INTECONT® Tersus MULTISTREAM solids flow

feeder
Instruction Manual

BV-H2478 GB
PASS - Service you can rely on
Fast, comprehensive, anywhere in the world

Quality and reliability are the cornerstones of our company’s


philosophy. That is why we consider a comprehensive service
concept simply par for the course, from strict quality control,
installation and commissioning through to seamless support
across the entire product life cycle.
With over 30 service stations and over 180 service specialists,
you can count on us to be there whenever – and wherever –
you need us.

During office hours, service specialists from all divisions are


on hand to analyze problems and failures. Look at
www.schenckprocess.com for your nearest
Schenck Process Location.

Are you looking for individual, perfect-fit service solutions?


Then our service system PASS is the ticket. It covers the en-
tire service spectrum, from simple inspections through to full
service. Interested?
Then find out more about the individual components at
www.schenckprocess.com/en/service.

© by Schenck Process GmbH


Pallaswiesenstraße 100, 64293 Darmstadt, Germany
Phone: +49 6151 1531-0 ; www.schenckprocess.com
All rights reserved. Any reproduction of this documentation,
regardless of method, without prior permission by
Schenck Process GmbH in writing, even by excerpt, is prohi-
bited.
Subject to change without prior notice.

Note: Translation of the original German Instruction

(origin: ST4, 510500107 V1)


Table of Contents

Table of Contents
Contents

1 About This Manual ................................................................


................................................................................................
................................................................................................
................................................................1
................................1

2 Safety notes................................
notes................................................................
................................................................................................
................................................................................................
..........................................................................
..........................................3
..........3
2.1 Signal Words .........................................................................................................................................4
2.1.1 Signal Words for Safety Warnings ................................................................................................4
2.1.2 Signal Words for Application Notes ..............................................................................................5
2.2 Five Safety Rules of Electrical Engineering ..........................................................................................6
2.3 Damaged / Defective Electrical Components ........................................................................................6

3 General Diagram ................................................................


................................................................................................
................................................................................................
..................................................................
..................................7
..7
3.1 An overview of the INTECONT Tersus .................................................................................................7
3.2 MULTISTREAM block circuit diagram ...................................................................................................8
3.3 Functional mode ....................................................................................................................................9
3.3.1 Measuring principle .......................................................................................................................9
3.3.2 Automatic control ..........................................................................................................................9
3.3.3 Control operating modes ............................................................................................................ 10
3.3.4 Batching ..................................................................................................................................... 10
3.4 Characteristics .................................................................................................................................... 11

4 Operation................................................................
................................................................................................
................................................................................................
............................................................................
............................................15
4.1 Quick guide ......................................................................................................................................... 15
4.2 Function block..................................................................................................................................... 17
4.3 Operating in Normal Operation........................................................................................................... 18

5 Service Functions ................................................................


................................................................................................
...............................................................................................
...............................................................21
5.1 Display Test and Version Number ...................................................................................................... 21

6 Counter functions ................................................................


................................................................................................
................................................................................................
................................................................23

7 Mode functions ................................................................


................................................................................................
................................................................................................
...................................................................
...................................25
7.1 Types of operation .............................................................................................................................. 25
7.2 Keyboard operation ON/OFF.............................................................................................................. 26
7.3 Prefeeder ............................................................................................................................................ 26
7.4 Simulation ........................................................................................................................................... 26

8 Calibration functions ................................................................


................................................................................................
...........................................................................................
...........................................................27
8.1 Starting the calibration functions ........................................................................................................ 27
8.2 Tare TW .............................................................................................................................................. 28
8.3 Weight Check CW .............................................................................................................................. 29
8.4 Setting the Time ................................................................................................................................. 30

9 Parameter functions ................................................................


................................................................................................
............................................................................................
............................................................31
9.1 Read Parameters .............................................................................................................................. 31

10 Printer functions ................................................................


................................................................................................
................................................................................................
..................................................................
..................................33
10.1 Status Report ...................................................................................................................................... 33

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -i-
Table of Contents

11 Batching functions ................................................................


................................................................................................
..............................................................................................
..............................................................35
11.1 Batching mode .................................................................................................................................... 35
11.2 Record the batch ................................................................................................................................ 37

12 Startup operation ................................................................


................................................................................................
................................................................................................
................................................................39
12.1 Parameter Input .................................................................................................................................. 39
12.2 Function Check ................................................................................................................................... 39
12.3 Test With Calibration Weight .............................................................................................................. 40
12.4 Check with bulk solids ........................................................................................................................ 41

