TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

ተ.ቁ ተፈላጊዉ የቴክኒክ መመዘኛ ነጥቦች መደበኛ መለኪያዎችን ጨምሮ


Category Essential features Bidders compliance Response
1. Number of sources it It should be Three Source Automatic Transfer COMPLY
can support as an Switch System consisting of (3) Three Auto SCHNEIDER ASCO ATS has been manufactured to operate with
input Transfer switches that have been prototype three source power supplies in this case mains, and two
tested, factory built, production-tested, and site- generators, as shown below
tested together with all accessories necessary
for a complete installation. Three Sources are
as follows: 1- Utility, 2-New Generator Set and
Existing Generator Set.

2. Industry compatibility The automatic transfer switch shall be COMPLY


industrial (NOT residential) grade and SCHNEIDER ASCO ATS has been manufactured to meet the
furnished so as to maintain system industrial grade of operation.
compatibility and local service responsibility for
the complete emergency power system

3. Number of poles The automatic transfer switch (ATS) shall be a COMPLY


minimum 4-pole design (3-pole + neutral), SCHNEIDER ASCO ATS has been manufactured to operate with 4
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

rated for full load, continuous operation. numbers of poles (3 pole and neutral)
• To transition between 3 sources – 1 Utility and 2
Generators
• Industrial Grade
• 4 Pole (3 Phase + Neutral)
• 400V /50Hz Service voltage.
4. Multi – voltage The transfer switch shall be supplied with COMPLY
compatibility (single multi-voltage capability to allow use on a SCHNEIDER ASCO ATS has been manufactured to operate with
phase and three phase variety of standard system voltage levels different voltage capabilities such as 240V, 380V, 480V, 600V.
system) without replacement of components. The
transfer switch shall be field configurable to
operate on the following nominal system
voltages; 240V, 380V, 480V, 600V.

5. Rating Rating of the automatic transfer switch shall be COMPLY


800 AMP SCHNEIDER ASCO ATS has been manufactured to operate with
800AMP current rating.
6.
6.1 Voltage condition The ATS shall continually monitor the COMPLY
monitoring capability condition of the utility supply SCHNEIDER ASCO ATS has been manufactured to give priorities
voltage/frequency and shall automatically to the emergency generator while the mains is failed and will
respond to a utility power failure condition by start the second genset if the emergency generator is not working
issuing an engine start signal to the New well or fail to start, but both generators will start immediately the
Emergency standby generator. In the event of mains fails the difference is if the selected or preferred generator
the New Generator Set failure the Existing is ok to start working the second one will commanded to stop and
Generator Set will be signaled to start. start working if and only if the preferred generator is not able to
work.
6.2 Automation capability The ATS shall automatically transfer the COMPLY
between mains and emergency load to the generator supply in the SCHNEIDER ASCO ATS has been manufactured to automate
failure event of a utility supply failure and return the operations between generator and mains.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

load to the utility supply upon restoration.

6.3 Load test capability When an On-Load test mode is activated, the COMPLY
ATS shall automatically transfer the emergency SCHNEIDER ASCO ATS has been manufactured to operate with
load to the generator supply and return the load on load test capabilities on the generator so that it enables the
to the utility supply upon test completion. generator to test load caring capacity with the mains presence.

6.4 Transfer capability The ATS shall perform a closed transition fast COMPLY
from genset to mains power transfer between operating generator SCHNEIDER ASCO ATS has been manufactured to operate to
and the utility supply once the utility power have a fast power transfer time to go from generator to the mains
source has been restored. when the mains source is restored.

6.5 ATS components The Automatic Transfer Switch package shall COMPLY
include the following main components: SCHNEIDER ASCO ATS has been manufactured to operate with
A. ATS Enclosure the components listed below
B. Power Switching Mechanism • ATS Enclosure
C. Automatic Transfer Switch Controller: • Power Switching Mechanism
D. Operator Interface Display • Automatic Transfer Switch Controller:
E. Source Voltage & Frequency Sensors • Operator Interface Display
F. ATS control logic c/w Integrated Time • Source Voltage & Frequency Sensors
Delays, Inputs & Outputs
• ATS control logic c/w Integrated Time Delays, Inputs &
G. Engine Start Output Contact
Outputs
• Engine Start Output Contact
7. Experience The Transfer Switch shall be designed and COMPLY
manufactured in a facility, which is registered to SCHNEIDER ASCO ATS has been manufactured to operate with
an ISO 9001:2008 quality system. The supplier quality system of ISO 9001:2008 registered and the company has
shall have a minimum of 10 years’ experience over 10 years of experience on this field.
designing and manufacturing automatic
transfer switches.
8. Weather condition The Transfer Switch should operate COMPLY
compatibility continuously in Addis Ababa and entoto altitude SCHNEIDER ASCO ATS has been manufactured to operate to
and weather condition. withstand harsh weather conditions and then will operate In
Addis Ababa and entoto altitude and weather conditions.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

9. Capability of load with The automatic transfer switch assembly shall be COMPLY
our derating rated for 100% continuous load without de- SCHNEIDER ASCO ATS has been manufactured to work 100%
rating. continuous load without de rating.

10. Short circuit fault Short Circuit fault withstand current rating of COMPLY
current rating the complete assembly shall be 50 K amps RMS SCHNEIDER ASCO ATS has been manufactured to operate with
for up to 3 Cycles. The interrupting and closing short circuit fault withstand current rating of 36KA.
rating shall be equal to or exceed the required
withstand rating. This rating shall be obtained
with standard upstream over current protection
devices.
11. Enclosure The complete ATS assembly shall be mounted COMPLY
in a NEMA 3R rated enclosure suitable for SCHNEIDER ASCO ATS has been manufactured to operate with
outdoor application. NEMA 3R rated enclosure and it is suitable for outdoor
application.
12. Accessibility of ports The rear section shall contain bussing and COMPLY
provisions for customer incoming and outgoing SCHNEIDER ASCO ATS has been manufactured to operate with
line and load cables. Access shall be from the rear section which has bussing and provisions for cable
rear by removable rear covers. incomings and outgoing line and load cables.

13. Lugs Adequate size and quantity of ground lugs shall COMPLY
be provided and shall conform to NEC/CEC SCHNEIDER ASCO ATS has been manufactured to operate with
guidelines. Ground bus shall be a full-length adequate size and quantity of ground lugs will be provided and
copper ground bus bonded to the frame with which are conform to NEC/CEC.
adequate size and quantity of ground lugs and
shall conform to NEC/CEC guidelines.

