Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

INSTALLATION AND PROGRAMMING

Phasefale's TACm Version 5.6 Software


INDEX up to 100 metres by joining an extra inputs are extra low voltage inputs and
1. Installation cable (use double insulated cable) but require voltage free contacts. Closing
2. Programming the join must be well insulated and away the contacts momentarily will initiate
2a. Advanced Programming Options from any dirt or moisture. the function. Refer to the wiring
2b. A Programming Example Dirt or moisture at the join will reduce diagram for correct wiring of these
3. Cooling and Heating Operations the resistance of the probe and result in inputs.
4. Alarm a higher temperature reading than The optional Alarm Isolate input
5. Defrost normal. requires voltage free contacts and is
6. Temperature Logging active while the contacts remain closed.
7. Alphabetical Table of Indications The complog interface wiring is
8. TACm Wiring Diagram described separately.
Electrical Installation
Installation Self-Test
General Overview and Introduction Refer also to the electrical wiring
Press and together for 5 seconds.
diagram for connection details. The
The TACm automatically cycles its
Phasefale's TACm is extremely simple 4 00 k
R es is tan c e outputs in the following sequence:
to set up and operate. The temperature
is shown on the LED display. If cooling 3 00 k
Display Action sec.
or heating operations are occurring a
point is displayed at the end of the 2 00 k
CO/CF Control On&Off 10/4
temperature display. Flashing of the LO/LF Light On&Off 4/4
temperature indicates an alarm situation. 1 00 k
T Deg C dO/dF Dialler+Buzzer 4/4
During defrost, dF is displayed. The HO/HF Heater On&Off 4/4
programmed settings may be viewed by 0k FO/FF Fan On&Off 4/4
-20 -10 0 10 20
pressing and holding the button for 2 M P ro b e-
seconds. R e s is tan c e v s T e m p. (C e ls iu s)