13 Parameters ................................................................
................................................................................................
................................................................................................
.........................................................................
.........................................43
13.1 Abbreviations ...................................................................................................................................... 44
13.2 Configuring Event Messages.............................................................................................................. 45
13.3 Parameter Listing .............................................................................................................................. 45
13.3.1 Parameter Overview .................................................................................................................. 45
13.3.2 Parameter Details ...................................................................................................................... 54
13.3.2.1 Parameter Block 01 - Dialog Behaviour ..................................................................................... 54
13.3.2.2 Parameter Block 02 - Rated Data .............................................................................................. 58
13.3.2.3 Parameter Block 03 - Calibration Data ...................................................................................... 60
13.3.2.4 Parameter Block 04 - Calibrat. Results ...................................................................................... 61
13.3.2.5 Parameter Block 05 - Analog Outputs ....................................................................................... 62
13.3.2.6 Parameter Block 06 - Limit Values ............................................................................................. 64
13.3.2.7 Parameter Block 07 - Filters....................................................................................................... 65
13.3.2.8 Parameter Block 08 - AUTO Zero Set ....................................................................................... 66
13.3.2.9 Parameter Block 09 - Batch Mode ............................................................................................. 68
13.3.2.10 Parameter Block 10 - Maintenance interval ............................................................................... 70
13.3.2.11 Parameter Block 11 - Events ..................................................................................................... 71
13.3.2.12 Parameter Block 12 - Rate controller ......................................................................................... 74
13.3.2.13 Parameter Block 13 - Linearization ............................................................................................ 81
13.3.2.14 Parameter Block 14 - Digital Inputs ........................................................................................... 83
13.3.2.15 Parameter Block 15 - Digital Outputs ......................................................................................... 85
13.3.2.16 Parameter Block 16 - Communication EasyServe ..................................................................... 87
13.3.2.17 Parameter Block 17 - Communication Fieldbus......................................................................... 88
13.3.2.18 Parameter Block 18 - Fixed mode configuration ........................................................................ 93
13.3.2.19 Parameter Block 19 - Ethernet ................................................................................................... 95
13.3.2.20 Parameter Block 20 - Data Logging ........................................................................................... 96
13.3.2.21 Parameter Block 21 - Configuration HMI Values ....................................................................... 98
13.3.2.22 Parameter Block 22 - Flow Gate ................................................................................................ 99
13.3.2.23 Parameter Block 23 - Additional device ................................................................................... 102

14 Event messages ................................................................


................................................................................................
...............................................................................................
............................................................... 103

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- ii - Schenck Process Group
Table of Contents

15 Events ................................................................
................................................................................................
................................................................................................
..............................................................................
.............................................. 105
15.1 Events Details ................................................................................................................................... 105
15.1.1 Event Group: Calibration .......................................................................................................... 105
15.1.2 Event Group: Controller ........................................................................................................... 106
15.1.3 Event Group: Electrical System ............................................................................................... 106
15.1.4 Event Group: Interlock ............................................................................................................. 107
15.1.5 Event Group: Material Flow...................................................................................................... 107
15.1.6 Event Group: MAX ................................................................................................................... 107
15.1.7 Event Group: MIN .................................................................................................................... 108
15.1.8 Event Group: Sequence Monitoring ......................................................................................... 109
15.1.9 Event Group: System Message ............................................................................................... 110

16 Hardware and technical data................................................................


................................................................................................
.............................................................................
............................................. 111
16.1 Technical Data and Replacement Parts ........................................................................................... 111
16.2 Connection Diagrams ....................................................................................................................... 114
16.3 Replacing INTECONT PLUS with INTECONT Tersus ..................................................................... 116
16.4 PROFIBUS Module (VPB8020) ........................................................................................................ 119
16.5 DeviceNet Module (VCB8020) ........................................................................................................ 121
16.6 Modbus Interface VSS8020.............................................................................................................. 123
16.7 LED diagnosis................................................................................................................................... 124

17 Web server functions ................................................................


................................................................................................
........................................................................................
........................................................ 125
17.1 Web Server ....................................................................................................................................... 125
17.2 System Information ........................................................................................................................... 126

18 Appendix ................................................................
................................................................................................
................................................................................................
..........................................................................
.......................................... 127
18.1 Service Values .................................................................................................................................. 127
18.2 Set option.......................................................................................................................................... 128
18.3 Test Connector ................................................................................................................................. 129
18.4 Sources of setpoints and switch signals ........................................................................................... 130
18.5 Measuring the flow rate .................................................................................................................... 132
18.6 Flow rate regulation .......................................................................................................................... 133
18.6.1 Constant controller ................................................................................................................... 134
18.6.2 Step controller .......................................................................................................................... 138
18.7 Linearization ..................................................................................................................................... 142

Index ................................................................
................................................................................................
................................................................................................
................................................................................
................................................ 143

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - iii -
About This Manual

1 About This Manual


The instruction manual for solids flow meters and solids flow feeders is intended for the service tech-
nician. It describes the functionality of the VIF 20650-xxx.. software.