14. Busbars Where load bus bars are utilized, they shall be COMPLY
tin plated round-edge high conductivity copper SCHNEIDER ASCO ATS has been manufactured to operate with
and be sized for 100% continuous load rating of load bus bars that are utilized and it is tin plated rounded-edge
the transfer switch, in accordance with NEMA, high conductive and which is sized for 100% continuous load
CSA and UL guidelines. The short circuit rating and also works in accordance of NEMA, CSA and UL
withstand rating of the completed bus assembly guidelines.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

shall be not less than the short circuit fault


current of the system.

15. Cable connections Provision shall be made to terminate all COMPLY


incoming and outgoing power cables and SCHNEIDER ASCO ATS has been manufactured to operate with
grounding conductors. Connections shall be via cable connection provision to terminate all incoming and
screw type cable lugs. outgoing power cable and ground conductors.

16. Cable entry The automatic transfer switch shall be COMPLY


constructed to accommodate bottom entry of SCHNEIDER ASCO ATS has been manufactured to operate with
incoming generator power cables, incoming bottom cable entry port for power cables.
utility power cables and bottom exit of outgoing
load cables. Cable type shall be copper
conductors with appropriate size for carrying
the rated parameters.

17. Power switching unit The power switching units shall be fix- COMPLY
mounted, utilize fully enclosed contacts and SCHNEIDER ASCO ATS has been manufactured to operate with
their withstand/closing rating shall be equal to power switching units which is fix-mounted, utilize fully enclosed
or exceed the required withstand rating of the contacts.
complete system.

18. Brand new materials All materials and parts used in the unit COMPLY
shall be new, of current manufacture, of best SCHNEIDER ASCO ATS has been manufactured to operate with
industrial grade, and free from defects and brand new materials which are free from defects and
imperfections. imperfections.

19. De-energizing All internal control devices used in the COMPLY


capability automatic transfer switch shall be capable of SCHNEIDER ASCO ATS has been manufactured to operate with
being de-energized and isolated from the all internal control devices to be de-energized and isolated from
system by use of an accessible isolation plug the system by use of an accessible isolation plug.
for servicing procedures as required.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

20. Serviceability The automatic transfer switch design shall COMPLY


provide front accessible components and SCHNEIDER ASCO ATS has been manufactured to operate with
wiring for easy serviceability. Power or control to have serviceability capability and power/control connections.
connections, which are not readily serviceable
while the transfer switch is mounted in its
enclosure, are not acceptable.

21. Strength and rigidity The enclosure shall consist of a 16 gauge or COMPLY
better steel angle /channel framework and be of SCHNEIDER ASCO ATS has been manufactured to operate with
adequate strength and rigidity to endure enclosure consist of 16 gauge and has adequate strength and
normal conditions of use and to support all rigidity.
equipment mounted within. Bolt-on steel
panels and hinged doors shall form the outer
shell of the enclosure.

22. Seismic events The Transfer Switch shall be designed and COMPLIANT
withstanding constructed to withstand seismic events when SCHNEIDER ASCO ATS has been manufactured to operate with
capability in building correctly anchored to the building structure. to withstand seismic events when correctly anchored to the
structure building structure.

The Transfer Switch shall successfully COMPLY


withstand a seismic event with a spectral SCHNEIDER ASCO ATS has been manufactured to withstand
acceleration of minimum 200%. seismic event with a spectral acceleration of minimum 200%
Transfer Switch anchoring detail drawings shall COMPLY
be furnished by the Transfer Switch supplier to SCHNEIDER ASCO ATS is to be supplied with Transfer Switch
the Owner and Installation Contractor for anchoring detail drawings shall be furnished by the Transfer
compliance of seismic ratings. Switch supplier to the Owner and Installation Contractor for
compliance of seismic ratings.
23. Source of power for Transfer switch control power shall be obtained COMPLY
controlling from the source being transferred to. The SCHNEIDER ASCO ATS has been manufactured to have a control
controls shall not require any connection to power which is obtained from the source being transferred.
external power sources for normal automatic And the controls will not require any connection to external
operation. Transfer switches requiring control power sources for normal automatic operation.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

power solely from the engine starting (or other)


batteries are not acceptable.
A control circuit isolation plug shall be provided COMPLY
to isolate all control circuitry inside the transfer SCHNEIDER ASCO ATS has been manufactured to operate with a
switch to facilitate maintenance procedures. control circuit isolation plug which will be provided to isolate all
When isolated, there shall be no voltage present control circuitry inside the transfer switch to facilitate
on the control circuitry. maintenance procedures, and when isolated there will not be
voltage present on the control circuitry.
24. Control cables The transfer switch shall have control plugs for COMPLY
all interconnection to provide superior SCHNEIDER ASCO ATS has been manufactured to have a control
serviceability. Separate plugs shall be provided plugs for all interconnection to provide superior serviceability.
for voltage sensing, ATS controller, engine start And separate plugs will be provided for voltage sensing, ATS
outputs, programmable 1/0 and controller, Engine start outputs, programmable 1/0 and
communications. All plugs shall be keyed to communications. All plugs will be keypad to prevent incorrect
prevent incorrect installation. installation.

25. PLC module The automatic transfer switch shall include a COMPLY
fully integrated microprocessor-based Transfer SCHNEIDER ASCO ATS has been manufactured to operate with
Switch Controller which shall provide the PLC module which will include a fully integrated microprocessor
following key features: – based transfer switch controller which will provide the
A. Graphical 7" Color Touch Screen Operator following key features
Interface Display A. Graphical 7" Color Touch Screen Operator Interface Display
B. Open and/or Closed Transition Transfer B. Open and/or Closed Transition Transfer Control
Control C. Utility/Gen Voltage and Frequency Metering
C. Utility/Gen Voltage and Frequency Metering D. Modbus TM RTU Serial Communication
D. Modbus TM RTU Serial Communication E. 8 Programmable Relay Output Contacts/more
E. 8 Programmable Relay Output F. 16 Programmable Digital Inputs/more
Contacts/more G. Engine Start Output Contact
F. 16 Programmable Digital Inputs/more
G. Engine Start Output Contact
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

The transfer switch controller shall include an COMPLY


operator interface graphical color touch screen SCHNEIDER ASCO ATS has been manufactured to operate with a
display which shall be door mounted. The transfer switch controller which will include an operator
display shall contain the following features: interface graphical color touch screen display which will be door
A. 7.0-inch Diagonal Color Display Screen mounted, the display will contain the following features.
B. Capacitive Touchscreen A. 7.0-inch Diagonal Color Display Screen
C. Resolution 800 x 480 (WVGA) B. Capacitive Touchscreen
D. Wide Viewing Angle C. Resolution 800 x 480 (WVGA)
E. Serial, Ethernet, USB Ports D. Wide Viewing Angle
F. SD Card Memory Card E. Serial, Ethernet, USB Ports
F. SD Card Memory Card

