FIM-16: Compressed Air Demand Side Automation

M&V Option – IPMVP Option A (One-time measurement for 24-hour) (3 days average basis)

Savings Summary: Based on the joint one-time measurement activity carried out by Siemens and Teva
team. Following are the savings summary details below.

Energy Savings Estimate kWh/Day


Pre-Retrofit daily energy consumption
[A] Baseline Energy Usage (kWh/Day) 2,893
(metered electric consumption)

Post-Retrofit kWh metered electric


[B] Estimated Energy Usage (kWh/Day) 2,319
consumption
[C] Savings (kWh/Day) [A]-[B] 574
# Please refer details of one-time measurement in Annexure A.

Result: As per the one-time measurement, daily average energy savings are reported as 574 kWh/Day.

Annexure A: Details of One Time Measurement Activity:

Run hr Run Hr Energy Meter Total


FIM-16 Compressed Air
Date Time Readings (ARCP- kWh Consumption
Demand Side Automation
(ARCP-9001) 9001) readings kWh
13/7/23 16:27 37781 3191109.4

PRE-MEASUREMENT 14/7/23 16:27 37805 24 3193912.8 2,803


*ARCP Set Pt- 6.5 bar
[A] 15/7/23 16:27 37829 24 3196809 2,896
*MAC unit and Air
Booster is bypass 16/7/23 16:27 37853 24 3199789.8 2,981
Average per Day 2,893
21/7/23 14:30 37971 3214248
POST-MEASUREMENT
*ARCP Set Pt- 6.5 bar, 22/7/23 14:30 37994 23 3216520.6 2,273
*MAC unit Control set
[B] 23/7/23 14:30 38018 24 3218832.6 2,312
pt. is 4.8 bar
*Air Booster is 24/7/23 14:30 38042 24 3221108.6 2,276
aligned
Average per Day 2,319

[C] Savings of pressure demand reduction by MAC unit and Air Booster (kWh/Day) 574

Siemens India Limited Teva API Limited

Ajay Singh & Lokesh Joshi Mr. Himanshu Tyagi