2. PROGRAMMING
1. INSTALLATION The basic programming steps are:
Enclosure Installation E x te n d M P ro b e to 1 0 0 m . • "Unlock" the TACm permanent
us in g H ea ts h rin k o n jo in s
The Enclosure can be mounted in any memory for programming
Active supply to the unit should be
position, and is splash proof. Mount the • Select the setting to be adjusted.
fused with a maximum rating of 10A.
base and fit two of the mounting screws • Alter the setting to your desired
The control and light outputs are rated
in the lid. The lid can then be hinged out value.
at 10A resistive. Motors larger than
to allow the electrical connections to be • Store the changed value.
1 HP MUST be switched via a relay or
made. contactor (available from Phasefale). • Return to normal operation.
Temperature Sensor (M Probe) The dialler output provides alarm
contacts which open on alarm or power a) To unlock the TACm and alter the
Installation settings, press and together for 5
The temperature sensor is an NTC loss. The contacts can be connected to
Phasefale's AD2 telephone dialler to seconds. UL will be displayed to
thermistor of extreme accuracy (0.2°C),
provide a remote alarm using existing indicate that the system is unlocked.
and it has a non-linear
resistance-temperature characteristic phone lines.
If an AD2 is connected, the 2-way b) After the TACm is unlocked press
(see chart below). It is ideally mounted
connector labelled "dialler" can be used until the setting you wish to alter is
in a position where refrigerated air is
to supply 12V DC to the dialler. The displayed. The settings and values are
circulating.
correct polarity is indicated on the displayed in the table below:
At least 150mm of the sensor cable
needs to be in the refrigerated space to wiring diagram. If a battery is fitted, Sett- De- Display adjustment
ensure accurate temperature sensing. connect to the battery. ing fault range
If the sensor cable is open or short TACmb is supplied with the battery SP 0.0 Control Setpoint °C
circuit, the TACm will display Er to back-up disconnected. Reconnect once (-35 ~ +55°C)
indicate the fault. If a defrost terminate mains power is connected.
dI Ec Differential Temp °C
probe is used it should be mounted in If the mdPCB option for heater and fan 0.5~5°C, Ec: economy
the evaporator coil. outputs is to be fitted, follow the
AH 13 High Alarm Temp. °C
The sensor cable is double insulated and instructions supplied with it.
(-30~ +60°C)
therefore does not need to be enclosed The optional toggle defrost,
AL -5.0 Low Alarm Temp. °C
in a conduit. There is no polarity to the synchronising time, terminate defrost,
(-40~+50°C)
sensor connection. It may be extended distress, clear memory and acknowledge
TACm Installation & Programming Page 1 of 4 Tacm56.doc, Q3 1997
ISSUE - 1 C:\Adobe\reader\Acrobat\plug_ins\OpenAll\Transform\temp\Tacm56.doc
At 90 Alarm Time Delay 2b. A PROGRAMMING • nd then 1 is displayed. We want 2
(0~99 minutes) EXAMPLE defrosts so press then to
nd 1 Number of defrosts per A small fruit room needs to be store.
24hr (0~6) controlled at 1.0°C. We want a high • dd then 30 is displayed, set the
dd 30 Defrost duration alarm at 9.0°C and a low alarm defrost duration to 45 and store
(1~99minutes) at -2.0°C to prevent the fruit from with .
c) After the setting to be adjusted is freezing. Being a small room, we will Step 3 Check our Settings
displayed, you can increase or decrease set the alarm time to 60 minutes. As we Press for 2 seconds, and our stored
the setting by pressing or until the are energy conscious, we will use the values are automatically displayed.
numerical value required is displayed. economy mode of operation. We want The TACm is now ready for operation.
d) To store the changed value, press the two 45 minute defrosts per day.
keypad. The new value is now 3. COOLING AND HEATING
stored indefinitely and will remain Step 1 Use the auto-setup to load OPERATIONS
during power loss. suitable settings: Heating and cooling control is between
e) If no keypad is pressed for 60 • Unlock the TACm using and the setpoint SP (cut in) and the setpoint
seconds the TACm will once again lock keys. Display reads UL, then... minus the differential dl (cut out). For
itself and further alterations will be • Display shows SP eg. 5.0. example: SP =10oC, dl =1.0oC: control
disallowed until unlocked again. This • Decrease the setpoint by pressing
will also occur if the key is pressed between 9.0oC and 10°C. Another
until 1.0 is displayed. example: SP = -10oC, dl =3.0oC: control
during the programming operation.
• Store the new setpoint with . between -10oC and -13oC.
Remember! you must store each altered
• dl (for differential) then Ec The Heating and Cooling options HE
value using
(Economy mode* ) is displayed. and Co [AA menu] select whether the
2a. ADVANCED [AAmenu] • Press and AU (Automatic C1/C2 output controls heaters or
PROGRAMMING OPTIONS mode*) is displayed. coolers. In heating mode there is no
A further series of functions and • Store the automatic setting with limit start timer or defrost function and
commands can be accessed during the key. programming options which relate to
Unlocking stage by simply pressing the defrosts will be skipped. If Cooling is
and keys for a total of 10 * There are three programming options selected, a limit start timer protects
seconds, at which time the symbol AA in differential dl : against short cycling the compressor.
is displayed. Program items which can Ec Economy mode - a method to reduce The timer will prevent the cooling
be accessed in the advanced menu are energy usage whilst using the internal output turning on for a period starting
indicated in the following table and are limit start timer to protect the the previous time the cooling output
explained under their appropriate compressor. turned on. Once this period has elapsed
function headings. AU Auto setup - Default settings (for the output is free to turn on as required.
all the programmable values) based on The limit start period is the units part of
Sett- Def- Value Shown your setpoint are loaded into the the AA (alarm acknowledge) setting.
ing ault (adjustment range) TACm's memory. For example AA=4,14,24 etc. means a
AA 14 Alarm Acknowledge/ 0.5 to 5.0 Differential Temperature in limit start period of 4 minutes,
Limit Start Time ° C - The specific temperature required AA=9,19,29,39 etc. means 9 minutes,
tr 5 Defrost Terminate or AA=10,20,30 etc means 0 minutes or
for the control. (See Cooling and
Range °C
Heating Operations) no limit start delay.
(2.5,5,7.5,10°C)
Co/He Co Cooling or heating
C1/C2 comes on when cooling is
Step 2 The TACm has stored close required.
mode values, but we now "fine tune" the
dt 1 Heater drain period The terminate/range temperature
settings for our application: function tE/rA [AA menu] sets a
(0~12minutes)
• Unlock the TACm: and temperature terminated defrost tE if a
Ft 1 Fan delay/ Pump down
time (0.0~4.0 min.) • Display UL. probe is connected (See Defrost), or it
dE/dg dE Electric or Hotgas • SP then 1.0 is displayed, press sets the range offset rA as described