The transfer switch controller display shall COMPLIANT


provide easy to navigate software menu screens SCHNEIDER ASCO ATS has been manufactured to operate with
for all ATS system information and control. the transfer switch controller display that will provide easy to
The following information shall be displayed navigate software menu screens for all ATS system.
within the software menu system: And the following information will be displayed on the screen
A. System Time/Date A. System Time/Date
B. ATS Power Mimic Bus B. ATS Power Mimic Bus
C. Source Available/ATS Position Indication C. Source Available/ATS Position Indication
D. Utility supply metering- 3 phase voltage and D. Utility supply metering- 3 phase voltage and frequency
frequency E. Generator supply metering- 3 phase voltage and frequency
E. Generator supply metering- 3 phase voltage F. ATS Load metering -3 phase voltage
and frequency G. Timer countdown display
F. ATS Load metering -3 phase voltage H. ATS Control Modes (Auto/Off/Manual/Engine Start)
G. Timer countdown display I. Data Logging of Events
H. ATS Control Modes J. Alarm Summary
(Auto/Off/Manual/Engine Start) K. Alarm Logs
I. Data Logging of Events L. Event Logs
J. Alarm Summary M. Virtual Synchro scope
K. Alarm Logs N. Calendar-Based Exercise Scheduler
L. Event Logs
M. Virtual Synchro scope
N. Calendar-Based Exercise Scheduler
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

The Transfer Switch Controller shall be an COMPLY


Intelligent Electronic Device (IED) which shall SCHNEIDER ASCO ATS has been manufactured to operate with
have a unique Internet Protocol (IP) Address for an Intelligent Electronic Device (IED) which shall have a unique
programming/configuring and remote Internet Protocol (IP) Address for programming/configuring and
communication. remote communication.

The Transfer Switch Controller shall be capable COMPLY


of operating in conjunction with other ATS SCHNEIDER ASCO ATS has been manufactured to operate in
controllers on a common Ethernet conjunction with other ATS controllers on a common ethernet
communication network. communication network.

Password Security: The transfer switch COMPLY


controller software program shall include a SCHNEIDER ASCO ATS has been manufactured to operate with
three (3) level security password system for three level of password security for access to all programming
access to all programming functions. Specific functions, specific password levels is going to be provided for
password levels shall be provided for "read “read only”, “read/write” and. "administrator". Password security
only", "read/write" and "administrator". will allow for users to be named with individual user names and
Password security shall allow for users to be login passwords.
named with individual user names and login
passwords.

All programming/configuring of the transfer COMPLY


switch controller set points SCHNEIDER ASCO ATS has been manufactured to operate with
including voltage, frequency and time delays programming or configuring feature of frequency voltage and
shall be software programmable from the front time delays in the front panel.
door mounted graphical display screen.

Utility/Gen Metering: Digital and Analog (i.e. COMPLY


graphical representative) metering shall be SCHNEIDER ASCO ATS
provided by the transfer switch controller for has been manufactured to operate with the following standard
the Utility and Generator supplies. The transfer metering features which will be provided for the utility and
switch controller shall have an accuracy of +- generator supplies;
0.5% (Full Scale) for all voltage and frequency A. Digital and graphical analog display of AC voltages.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

readings. The following standard metering B. Three phase or single-phase voltages (Line to Line & Line to
features shall be provided for the utility and Neutral).
generator supplies; C. Phaser diagram showing graphical phase relationship
A. Digital and graphical analog display of AC and voltage magnitude.
voltages. D. Symmetrical Component Diagrams (Positive, Negative &
B. Three phase or single-phase voltages (Line Zero sequence display).
to Line & Line to Neutral). E. Voltage phase rotation indication.
C. Phaser diagram showing graphical F. Frequency display to 0.1 Hz resolution.
phase relationship and voltage magnitude.
D. Symmetrical Component Diagrams
(Positive, Negative & Zero sequence display).
E. Voltage phase rotation indication.
F. Frequency display to 0.1 Hz resolution.
26.
26.1 Voltage and frequency
sensing The Transfer Switch controller shall have fully COMPLY
integrated 220-600V, 3 phase true RMS AC SCHNEIDER ASCO ATS
voltage sensing on the Utility Supply, generator has been manufactured to operate with fully integrated 220V-
supply and ATS Load bus for operation and 600V three phase true RMS AC voltage sensing on the utility
monitoring. Programmable set points shall be supply, generator supply and ATS load bus for operation and
provided for utility/generator source under monitoring.
voltage, overvoltage and phase unbalance.
AC voltage sensing shall utilize advanced COMPLY
symmetrical component algorithms to SCHNEIDER ASCO ATS
determine positive, negative and zero sequence has been manufactured to operate with AC voltage sensing with
voltages. This shall provide the capability to utilize advance symmetrical component algorithms to determine
detect true phase loss/unbalance (i.e. single positive, negative and zero sequence voltages, this will provide
phasing) protection on 3 phase systems where the capability to detect true phase loss/unbalance (i.e. single
re-generative phase voltages maybe present phasing) protection on 3 phase systems where re-generative
due to failed 3 phase transformers or motor phase voltages maybe present due to failed 3 phase transformers
loads. or motor loads.
AC Voltage sensing shall be fully configurable to COMPLY
allow operation on 3 phase 3 wire and 3 phase SCHNEIDER ASCO ATS
4 wire systems without use of additional has been manufactured to operate with AC Voltage sensing which
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

potential transformers on systems 60OVAC or is fully configurable to allow operation on 3 phase 3 wire and 3
below. phase 4 wire systems without use of additional potential
transformers on systems 60OVAC or below.

Phase Sequence & Phase Reversal COMPLY


Protection: Phase Sequence/Phase reversal SCHNEIDER ASCO ATS
protection shall be provided to inhibit transfer has been manufactured to operate with phase sequence and
between alternate sources should an incorrect phase reversal protection: which will provide to inhibit transfer
phase sequence condition exist between between alternate sources, the transfer switch controller then
connected sources. The Transfer Switch provide capability to program either ABC or CBA phase rotation.
controller shall provide capability to program
either A-B-C or C-B-A phase rotation.
Under Voltage Sensing: Three phase under COMPLY
voltage sensing shall be provided for both utility SCHNEIDER ASCO ATS
and generator supplies. Activation of an has been manufactured to operate with under voltage sensing
abnormal under voltage condition on any phase which will enables the generator to turn off while the under
shall initiate a load transfer to the alternate voltage sensed, The under voltage sensor is user adjustable from
source or shall inhibit a transfer to a source 70-100% of nominal and is based on a falling (i.e. drop-out)
until its voltage levels are within normal limits. voltage. The under-voltage sensor is factory set for drop-out at
The under voltage sensor shall be user 85% nominal voltage. The under voltage sensor will reset (i.e.
adjustable from 70-100% of nominal and shall pick-up) 5% above the dropout setting and is adjustable. The
be based on a falling (i.e. drop-out) voltage. under voltage sensor then include an adjustable transient time
The under voltage sensor shall be factory set delay feature
for drop-out at 85% nominal voltage. The
under voltage sensor shall reset (i.e. pick-up)
5% above the dropout setting and shall be
adjustable. The under voltage sensor shall
include an adjustable transient time delay
feature.
Over Voltage Sensing: Three phase over COMPLY
voltage sensing shall be provided for both utility SCHNEIDER ASCO ATS
and generator supplies. Activation of an has been manufactured to operate with over voltage sensing it
abnormal over voltage condition on any phase enables the generator to turn off when the over voltage limit set
shall initiate a load transfer to the alternate point is reached. The over voltage sensor is user adjustable from
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