This manual is available in different forms:


▪ A printed version
▪ An electronic document in the platform-independent ADOBE format (file ending: *.PDF)
▪ As online help in the Microsoft Windows HTMLHelp format (file ending: *.CHM)

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -1-
Safety notes

2 Safety notes
To avoid personal injury and material damage, follow the safety regulations stated below.
Additionally you should also observe:
▪ Safety information given in order-specific documentation
▪ Safety information relating to mechanical components
▪ Instructions and safety instructions for parts manufactured by thrid-party suppliers or parts that are not
part of Schenck's scope of delivery.
When performing installation, commissioning and service work, observe all applicable local regulations.

Intended Use
The measuring system and connected mechanical components is intended solely for weighing tasks and
related control applications. It is not intended for any other use.

Risks
If properly installed and put into service the measuring system itself does not represent a hazard.
Hazards may arise when the system is used for control operations or for transporting weighed goods. Po-
tential sources of danger would then be add-on equipment that the material weighed is transported or me-
tered in. Residual risks may originate from the measuring system if unskilled operators improperly handle
the system.
This measuring system may be a component of a more complex system. The operating company is fully
responsible for overall plant safety.

Personnel
Personnel
Preparation, assembly, commissioning, operation, maintenance and servicing may only be carried out by
qualified personnel.
All persons working on the system are required to observe the safety hints and know the parts of the tech-
nical documentation relevant to their work.
The operating company is responsible for instructing his operators to observe all regulations and instruc-
tions given.

Changing parameters
The parameters dictate how the measuring system functions. Only personnel familiar with the device's mode
of operation may alter these parameters (e.g. after training by Schenck Process). Parameters incorrectly set
may cause injuries or damage to the machine whenever a control system is connected. They can also ad-
versely affect weighing operation.

Password
Password
Passwords safeguard the parameters against unauthorized alteration. The measuring system operating
company has to ensure safe password handling.

Acknowledging Event Messages


Error messages may be acknowledged only after cause of fault has been remedied.
Ensure that any connected peripheral devices are functioning correctly before acknowledging an event. Any
connected control systems in particular must be in safe state.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -3-
Safety notes

Service and Maintenance


▪ Observe any warning symbols on the scales.
▪ The measuring system must be shut down before work is performed on mechanical equipment or peri-
pheral devices (control systems in particular). Take appropriate action to ensure that the measuring sys-
tem cannot be inadvertently restarted.
▪ Before performing work on the electrical equipment, disconnect the power supply (pull the plug!).
▪ The devices may be operated only in the provided housings. There is danger of contacting live parts.

Moisture and Humidity


Humidity
All of the parts of the scales, particularly electrical components, must be protected from moisture and humid-
ity when the housing is open such as during service work. Observe housing protection standards.

Design Modifications
Unauthorized modifications to the system and/or use of replacement parts not supplied by Schenck Process
voids Schenck Process's liability for any resulting damages. This especially applies to alterations which
could affect the operating safety of the system.

Replacing Components
Spare parts must meet the technical specifications indicated by Schenck Process. To ensure this require-
ment is met, only genuine Schenck Process spare parts should be used. When using other spare parts, the
warranty will be void.

2.1 Signal Words

2.1.1 Signal Words for Safety Warnings


Potential hazards will always exist when working with technical devices. Hazards will arise if the machine
▪ is incorrectly installed,
▪ is started up incorrectly,
▪ is operated by untrained personnel, or
▪ is repaired by unqualified personnel.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
-4- Schenck Process Group
Safety notes

In this manual the following signal words will indicate hazards that may arise when using this machine:

DANGER
This signal word indicates a danger that can immediately cause the
most severe injuries up to and including death.
Follow all instructions to prevent this from occurring.

WARNING
This signal word indicates a danger that can cause serious injuries up
to and including death.
Follow all instructions to prevent this from occurring.

CAUTION
This signal word indicates a danger that can cause slight or medium
injuries.
Follow all instructions to prevent this from occurring.

2.1.2 Signal Words for Application Notes

Signal words for information on material damages and on the optimal use of the machine

STRICTLY OBSERVE
Signal word used to identify situations in which material or environ-
mental damage could occur.
Follow all instructions to prevent this from occurring.

HINT
Signal word used to identify information on using the product eco-
nomically and at an optimal level of efficiency.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -5-
Safety notes

2.2 Five Safety Rules of Electrical Engineering


Engineering

These fives safety rules must be followed in the order shown before work is begun on electrical systems.
Once the work is finished, they are to be applied in reverse order.

DANGER
Electric shock from live components.
There is a danger of life from an electric shock.
– Take all possible precautions to ensure safety before work is begun on
live components. Observe, among other things, the following:
1. Disconnect the components.
2. Secure them against inadvertent restart.
3. Ensure that the components have been de-energized.
4. Above 1 KV: earth and bypass the cables.
5. Cover or shield adjacent, live components.

