Sample Description :
TERRANITE
Sample as Received
Customer Reference No
:
WO/PO No:
Sample Condition :
Sample Quantity (Approx) : Sample Size (Approx) :
SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED
Digitally signed
by Umesh Gupta
Date:
2018.02.12
14:37:25 +05:30
Report Issued By
Spectro Analytical Labs Limited E-41, Okhla Industrial Area, Phase-II, New Delhi-110020 (India)
Phone : +91-11-40522000, 41611000 || Fax : +91-11-40503150, 40503151 || Email: care@spectro.in
BIS, DGS&D, DDA, MOEF and DGCA Approved, ISO 9001:2008, ISO 14001:2004 & OHSAS 18001:2007 Certified Laboratory
Please refer to our Website www.spectro.in for Terms & Condition
Format No: SALLGN/TRF/GEN
Issue No: 01, Issue Date: 01.04.17
CIN: U74220DL1998PLC092698
TEST REPORT Page 2 of 3
Report No D180207068/D180207068-1
1 Leachable Elements
Hex.Chromium (as Cr+6) ,mg/kg < 0.10 IS: 3025 (P-52) 2003
Leaching condition
pH - 9.74
Digitally signed
by Umesh Gupta
Date:
2018.02.12
14:37:25 +05:30
Analyst Signature Authorised Signatory
Format No: SALLGN/TRF/GEN
Issue No: 01, Issue Date: 01.04.17
CIN: U74220DL1998PLC092698
TEST REPORT Page 3 of 3
Report No D180207068/D180207068-1
(i) Corrosion rate of copper plated earth electrode: µm/yr 7.3 (max) 5.34
(At non aggressive environments and applied voltage 30 mV) IEC 62561-7 /
2
Polarization resistance: Ω.m 4 (min) 5.25 ASTM G59-97 /
(ii) Corrosion rate of galvanized earth electrodes: µm/yr 9.9 (max) 6.32 ASTM G102-89
Conclusion:The sample meets the requirement given in the specification IEC 62561-7