source or shall inhibit a transfer to a source 100-130% of nominal and is based on a rising (i.e. pick-up)
until its voltage levels are within normal voltage. The over voltage sensor is factory set for pick-up at 115%
limits. The over voltage sensor shall be user nominal voltage. The over voltage sensor is reset (i.e. drop-out)
adjustable from 100-130% of nominal and shall 5% below the pick-up setting and is user adjustable. The over
be based on a rising (i.e. pick-up) voltage. The voltage sensor includes an adjustable transient time delay
over voltage sensor shall be factory set for pick- feature.
up at 115% nominal voltage. The over voltage
sensor shall reset (i.e. drop-out) 5% below the
pick-up setting and shall be adjustable. The
over voltage sensor shall include an adjustable
transient time delay feature.
Phase Unbalance/Phase Loss Sensing: COMPLY
Voltage phase unbalance/phase loss sensing SCHNEIDER ASCO ATS
shall be provided for the generator and utility has been manufactured to operate with phase loss sensing or
supplies. Activation of an abnormal utility phase unbalance sensing, this will enable the generator to turn off
phase unbalance condition shall initiate the when the generator it senses phase unbalance or phase loss.
generator to start and to transfer on load. The The voltage phase unbalance sensor is user adjustable from 3-
voltage phase unbalance sensor shall be user 30% of nominal and is factory set for pick-up at 5% nominal
adjustable from 3-30% of nominal and shall be voltage. The voltage phase unbalance sensor includes an
factory set for pick-up at 5% nominal voltage. adjustable transient time delay feature.
The voltage phase unbalance sensor shall
include an adjustable transient time delay
feature.
Under Frequency Sensing: Under frequency COMPLIANT
sensing shall be provided for both utility and SCHNEIDER ASCO ATS
generator supplies. Activation of an abnormal has been manufactured to operate with under frequency sensing
under frequency condition shall initiate a load which will provide for both utility and generator supplies.
transfer to the alternate source or shall inhibit The under frequency sensor is user adjustable from 70-100% of
a transfer to a source until its frequency nominal and is based on a falling {i.e. drop-out) frequency. The
levels are within normal limits. The under under frequency sensor is factory set for drop out at 80%
frequency sensor shall be user adjustable from nominal frequency. The under frequency sensor is reset {i.e.
70-100% of nominal and shall be based on a pick-up) 10% above the dropout setting and is adjustable. The
falling {i.e. drop-out) frequency. The under under-frequency sensor includes an adjustable transient time
frequency sensor shall be factory set for delay feature.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

drop out at 80% nominal frequency. The


under frequency sensor shall reset {i.e. pick-
up) 10% above the dropout setting and shall
be adjustable. The under-frequency sensor
shall include an adjustable transient time delay
feature.
Over Frequency Sensing: Over frequency COMPLY
sensing shall be provided for both utility and SCHNEIDER ASCO ATS
generator supplies. Activation of an abnormal has been manufactured to operate with over frequency sensing
over frequency condition shall initiate a load which will provide for both utility and generator supplies.
transfer to the alternate source or shall inhibit a The over frequency sensor is user adjustable from 100-130% of
transfer to a source until its frequency levels are nominal and is based on a rising (i.e. pick-up) frequency. The
within normal limits. The over frequency sensor over frequency sensor is a factory set at 115% nominal voltage.
shall be user adjustable from 100-130% of The over frequency sensor is reset (i.e. drop-out) 5% below the
nominal and shall be based on a rising (i.e. pick- pick-up setting and it is user adjustable. The over frequency
up) frequency. The over frequency sensor shall sensor includes an adjustable transient time delay feature.
be factory set at 115% nominal voltage. The
over frequency sensor shall reset (i.e. drop-out)
5% below the pick-up setting and shall be
adjustable. The over frequency sensor shall
include an adjustable transient time delay
feature.
27.1 Time delays for The following time delay functions shall be COMPLY
different cases provided within the transfer switch controller: SCHNEIDER ASCO ATS
Engine Start - A time delay on engine start has been manufactured to operate with time delay function which
shall be provided to delay the engine start will provide within the transfer switch controller.
signal after failure of the utility source. The time And the time delay on engine start will be provided to delay the
delay shall be user adjustable 0- 60 seconds, engine start signal after utility sources, The time delay for engine
factory set at three (3) seconds. is to be user adjustable 0- 60 seconds, factory set at three (3)
seconds.
Engine Warmup - A time delay for engine COMPLY
warm up shall be provided which permits SCHNEIDER ASCO ATS
transfer to the generator supply after generator has been manufactured to operate with engine warmup time
voltage and frequency have reached acceptable delay with user adjustable, The time delay is to be user adjustable
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

limits. The time delay shall be user adjustable 0- 0-60 minutes, factory set at two (2) seconds.
60 minutes, factory set at two (2) seconds.
Utility Return - A time delay for return to COMPLY
utility shall be provided which permits a re- SCHNEIDER ASCO ATS
transfer back to the utility supply only after has been manufactured to operate with utility return time delay
stable voltage and frequency condition exists with user adjustable, The time delay is to be user adjustable 0-60
for the specified time period. The time delay minutes, factory set at two (2) minutes.
shall be user adjustable 0-60 minutes, factory
set at two (2) minutes.
Engine Cooldown - A time delay for engine COMPLY
cooldown shall be provided which delays the SCHNEIDER ASCO ATS
engine stop signal after load has retransferred has been manufactured to operate with engine cooldown delay
back to the utility source. The time delay shall time with user adjustable, The time delay is user adjustable 0- 60
be user adjustable 0- 60 minutes, factory set at minutes, factory set at two (2) minutes.
two (2) minutes.
Neutral Delay - A time delay for neutral COMPLY
position shall be provided in the open SCHNEIDER ASCO ATS
transition mode to minimize the effect of out-of- has been manufactured to operate with neutral delay time with
phase transfer due to connected motor load. user adjustable time frame, The time delay is user adjustable 0-
The time delay shall be user adjustable 0- 120 120 seconds, factory set at three (3) seconds.
seconds, factory set at three (3) seconds.
Gen Commit to Transfer Delay - A time delay COMPLIANT
for Gen Commit to Transfer position shall be SCHNEIDER ASCO ATS
provided. Should the generator fail to transfer has been manufactured to operate with gen commit time delay
on load with the "commit to transfer" feature with transfer position to be provided, The time delay is user
enabled, the ATS shall automatically re-transfer adjustable 0-600 seconds, factory set at three hundred (300)
back to the utility supply if within nominal seconds.
limits following expirary of the "Gen Commit
to Transfer" timer. The time delay shall be
user adjustable 0-600 seconds, factory set at
three hundred (300) seconds.
Transfer Fail Delay - A time delay for Transfer COMPLY
Fail delay shall be provided. SCHNEIDER ASCO ATS
has been manufactured to operate with transfer fail delay with
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

