯ ﺑﻴﻦ ﺭﻓﺘﻦ ﻓﺸﺎﺭ ﻫﻮﺍ ﭘﺲ ﺍﺯ ﺩﺭﻳﺎﻓﺖ ﺳﻴﮕﻨﺎﻝ ﻣﺮﺑﻮﻃﻪ ﺍﺯ ﻃﺮﻳﻖ ﭘﺮﺷﺮ ﺳﻮﺋﻴﭻ ﺩﺭ ﻛﻨﺘﺮﻟﺮ
ﻭﻗﻔﻪ ﺩﺭ ﻣﺮﺣﻠﻪ ﺁﻏﺎﺯﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ 8ﺳﻴﮕﻨﺎﻝ ﻣﺮﺑﻮﻁ ﺑﻪ ﻭﺿﻌﻴﺖ ﺷﻌﻠﻪ ﻛﻮﺗﺎﻩ ) (Low fireﺭﺍ ﺍﺯ ﺳﻮﺋﻴﭻ ﻛﻤﻜﻲ mﺩﺭﻳﺎﻓﺖ ﻧﮕﺮﺩﻩ ﺍﺳﺖ .
ﻓﻌﺎﻟﻴﺖ ﻛﻨﺘﺮﻟﺮ ﺗﺮﻣﻴﻨﺎﻝ 6ﻭ 7ﻭ 14ﻛﻤﺎﻛﺎﻥ ﺗﺎ ﺯﻣﺎﻥ ﺭﻓﻊ ﻛﺎﻣﻞ ﺍﻳﺮﺍﺩ ﺑﺮﻗﺪﺍﺭ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ
ﻋﺪﻡ ﻭﺟﻮﺩ ﺳﻴﮕﻨﺎﻝ ﺍﻳﻤﻨﻲ ﺭﻭﺋﻴﺖ ﺷﻌﻠﻪ ﻋﻠﻲ ﺭﻏﻢ ﺗﻜﻤﻴﻞ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ TSA
1 LOCKOUT
ﻋﺪﻡ ﻭﺟﻮﺩ ﺳﻴﮕﻨﺎﻝ ﺭﻭﺋﻴﺖ ﺷﻌﻠﻪ ﺩﺭ ﭘﺎﻳﺎﻥ ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﺍﻳﻤﻨﻲ ﺩﻭﻡ ) ﺳﻴﮕﻨﺎﻝ ﺭﻭﺋﻴﺖ ﺷﻌﻠﻪ ،ﺷﻌﻠﻪ ﺍﺻﻠﻲ ﺩﺭ
2 LOCKOUT
ﻣﺸﻌﻠﻬﺎﻱ ﭘﻴﻠﻮﺕ ﻣﻨﻘﻄﻊ (
ﺩﺭﺻﻮﺭﺗﻴﻜﻪ ﻓﺎﻟﺖ LOCKOUTﺩﺭ ﺯﻣﺎﻧﻬﺎﻳﻲ ﺧﺎﺭﺝ ﺍﺯ ﻓﺎﺻﻠﻪ ﺯﻣﺎﻧﻲ ﺑﻴﻦ ﺁﻏﺎﺯ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﻭ ﻓﻌﺎﻟﻴﺖ ﺟﺮﻗﻪ ﺯﻥ ﺍﺗﻔﺎﻕ ﺑﻴﻔﺘﺪ ،ﺗﻮﺳﻂ ﻧﻤﺎﻳـﺸﮕﺮ ﻭ
ﻧﺸﺎﻧﻪ ﻫﺎﻱ ﺗﻮﺿﻴﺢ ﺩﺍﺩﻩ ﺷﺪﻩ ﻓﻮﻕ ﻗﺎﺑﻞ ﺭﻭﺋﻴﺖ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ ﻭ ﻣﻌﻤﻮﻻ ﻋﻠﺖ ﺑﺮﻭﺯ ﻣﺸﻜﻞ ،ﺍﺭﺳﺎﻝ ﺳﻴﮕﻨﺎﻟﻬﺎﻱ ﺭﻭﺋﻴﺖ ﺷﻌﻠﻪ ﭘـﻴﺶ ﺍﺯ ﻣﻮﻋـﺪ ﻣﻘـﺮﺭ
ﻣﻴﺒﺎﺷﺪ .
ﻧﻤﺎﻳﺸﮕﺮ : LOCKOUT
ﺩﺭﺻﻮﺭﺕ ﺑﺮﻭﺯ ﻓﺎﻟﺖ LOCKOUTﻛﻨﺘﺮﻟﺮ ﻣﺸﻌﻞ ﻣﻴﺘﻮﺍﻧﺪ ﺑﻼﻓﺎﺻﻠﻪ ﺭﻳﺴﺖ ﺷﻮﺩ :
ﺩﻛﻤﻪ ﺭﻳﺴﺖ ﻣﻮﺟﻮﺩ ﺑﺮ ﺭﻭﻱ ﻛﻨﺘﺮﻟﺮ ) ﺭﺍ ﻛﻪ ﺭﻭﻱ ﻧﻤﺎﻳﺸﮕﺮ LOCKOUTﻗﺮﺍﺭ ﺩﺍﺭﺩ ( ﺑﻴﺶ ﺍﺯ 10ﺛﺎﻧﻴﻪ ﺑﺼﻮﺭﺕ ﻣﻤﺘﺪ ﻓﺸﺎﺭ ﻧﺪﻫﻴﺪ.
ﺳﻜﻮﺋﻨﺲ ﺳﻮﺋﻴﭻ ﻫﻤﻴﺸﻪ ﺩﺭ ﺣﺎﻟﺘﻬﺎﻱ ﺫﻳﻞ ﺑﻪ ﻣﻮﻗﻌﻴﺖ ﺷﺮﻭﻉ ﺧﻮﺩ ﺑﺎﺯﻣﻴﮕﺮﺩﺩ :
ﭘﺲ ﺍﺯ ﺭﻳﺴﺖ ﺷﺪﻥ
ﭘﺲ ﺍﺯ ﺍﺻﻼﺡ ﻭ ﺭﻓﻊ ﻓﺎﻟﺘﻲ ﻛﻪ ﻣﻨﺠﺮ ﺑﻪ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺗﺠﻬﻴﺰ ﺷﺪﻩ ﺍﺳﺖ .
ﭘﺲ ﺍﺯ ﻫﺮ ﺑﺎﺭ ﻗﻄﻊ ﺑﺮﻕ
ﺩﺭ ﺧﻼﻝ ﻫﺮ ﻳﻚ ﺍﺯ ﺑﺎﺯﻩ ﻫﺎﻱ ﺯﻣﺎﻧﻲ ﻓﻮﻕ ،ﻓﻘﻂ ﺑﺮﻕ ﭘﺎﻳﻪ ﻫﺎﻱ 7ﻭ 9ﺍﻟﻲ 11ﺑﺮ ﻗﺮﺍﺭ ﻣﻴﺒﺎﺷﺪ .
ﺳﭙﺲ … LFL1ﻣﺠﺪﺩﺍ ﭘﺮﻭﺳﻪ ﻛﻨﺘﺮﻟﻲ ﺭﺍﻩ ﺍﻧﺪﺍﺯﻱ ﺟﺪﻳﺪﻱ ﺭﺍ ﺑﺮﺍﻱ ﻣﺸﻌﻞ ﺁﻏﺎﺯ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ .
ﻓﺮﻣﺎﺋﻴﺪ .