defrost • dl then EC is displayed, press . below:
tE/rA tE S2 input as temperature • AH then 14 is displayed, decrease An external trimpot of 100k Ω value
sensor defrost terminate the high alarm to 9.0 using Store may be used to modify the control
or rAnge via external the new high alarm setting with .
potentiometer
temperature up or down by 2.5, 5.0, 7.5
• AL then -4.0 is displayed, increase or 10oC as set by the tr setting. The
Sd/Hd Sd Show/Hide temperature
display during defrost
the low alarm setting to -2.0 using programmed value SP then becomes the
St 3 Time of first defrost "midpoint" of the setpoint range. 0kΩ
(0~23) • Store the new low setting using gives the minimum, 100kΩ gives the
CA 0.0 Calibration Offset • At then 90 is displayed, decrease maximum and 50kΩ leaves the setpoint
(-9.9 to 9.9°C) the alarm time delay to 60 using , unchanged. If no trimpot is connected,
then store with . the setpoint remains unaltered. The high
TACm Installation & Programming Page 2 of 4 Tacm56.doc, Q3 1997
ISSUE - 1
and low alarm temperatures AH, AL Press to find out when the next Output C L H F time
will be shifted in conjunction with the defrost will occur, td is displayed, Representing;Liquid ; Suction;Heater; Fan
setpoint SP. Note that SP, AH and AL followed by the number of hours until Cooling on/off on off on
will reflect the altered setpoints when the next defrost. Similarly, pressing P/D off on off on Ft
viewed by pressing from normal displays Fd followed by the number of Defrost off off on off dd
operations. By using fixed resistors, hours since the last defrost occurred. Drain off off off off dt
specific temperature setpoints can be The decimal place represents 10 Fan on/off on off off Ft
set up using a rotary switch or time minutes, ie 2.4 is 2 hours and 40 Cooling on/off on off on
clock. minutes.
To initiate a Toggle Defrost, hold the A second M Probe may be used as a
4. ALARM button for 1 second and either dF or Co temperature termination sensor for the
The Alarm function has a high will be displayed, to indicate whether defrost. It is used between the S & S2
temperature (in °C) setpoint, AH, a low the refrigeration is presently in defrost outputs. The tE/rA setting should be
temperature (in °C), AL, and a time or cooling mode. Press the button set to tE and the defrost terminate
delay, At. If either setpoint is exceeded followed by to initiate a defrost or temperature set by tr at 2.5, 5.0, 7.5 or
for longer than the time delay an alarm press the button followed by to 10o C.
will occur. If cooling mode is selected terminate a defrost. This function can
the low alarm will occur in 1/4 of the also be accomplished with an external 6. TEMPERATURE
time delay At. The optional distress toggle defrost switch (which will LOGGING
alarm will initiate an alarm immediately alternate the status between defrost and
Press both and buttons together.
if connected, as will a power failure if cooling when closed) or via the
terminate defrost input (which will Lo (Logging) is displayed. Pressing
the internal battery backup option is
terminate a defrost and initiate a drain will show the highest temperature in the
used.
period). last hour, continue pressing and the
An Alarm is indicated by the
Further defrost functions can be previous hour's highest is indicated - up
temperature display flashing
accessed via [AA menu]. The Sd (Show to 99 hours. PL indicates that a power
accompanied by the sounding of a
defrost) function alternates the display loss occurred. If you wish to know how
buzzer, a flashing alarm light and/or a
between dF and the temperature during many hours ago a record was stored,
dial signal if these accessories are
defrosts, whilst Hd (Hide defrost) press and together to show the
connected.
causes the display to show only dF hours since the record was made. Once
An alarm may be acknowledged by
during defrost. again, pressing will return you to
pressing momentarily or via an
Also accessible [AA menu] , St refers to normal operation.
external switch. The light will then be
steady on and the buzzer and dialler off the Start Time of the first defrost. Repeat the above sequence but press
Defrosts will then occur at periods and the lowest temperatures will be
for the period set by AA [AA menu].
evenly spaced during the day as set by shown.
The alarm will reoccur after this period
of time unless the temperature returns to nd . So, groups of TACm's may be set
normal. to stage defrosts between them by
An Alarm Memory is shown by the selecting different start times for each
display flashing but no other alarm unit, and synchronising the time with a
indications. This indicates that an alarm master clock via the synchronise input.
has occurred but that the temperature The Heater Drain Time dt [AA menu]
has since returned to normal. It may be sets the period in minutes from the end
cleared by pressing the button. of the defrost period dd until the
If a hot gas defrost is used [dg in cooling output is allowed to operate.
advanced menu], the light output cannot The Ft Fan Delay Time sets the period
be used as an alarm light, the buzzer and in minutes from the end of the drain
dialler outputs still operate as normal time when cooling comes on to the time
during alarm. when the fans are allowed to operate.
The decimal place represents 10
5. DEFROST seconds, ie 1.3 is 1 minute 30 seconds.
The defrost duration dd is the time in The dE/dg (Electric/hot Gas defrost)
minutes in which the refrigeration is [AA menu] allows the unit to control
switched off and the heaters are on. Electric (Liquid,Heater and Fan) or Hot
Defrosts are spaced at equal periods Gas (Liquid,Suction,Hot Gas and Fan)
during the day and the number per day defrosts.
is set by nd. For example, if nd = 2 a A Hot Gas defrost uses the Light output
defrost will occur every 12 hours. as the Suction solenoid control and the
A 24 hour clock sets the time of day for Ft setting as a pump down time. The
defrosts. The optional synchronise input Hot Gas output sequence is as follows..
will set the clock to midnight if closed. HOT GAS SEQUENCE
TACm Installation & Programming Page 3 of 4 Tacm56.doc, Q3 1997
ISSUE - 1
7. ALPHABETICAL LIST OF DISPLAY INDICATIONS
Def Def Def
AA Alarm Ack./Limit Start 14 dI Differential °C Ec Lo Logging -
AC AC Mains Failure - dO Dialler ON - LO Light OFF -
AH High Alarm temp.°C 13 dt Heater drain time mins 1 n6 software version 5.6 -
AL Low Alarm temp °C -5 Ec Economy mode Ec nd number of defrosts -
At Alarm time delay mins 90 Er Probe Error(open/short) - PL Power Loss -
AU Automatic setup - Fd from last defrost hours - rA Range (via pot.) tE
CA Calibrate 0 FF Fan OFF - Sd Show temp during defrost Sd
Co Cooling mode Co FO Fan ON - SP Setpoint temperature 0.0
CO Cooling ON - Ft Fan delay time mins 1 td time to next defrost hours -
CF Cooling OFF - Hd Hide defrost temp °C Sd tE temperature terminate tE
dd defrost duration mins 30 HE Heating mode Co tr defrost termination/range°C 5
dE Electric defrost dE HF Heater OFF - UL programming unlocked -
dF Defrost or Dialler OFF - H0 Heater ON -
dg Gas defrost dE LF Light OFF - Def is the default setting