The timer shall activate a fail alarm condition if user adjustable time frame, The time delay is user adjustable 0-
the transfer switch fails to successfully transfer 600 seconds, factory set at thirty (30) seconds.
within the transfer fail time delay setting. The
time delay shall be user adjustable 0- 600
seconds, factory set at thirty (30) seconds.
28
29. Timer Bypass: The transfer controller shall provide a timer COMPLY
bypass function to automatically bypass SCHNEIDER ASCO ATS
unwanted delays during testing or maintenance has been manufactured to operate with a timer bypass function to
procedures. The timers shall automatically reset automatically bypass unwanted delays during testing or
on the next operation sequence to their original maintenance procedures, and the time delays will have a user-
setting. The following time delays shall have a initiated bypass features-
user-initiated bypass feature: A. Engine Warmup Delay
A. Engine Warmup Delay B. Utility Return Timer
B. Utility Return Timer C. Engine Cooldown Timer
C. Engine Cooldown Timer D. Neutral Delay Timer
D. Neutral Delay Timer
30. Real time clock The transfer controller shall provide a real-time COMPLIANT
clock to display system time and date for use by SCHNEIDER ASCO ATS
event logging and the ATS exercise scheduler. has been manufactured to operate with real time clock to display
The real-time clock shall have automatic system time and date for use by event logging and the ATS
shifting of date/time for daylight savings and exercise scheduler
leap year occurrences. The real-time time clock
shall be powered by an independent 10 year life
battery to maintain all time/date settings upon
loss of control power.
31. ATS Status The transfer switch controller shall provide the COMPLY
Indication: following indication lights/icons on a common SCHNEIDER ASCO ATS
screen for simple visual indication of ATS has been manufactured to operate with ATS status indication
status: which will provide the following indication screen for simple
A. Utility/Gen Source available visual indication of the ATS status
B. Load Bus Energized A. Utility/Gen Source available
C. ATS Position: Utility or Generator Source B. Load Bus Energized
Connected to Load C. ATS Position: Utility or Generator Source Connected to Load
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

D. Engine Start Signal Initiated D. Engine Start Signal Initiated


E. ATS in TEST or Exercise Mode E. ATS in TEST or Exercise Mode
F. Load Shed is active F. Load Shed is active
G. Current ATS Operating Mode G. Current ATS Operating Mode (Auto/Off/Man/Test)
(Auto/Off/Man/Test) H. Common alarm (Flashing Icon)
H. Common alarm (Flashing Icon) I. Security Access Locked/Unlocked
I. Security Access Locked/Unlocked
32 Alarm Annunciation: The transfer switch controller shall provide an COMPLY
alarm annunciation screen to indicate the status SCHNEIDER ASCO ATS
of all individual alarm conditions on the ATS. has been manufactured to operate with alarm annunciation which
The alarm screen shall have an alarm reset will have an alarm reset function.
function.
33. Alarms Log: The transfer switch controller shall provide an COMPLY
alarm log screen to indicate a history of recent SCHNEIDER ASCO ATS
alarms. All alarm logs shall be provided with a has been manufactured to operate with alarm logs and the
time/date stamp and the name of user who transfer switch controller will provide an alarm log screen to
reset the alarm. Alarm logs can be filtered by indicate a history of recent alarms.
calendar date.
34. Events Log: The transfer switch controller shall provide an COMPLY
event log screen to indicate a history of recent SCHNEIDER ASCO ATS
events. All event logs shall be provided with a has been manufactured to operate with event logs which can be
time/date stamp and the name of user who filtered by calendar date.
activated/deactivated a specific event. Event
logs can be filtered by calendar date.
35. Virtual Synchro For transfer switches equipped with open COMPLY
scope: transition -fast transfer or closed transition SCHNEIDER ASCO ATS
transfer mechanisms, the transfer controller has been manufactured to operate with virtual synchro scope
display shall indicate the operating status of the which will include the following displays
"in-sync" transfer operation. Operating status A. Virtual Synchro scope showing graphical phase degree and
shall include the following display features: speed (slow-fast) representation between the two sources prior
A. Virtual Synchro scope showing graphical to transfer operation.
phase degree and speed (slow-fast) B. Voltage Difference meter displayed in% system voltage
representation between the two sources prior C. Slip Frequency meter displayed in% of system frequency
to transfer operation. D. Generator and Utility Phase A-N voltage
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

B. Voltage Difference meter displayed in% E. Generator and Utility frequency


system voltage
C. Slip Frequency meter displayed in% of
system frequency
D. Generator and Utility Phase A-N voltage
E. Generator and Utility frequency
36. ATS Control Mode: The transfer switch controller shall provide COMPLY
selectable operating modes available from the SCHNEIDER ASCO ATS
main operating screen. The following operating has been manufactured to operate with ATS control mode of
modes shall be provided: selectable operating modes available from the main operating
A. Auto: ATS shall operate automatically during screen.
a utility power failure And the following operating model will be provided
B. Off: ATS shall not start engine or transfer A. Auto: ATS will operate automatically during a utility power
load during a utility power failure failure
C. Manual: ATS can be operated manually to B. Off: ATS not start engine or transfer load during a utility
the desired source. power failure
D. On Load Test: ATS shall be selected to C. Manual: ATS can be operated manually to the desired source.
operate in On-Load test mode and permit load D. On Load Test: ATS can be selected to operate in On-Load test
transfer mode and permit load transfer
E. Off Load Test: ATS shall be selected to E. Off Load Test: ATS can be selected to operate in Off-Load test
operate in Off-Load test mode and shall not mode and shall not permit load transfer
permit load transfer F. Timed Test: ATS can be selected to operate in a Timed test
F. Timed Test: ATS shall be selected to mode
operate in a Timed test mode G. Closed Transition: ATS can be selected to operate in a Closed
G. Closed Transition: ATS shall be selected to Transition Transfer mode
operate in a Closed Transition Transfer mode H. Cyclic: to operate DG in programmable cyclic mode with
H. Cyclic: to operate DG in programmable selectable priorities.
cyclic mode with selectable priorities.
Utility Retransfer Operation Selection: The
operator interface display shall provide a
selection for Utility Re-transfer operation. The
utility re-transfer operation shall be user
selectable for Automatic, or Manual re-transfer
operation. When Manual re-transfer mode is
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

