DYNA-KIT

COMMUNICATION ADAPTER

TCB-DK01SS-E

Connection Instructions
Back Next
1
Contents

COMMUNICATION ADAPTER: TCB-DK01SS-E


Connection Adaptor
Internal View

Connection Cables
Type ‘A’, ‘B’, ‘C’

Kit Accessories:
Owners Manual, CD, USB & Serial PC
Connection Cables Connection Adaptor

Home Back Next


1
Set-up Configuration to connect Dyna Doctor

DI / SDI / MULTI SPLIT CONNECTION - 6 PIN


Operation Mode Setting: Serial Outdoor Unit Model Code
SW1: Bit 3 = OFF
DI (RAV-) DI (RAV-) IES (RAS-)
Operation mode Com baud rate
SW1 SW2 SM560AT-E SP404AT-E M14EAVE
SM561AT-E SP454AT-E M14EACVE
ON
SM562AT-E SP564AT-E M18EAVE
SM563AT-E SP804AT-E M18EACVE
OFF
1 2 3 4 1 2 3 4 SM801AT-E SP1104AT M14GAV
SM802AT-E SP1404AT-E M14GACV
DYNA KIT ADAPTER SM803AT-E SP1604AT-E M18GAV
M18GAV2C
CN 800
SERIAL PARALLEL CN 804 CN 009
CN 101 CN 102 SM2244AT-E
5M34UAV-E
SM2804AT-E
3M26UAV-E
6 pins 8 pins CN ***
CN 800 CN 801

6 Pins (large)
6 Pins (large)
Cable Type: ‘B’

Communication Type: Serial


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

DI / SDI / MULTI SPLIT CONNECTION - 8 PIN


Operation Mode Setting: Parallel Outdoor Unit Model Code
SW1: Bit 3 = ON
DI (RAV-) SDI (RAV-) IES (RAS-)
Operation mode Com baud rate SM800AT-E SP560AT-E M18YAV
SW1 SW2 SM1100AT-E SP562AT-E M18YACV
ON SM1101AT-E SP800AT-E 3M23YACV
SM1102AT-E SP802AT-E 3M26YACV
OFF SM1103AT-E SP1100AT-E 4M27YAV
1 2 3 4 1 2 3 4 SM1400AT-E SP1102AT-E 4M27YACV
SM1401AT-E SP1400AT-E 4M30YACV
DYNA KIT ADAPTER SM1402AT-E SP1402AT-E 4M27GAV
SM1403AT-E 4M27GACV
SERIAL PARALLEL SM1603AT-E 3M18SAV
3M18SACV
CN 101 CN 102 3M20SACV
4M23SAV
6 pins 8 pins
CN 800 CN 801 4M23SACV
4M26SACV
CN ***
CN 801

8 Pins
8 Pins
Cable Type: ‘A’

Communication Type: Parallel


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

MINI-SMMS CONNECTION

Operation mode Com baud rate MCY-


SW1 SW2 MAP0401HT
ON MAP0501HT
MAP0601HT
OFF
1 2 3 4 1 2 3 4

DYNA KIT ADAPTER

SERIAL PARALLEL
CN 101 CN 102

6 pins 8 pins

CN800

6 Pins (small)
6 Pins (large)
Cable Type: ‘C’

Communication Type: Serial


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

SMMS / SHRM CONNECTION

Operation mode Com baud rate


SW1 SW2
ON

OFF
1 2 3 4 1 2 3 4

DYNA KIT ADAPTER

SERIAL PARALLEL
CN 101 CN 102

6 pins 8 pins

CN800

6 Pins (small)
6 Pins (large)
Cable Type: ‘C’

Communication Type: Serial


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

SMMSi CONNECTION 8,10 &12Hp

Operation mode Com baud rate


SW1 SW2
ON

OFF
1 2 3 4 1 2 3 4

DYNA KIT ADAPTER

SERIAL PARALLEL
CN 101 CN 102

6 pins 8 pins

CN800

6 Pins (small)
6 Pins (large)
Cable Type: ‘C’

Communication Type: Serial


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

SMMSi CONNECTION 14 &16Hp

Operation mode Com baud rate


SW1 SW2
ON

OFF
1 2 3 4 1 2 3 4

DYNA KIT ADAPTER

SERIAL PARALLEL
CN 101 CN 102

6 pins 8 pins

CN800

6 Pins (small)
6 Pins (large)
Cable Type: ‘C’

Communication Type: Serial


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

MMS CONNECTION CN801


System Data

Operation Mode Setting: Parallel HEAT PUMP


SW1: Bit 3 = ON
Operation mode Com baud rate MM-A0280HT
SW1 SW2 MM-A0280HX
ON MM-A0224HT
MM-A0224HX
OFF MM-A0160HX
1 2 3 4 1 2 3 4

DYNA KIT ADAPTER


COOLING
ONLY
SERIAL PARALLEL

CN 101 CN 102 MM-A0280CT


MM-A0280CX
6 pins 8 pins MM-A0224CT
MM-A0224CX
MM-A0160CX
CN800
Outdoor Data
8 Pins
8 Pins
Cable Type: ‘A’

Communication Type: Parallel


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

ESTIA : HYDRO UNIT CONNECTION


Operation Mode Setting: Parallel
SW1: Bit 3 = ON
Operation mode Com baud rate
SW1 SW2
ON

OFF
1 2 3 4 1 2 3 4 CN 21

DYNA KIT ADAPTER

SERIAL PARALLEL

CN 101 CN 102

6 pins 8 pins

CN 21

8 Pins
8 Pins
Cable Type: ‘A’

Communication Type: Parallel


Home Back Next
1
Set-up Configuration to connect Dyna Doctor

General Information: DK01SS-E

USB Connection
The USB driver is not supplied for Dyna Doctor,
the driver can be download free of charge from
the website link below:

URL:http://www.ftdichip.com/FTDrivers.htm

Device Name:FT232R

DYNA-KIT connection to a PC via RS-232C.


When you connect DYNA-KIT to a PC via RS-232C, you also need a
USB connection to provide a power supply of 5volts DC.

Home Back Next


1
Set-up Configuration to connect Dyna Doctor

DYNA DOCTOR COMMUNICATION CONNECTION ERROR

Above alert indicates that the USB COM port of the PC and
Dyna Doctor Software Program do not match.

For a resolution, follow process detailed on next slide.

Home Back Next


1
Set-up Configuration to connect Dyna Doctor

STEP 1
Access Device Manager on
your PC

STEP 2
Open ‘PORTS’ menu Check
assigned port Number (COM?)

STEP 3
Dyna Doctor Menu, select
‘setup’ from the ‘file’ drop down
menu & select the relevant
COM port.

Home Back Next


1
Set-up Configuration to connect Dyna Doctor

CONNECTION CABLE MODIFICATION

ORIGINAL CABLE MODIFIED CABLE

Modified Cables = location lugs (x2) have been removed to


enable the universal Outdoor PCB connection to the relevant
discontinued Toshiba products.

Home Back Next


1
Cable for applicable model

Home Back Next


Attached Cable and the table of applicable model 1

Home Back Next