Red +12V DC 15mA MAX


For AUX. EQUIP (eg AD-1 Dialler) 20 AMP 1Hp 240VAC outputs
Black (USE BATT. CONN. FOR TACmB) P mdPCB
+ -
F OPTION F1 F2 H1 H2
10A RES. MAX
1 Hp H BLK
Ref TACV5WD
A
URITY DEVICE
REMOTE SEC-

RANGE/TERM.

HEATER
(or HEAT)
COOLING

DEFROST
BUZZER

SENSOR
SUPPLY

EVAP. TO
ALARM
12 Vdc
LIGHT

TEMP.

FAN TO 1HP 3.7kW

A N C1 C2 L1 L2 D1 D2 B1 B2 S S4 S3 S2 S1 S 7Dx40mm
N
M Probe
CONTACTS OPEN

L
ON ALARM

*Defrost Terminate Sensor


Alarm
Light
*Range Control Resistor
L 100k
Terminate Defrost

Refrig. SECURITY B Toggle Defrost N


22k
Solenoid SYSTEM: BMS NOTE:
or DDC, OR AD2 Syncronise Time
DIALLER 100k These Door
Heat R/H
12V 15mA switch &
Relay Isolate Alarm connections
MAX Cabinet
must
light.
Acknowledge Alarm
be
To Telephone *Optional,
22k Clear Memory voltage
A N Socket use only
Distress Alarm free. one at a
100k
8. TACm WIRING DIAGRAM time

For Technical assistance contact :


PHASEFALE PTY LTD
36 Bulli Street, Moorabbin. Vic. 3189, AUSTRALIA. ACN 078 932 448
Tel (03) 9553 0800 Fax (03) 9553 3993. Intl.Tel +613 9553 0800
www.phasefale.com.au sales@phasefale.com.au
TACm Installation & Programming Page 4 of 4 Tacm56.doc, Q3 1997
ISSUE - 1

You might also like