selected, the user can initiate when the


retransfer to utility power shall occur.
37. Test Modes: The transfer switch controller shall provide the COMPLY
following user selectable test modes and SCHNEIDER ASCO ATS
features: has been manufactured to operate with transfer switch controller
A. On Load/Off Load: The operator interface which will provide the following user selectable test modes and
shall provide selection of "OFF• LOAD” testing features
(i.e. load does not transfer to generator) or A. On Load/Off Load: The operator interface to be provide
“ONLOAD" testing (i.e. load transfers to selection of "OFF• LOAD” testing or “ONLOAD" modes.
generator) modes. B. Automatic Timed Test Modes: Automatic timed test mode
B. Automatic Timed Test Modes: Automatic to be provided to allow for tests to be manually initiated and
timed test mode shall be provided to allow for automatically terminated. Timed test modes to be user adjustable
tests to be manually initiated and automatically (0-999 minutes). The load will then automatically re-transfer
terminated. Timed test modes shall be user back to the utility supply and then the generator fail on load.
adjustable (0-999 minutes). The load shall C. Automatic Gen Exerciser: A calendar based automatic
automatically re-transfer back to the utility exercise time function to be provided for generator testing. The
supply should the generator fail on load. Exercise scheduler to be fully programmable for; start/stop date
C. Automatic Gen Exerciser: A calendar & time, duration of the test and type of test mode (i.e. On-Load or
based automatic exercise time function shall be Off-Load). The exercise timer will utilize the transfer controller’s
provided for generator testing. The Exercise internal time clock for referencing all timing functions. The
scheduler shall be fully programmable for; transfer switch will automatically re-transfer back to the utility
start/stop date & time, duration of the test and supply if the generator set fails during an exercise period.
type of test mode (i.e. On-Load or Off-Load).
The exercise timer shall utilize the transfer
controller’s internal time clock for referencing
all timing functions. The transfer switch shall
automatically re-transfer back to the utility
supply if the generator set fails during an
exercise period.
38. Scheduler: A calendar-based scheduler shall be provided COMPLY
by the transfer switch controller. The scheduler SCHNEIDER ASCO ATS
shall operate based on the transfer switch has been manufactured to operate with scheduler which will
controller real-time clock. The scheduler shall provide by the transfer switch controller. The user can program
allow users to program over 20 specific event over 20 specific event schedules,
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

schedules to be added. Each event can be edited the scheduler allows the following programming functionalities.
individually and its operating status can be A. Schedule Event Start Date/Time
monitored. The scheduler shall allow the B. Event Period (Day/Week/Month/Year)
following programming functionality: C. Schedule Event Stop Date/Time
A. Schedule Event Start Date/Time D. Event Duration (mins/hours)
B. Event Period (Day/Week/Month/Year) E. Event Operation Type (Off-Load Test, On-Load Test)
C. Schedule Event Stop Date/Time F. Number of Re-occurring Events (one-time or number of
D. Event Duration (mins/hours) events)
E. Event Operation Type (Off-Load Test, On-
Load Test)
F. Number of Re-occurring Events (one-time or
number of events)
39. Transfer Switch Fail The following transfer switch failure logic and COMPLY
Logic: alarming shall be provided during open or SCHNEIDER ASCO ATS
closed transition transfer sequences has been manufactured to operate with the transfer switch fail
A. Transfer Fail: Control logic shall be provided logic and alarms to be provided during open or closed transition
for sensing a transfer switch failure in open or transfer sequences.
closed transition mode. When an alarm A. Transfer Fail: Control logic to be provided for sensing a
condition is activated, the transfer controller transfer switch failure in open or closed transition mode. When
shall automatically force a transfer to the an alarm condition is activated, the transfer controller will
alternate source if available. automatically force a transfer to the alternate source if available.
B. Power Switching Device Fail: Control B. Power Switching Device Fail: Control logic to be provided to
logic shall be provided to detect if a power detect if a power switching device fails to close or open during
switching device fails to close or open during an open or closed transition operating sequence. and a power
an open or closed transition operating switching device fail to close or open for any reason within a
sequence. Should a power switching device fail preset time period (adjustable), an alarm light and alarm relay
to close or open for any reason within a preset contact will then be activated.
time period (adjustable), an alarm light and C. Gen Failure: Control logic shall be provided for immediate
alarm relay contact shall be activated. transfer to the utility supply (if within acceptable limits)
C. Gen Failure: Control logic shall be provided should the generator set fail during any activated test mode.
for immediate transfer to the utility supply (if
within acceptable limits) should the
generator set fail during any activated test
mode.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

40. Gen Commit to Programmable control logic shall be provided to COMPLY


Transfer Logic: select whether or not the load shall be SCHNEIDER ASCO ATS
transferred to the generator (following a utility has been manufactured to operate with gen commit to transfer
power failure) if the utility supply is logic
restored immediately before the generator will provide to select whether or not the load to be transferred to
transfers on load. With the feature programmed the generator, if the utility supply is restored immediately before
as NO (DISABLED), the transfer switch shall the generator transfers on load, and features programmed as NO
not commit a transfer to the generator after the the transfer switch will no commit a transfer to the generator
engine start delay has expired, but shall return after the engine start delay has expired, but it will return to the
to the utility supply if immediately restored. utility supply if immediately restored.
With the feature programmed as YES With a feature programmed as YES the transfer switch will
(ENABLED), the transfer switch shall commit a commit a transfer to the generator after the engine start delay has
transfer to the generator after the engine start expired, this features will then automatically cancelled after
delay has expired. This feature shall be expiry of the Gen commit to transfer timer with 5 minutes user
automatically cancelled after expirary of the adjustable with the generator fail to start.
Gen Commit to Transfer timer (5 mins
adjustable) should the generator fail to start.
41. Load Disconnect Control logic shall be provided to signal an COMPLY
Contact (LDC): external load (e.g. elevator) of an impending SCHNEIDER ASCO ATS
transfer to and from the generator supply. The has been manufactured to operate with load Disconnect contact
contact shall close prior to a transfer and (LDC) which have different features that have all the required
remain closed until the transfer is completed points raised here, A pre-transfer delay function is to be provided,
and the post transfer delay time has expired. A programmable O – 30 seconds. A post transfer delay function is to
pre-transfer delay function shall be provided, be provided, programmable O - 30 seconds.
programmable O – 30 seconds. A post transfer
delay function shall be provided, programmable
O - 30 seconds.
42. Engine Start Two (2) engine start contacts shall be provided COMPLY
Contacts: which shall close to initiate starting of the SCHNEIDER ASCO ATS
engine. has been manufactured to operate with engine start contacts
which will provide which has close to initiate starting of the
engine.
43. Load Shed: The transfer controller shall have provisions to COMPLY
provide a load shed output contact via SCHNEIDER ASCO ATS
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

assignment of one of the programmable output has been manufactured to operate with load shed output contact
contacts. The Load shed output shall be via assignment of one of the programmable output contacts.
activated whenever the generator transfers on And the load shed output will then be activated whenever the
load and shall reset once the utility supply generator transfers on load and will reset once the mains back on
retransfers back on load. the Load shed feature load.
shall be programmable based on a generator And the load shed feature is programmable based on a generator
kW load set point. KW load set point.
44. User Programmable a minimum of Sixteen (16) user programmable COMPLY
Digital Inputs: digital inputs shall be provided by the transfer SCHNEIDER ASCO ATS
controller. The digital inputs shall accept a dry has been manufactured to operate with user programmable
(isolated) logic contact to switch to DC digital inputs. With a minimum of Sixteen (16) user
negative(ground). Each input shall allow programmable digital inputs that will be provided by the transfer
mapping to over 30 different control or controller.
monitoring functions as available within the The digital input will accept a dry (isolated) logic contact to
transfer controller database. The following switch to DC negative(ground), each input allow mapping to over
inputs shall be mapped as factory defaults: 30 different controller or monitoring functions.
A. Remote Test - Utility Power Fail Simulate And the following inputs will be mapped as factory defaults
(Close to Test) A. Remote Test - Utility Power Fail Simulate (Close to Test)
B. Remote Alarm Reset (Momentary Close to B. Remote Alarm Reset (Momentary Close to Reset)
Reset) C. Service Disconnect Mode Activated (External Control Switch)
C. Service Disconnect Mode Activated (External D. Utility Power Switching Device (USD) Tripped
Control Switch) E. Generator Power Switching Device (GSD) Tripped
D. Utility Power Switching Device (USD) F. Transfer Control in Manual (External Control Switch)
Tripped G. Transfer Control in Closed Transition Mode (External Control
E. Generator Power Switching Device (GSD) Switch)
Tripped H. Utility Power Switching Device (USD) Open
F. Transfer Control in Manual (External I. Generator Power Switching Device (GSD) Open
Control Switch) J. Generator Bypass Switch (GB) Closed
G. Transfer Control in Closed Transition Mode K. Utility Bypass Switch (NB) Closed
(External Control Switch) L. Load Isolate Switch (LI) Closed
H. Utility Power Switching Device (USD) Open M. Generator Isolate Switch {GI) Closed
I. Generator Power Switching Device (GSD) N. Utility Isolate Switch {NI) Closed
Open 0. Inhibit Transfer to Utility (Source 1)
J. Generator Bypass Switch (GB) Closed P. Inhibit Transfer to Generator (Source 2/3)
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

K. Utility Bypass Switch (NB) Closed


L. Load Isolate Switch (LI) Closed
M. Generator Isolate Switch {GI) Closed
N. Utility Isolate Switch {NI) Closed
0. Inhibit Transfer to Utility (Source 1)
P. Inhibit Transfer to Generator (Source 2/3)
45. User Programmable minimum of Eight (8) user programmable COMPLY
Output Contacts: output contacts shall be provided by the SCHNEIDER ASCO ATS
transfer controller. Each output contact shall be has been manufactured to operate with user programmable
user programmable. The following outputs shall output contacts: with a minimum of eight user programmable
be mapped as factory defaults: output contacts.
A. Load on Utility (AUX U) And the following outputs will be mapped as factory defaults.
B. Load on Generator (AUX G) A. Load on Utility (AUX U)
C. Load Disconnect Contact (LDC) B. Load on Generator (AUX G)
D. Fail to Transfer (FIT) C. Load Disconnect Contact (LDC)
E. ATS Not in Auto D. Fail to Transfer (FIT)
F. ATS in Auto E. ATS Not in Auto
G. Utility Power Available {UPA} F. ATS in Auto
H. Generator Power Available {GPA) G. Utility Power Available {UPA}
Remote Alarm Contacts: A factory installed H. Generator Power Available {GPA)
common alarm output Normally Open, for
connection to the remote management system COMPLY
shall be included. Remote management system SCHNEIDER ASCO ATS
shall be included having the following contact. has been manufactured to operate with remote alarm contacts.
A. Load on Utility And also included remote management system with the following
B. Load on New Generator Set contact
C. Load on Existing Generator Set A. Load on Utility
B. Load on New Generator Set
C. Load on Existing Generator Set
46. Transfer to Controller shall provide a programmable digital COMPLY
Generator Inhibit: input to inhibit transfer to generator until SCHNEIDER ASCO ATS
external signal is removed. Input can be utilized has been manufactured to operate with transfer to generator
in multiple generator/ATS applications. inhibit
and the Controller will provide a programmable digital input to
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

inhibit transfer to generator until external signal is removed.


Input can be utilized in multiple generator/ATS applications.
47. In-Sync Transfer For transfer switches equipped to operate in COMPLY
Sensor: a fast "open" or "closed" transition transfer SCHNEIDER ASCO ATS
sequence, the transfer switch controller shall has been manufactured to operate with in-sync transfer sensor
provide an integrated "in-sync" transfer which has many uses in the system, The in-sync sensor is also
sensor to safely permit in-sync transfers to provide a zero degree closing angle target by utilization of
occur when both sources are available. The in- anticipatory closing angle control logic for different levels of slip
sync transfer sensor shall provide adjustable frequency.
voltage and frequency thresholds to only permit
transfers when the two sources are safely in
phase. The in-sync sensor shall also provide a
zero degree closing angle target by utilization
of anticipatory closing angle control logic for
different levels of slip frequency.
48. Modbus TCP The transfer switch controller shall provide a COMPLY
Ethernet l00BaseT Ethernet port for customer SCHNEIDER ASCO ATS
Communication: connection to a remote data monitoring device has been manufactured to operate with MODBUS TCP/IP ethernet
such as PLC or desktop PC. The Ethernet Port communication which will provide a l00BaseT Ethernet port for
shall provide Modbus TCP protocol with data customer connection to a remote data monitoring device such as
registers defined in the Modbus Communication PLC or desktop PC. The Ethernet Port will provide Modbus TCP
Manual. The Modbus port shall provide the protocol with data registers defined in the Modbus
following main data register information: Communication Manual. The Modbus port will provide different
A. ATS Position Status functionalities such as below
B. ATS Source and Load Status A. ATS Position Status
C. Alarm status B. ATS Source and Load Status
D. Utility/Generator 3 Phase Voltage C. Alarm status
E. ATS Load Bus voltage D. Utility/Generator 3 Phase Voltage
F. ATS Load Bus Power Metering (kW, kVA, E. ATS Load Bus voltage
kVAR, PF) when power metering option is F. ATS Load Bus Power Metering (kW, kVA, kVAR, PF) when
provided). power metering option is provided).
G. Event logging data G. Event logging data
H. Remote operation H. Remote operation
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

49. Data Logging The transfer controller shall provide data COMPLY
Memory: logging and shall store the data in non-volatile SCHNEIDER ASCO ATS
memory on a removable SD memory card. The has been manufactured to operate with data logging memory
following events shall be recorded and stored: with different functionalities
A. Total Number of Transfers and the following event will be recorded and stored
B.Total Number of Transfers due to source A. Total Number of Transfers
failure B.Total Number of Transfers due to source failure
C. Number of Hours Controller is energized C. Number of Hours Controller is energized
D. Number of Hours Load is on Utility D. Number of Hours Load is on Utility
E. Number of Hours Load is on Generator E. Number of Hours Load is on Generator

50. Four Source -controller shall include a Master/Slave COMPLY


Transfer Control functionality for use in configuring two SCHNEIDER ASCO ATS
independent transfer switches as a three-source has been manufactured to include a Master/Slave functionality
transfer system. for use in configuring two independent transfer switches as a
three-source transfer system.
51. Redundancy ATS should have redundant ATS controller. COMPLY
SCHNEIDER ASCO ATS
has been manufactured to have redundant ATS controller
52. Sequence of - In the event of a source 1 power failure the COMPLY
operations Master ATS controller shall check utility power SCHNEIDER ASCO ATS
source 2 then switch to utility 2. If utility 1 and has been manufactured to operate with sequence of operations
2 are not available it should send an engine like below
start signal to the slave input on the Slave In the event of a source 1 power failure the Master ATS controller
controller. The slave controller shall send an shall check utility power source 2 then switch to utility 2. If utility
engine start signal to both generators. If a 1 and 2 are not available it then send an engine start signal to the
preferred generator is selected, the Slave slave input on the Slave controller. The slave controller then send
controller will count down through the time an engine start signal to both generators. If a preferred generator
delay for engine failure and remain on the is selected, the Slave controller will count down through the time
preferred generator if it is available. If the delay for engine failure and remain on the preferred generator if
preferred generator is not available at that time, it is available. If the preferred generator is not available at that
the Slave ATS will transfer to the non-preferred time, the Slave ATS will transfer to the non-preferred generator. If
generator. If none-preferred is selected, the none-preferred is selected, the Slave ATS will transfer to the first
Slave ATS will transfer to the first available available generator. The unused generator will be shut down as
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

generator. The unused generator will be shut soon as the Slave ATS is connected to a good source.
down as soon as the Slave ATS is connected to a
good source.
53. Lockable access doors The ATS shall be equipped with lockable access COMPLY
doors. SCHNEIDER ASCO ATS
has been manufactured to operate with equipped lockable access
doors.
54. Priorities The ATS should support selecting priorities COMPLY
among the connected DG to start and have a SCHNEIDER ASCO ATS
cyclic operation feature. has been manufactured to support selecting priorities among the
connected DG to start and have a cyclic operation feature.
55. Wiring diagram and The manufacturer shall furnish complete COMPLY
schematics schematic and wiring diagrams for the SCHNEIDER ASCO ATS
particular automatic transfer switch and a is to be supplied with complete schematic and wiring diagrams.
typical wiring diagram for the entire system
showing all components, relays and part
numbers.
All wiring and connections to integrate the ATS
into the generator output shall be made by the
vendor before acceptance by the AMN
56. Weather proof This ATS shall be an integral part of the COMPLY
enclosure generator set and be secured to the weather- SCHNEIDER ASCO ATS
proof enclosure has been manufactured to operate with an integral part of the
generator set and be secured to the weather – proof enclosure.
57. Type of transition The transfer switch shall be open transition COMPLY
type, positively electrically and mechanically SCHNEIDER ASCO ATS
interlocked to prevent simultaneous closing and has been manufactured to operate with open type transition
mechanically held in both normal and which is electrically and mechanically interlocked.
emergency positions.
58. Protection Independent break before make action shall be COMPLIANT
used as protection to prevent dangerous source SCHNEIDER ASCO ATS
to source connections. has been manufactured to operate with independent break
protection before make action be used as protection to prevent
dangerous source to source connections.
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

59. Operation The transfer switch shall be approved for COMPLY


manual operation. The electrical operating SCHNEIDER ASCO ATS
means shall be approved for manual operation. has been manufactured to operate with manual operation as an
The electrical operating means shall be by option, Every portion of the contactor is positively mechanically
electric solenoid. Every portion of the contactor connected.
is to be positively mechanically connected.
60. Actuator The transfer switch electrical actuator shall COMPLY
have an independent disconnect means to SCHNEIDER ASCO ATS
disable the electrical operation during has been manufactured to have an independent disconnect means
manual switching. to disable the electrical operation during manual switching.
Main switch contacts shall be high pressure And the main switch contact will be high pressure silver alloy
silver alloy contacts to resist burning and contacts to resist burning and pitting for long life operation.
pitting for long life operation.
61. Input voltage Input voltage shall be stepped down to 24VAC COMPLY
for safety and reliability. SCHNEIDER ASCO ATS
has been manufactured to operate with input voltage which will
be stepped down to 24V AC for safety and reliability.
62. Indicator lamps Provide colored indicator lamps to be energized COMPLY
when the transfer switch position is in either SCHNEIDER ASCO ATS
UTILITY {white) or EMERGENCY (red). A third has been manufactured to operate with indicator lamps for all
lamp shall be provided to indicate STANDBY indication’s activities.
OPERATING (amber). These lights shall be
energized from utility or the engine-generator
set.
63. Operating handle Provide manual operating handle to allow for COMPLY
manual transfer. This handle shall be mounted SCHNEIDER ASCO ATS
inside the lockable enclosure so accessible only has been manufactured to operate with manual operating handle
by authorized personnel. to allow for manual transfer, and this handle is mounted inside
the lockable enclosure to accessible only by professionals or
authorized one
64. Safety switch Provide a safety disconnect switch to prevent COMPLY
load transfer and automatic engine start while SCHNEIDER ASCO ATS
performing maintenance. This switch will also has been manufactured to operate with safety switch that will
be used for manual transfer switch operation. prevent load transfer and automatic engine start while
TECHNICAL SPECIFICATION FOR AUTOMATIC TRANSFER SWITCH

performing maintenance, and this operation is used for also


manual operation.