2.3 Damaged/
Damaged/Defective Electrical Components

DANGER
Live damaged or defective components
There is a danger of life from an electric shock.
– Always have qualified personnel ensure that the components are nei-
ther damaged nor defective.
1. Qualified personnel must immediately replace or, if possible, repair
damaged or defective electrical components.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
-6- Schenck Process Group
General Diagram

3 General Diagram

3.1 An overview of the INTECONT Tersus


INTECONT Tersus is an extension of and improvement on the INTECONT system that has proven its worth
for years and has been used in more than 50,000 scales all over the world.
INTECONT Tersus is a measuring and measurement processing system of continuous weighing and
feeding equipment for
▪ Weighfeeders
▪ Conveyor belt scales
▪ Loss-in-weight feeders
®
▪ MULTICOR mass flow feeders based on the Coriolis principle
®
▪ MULTISTREAM solids flow feeders based on the inertia principle

The basic hardware equipment is aligned to the needs of the application.


The following can be installed as optional equipment:
▪ fieldbus modules
▪ 230 VAC power supply
▪ module with additional analog outputs and analog inputs

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -7-
General Diagram

3.2 MULTISTREAM block circuit diagram

Fig. 1: Basic diagram of the ITE inputs and outputs

1 Z Impulse output for connecting an external totalizing counter


2 A Analog Output
3 LC Load cell for ascertaining belt load
4 S Measuring chute
5 M Control output for a prefeeder
6 F Dribble feed signal for batching
7 G Coarse feed signal for batching
8 24 V Power Supply
9 ALARM Relay output for alarms
10 MAX Relay output for maximum monitoring
11 MIN Relay output for minimum monitoring
12 ACK. Acknowledge event messages
13 EXT. INPUT External fault message input
14 ON
15 ON/OFF Switch scales and totalizing on/off
16 RELEASE Release signal for recording totalizing

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
-8- Schenck Process Group
General Diagram

3.3 Functional mode

3.3.1 Measuring principle


principle
A free flowing stream of bulk solids is diverted in its direction with a solids flow meter. The force required for
diverting is measured and is a measure of the flow rate.
The amount of force is calculated from the theorem of conservation of momentum in physics where the bulk
solids' angle of entry and exit as well as the entry and exit velocity are applied.
The type of diversion and the way the force is recorded depend on the equipment's design type. Here are
two examples:

Fig. 2: The MULTISTREAM measuring principle

Depending upon the type of construction, various installation conditions should be observed that can be
found in any manual of mechanics.
With feed units, the measured mass flow I in control electronics is additionally compared with a preset
setpoint P and the PF feeder is controlled so that I = P.

3.3.2 Automatic control


The weighing electronics equipment can control the material feed into the measuring equipment provided
that the regulation has been activated per parameter P01.05. The controller is turned off with pure
measuring systems.
Principle
The targeted and actual flow rate are compared and the difference is fed to a controller. This changes the
flow rate of the PF material feeder until the actual value is equal to the setpoint.
Material feeder
Speed-regulated PF feeders (such as feed screws and starfeeders) require an external power stage. An
external position controller or a switching mechanism for the OPEN and CLOSE directions is needed with
position-controlled feeders (such as flow gates). The equipment supplies the control signal either propor-
tional to the desired volumetric flow or the control commands for opening and closing a motor position-
controlled feeder.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group -9-
General Diagram

3.3.3 Control operating modes


The controller can be operated in various modes if the flow rate is regulated by the control. The controller is
turned off per parameter P01.05 Control with pure measuring systems.
The following modes of operation are available to the measuring device.
▪ Gravimetric Mode (regulated)
The actual flow rate is adjusted to the setpoint. The maximum possible setpoint is the same as Nominal
Flow Rate (P02.02). An event message is generated if the input value is too large.
▪ Volumetric Mode (unregulated)
The conveyor element setting is proportional to the flow rate setpoint. Measurement of the actual flow
rate has no effect on the conveyor element adjustment. The flow rate approximately equals the specified
setpoint under nominal conditions.
The setpoint is limited to three times the nominal flow rate. An event message will be generated if this
limit is exceeded.
▪ Volumetric Synchronous Mode (unregulated)
This mode of operation is a special form of volumetric operation. It ensures a seamless transition when
switching from gravimetric to volumetric operation.

3.3.4 Batching
In batch mode a preset quantity of material is discharged and the feeding is subsequently switched off.
Once the batch setpoint has been reached the batch operation is complete. A subsequent start command to
the feeder will begin a new charge.
Batch filling can be carried out in all modes and variants of operation.
The general procedure for batch operation is shown in the following figure:

Fig. 3: Feeding

The segments shown in the figure mean the following:


0: Start the batch with a preset batch setpoint in units of weight.
1: Interrupt batch operation by switching off the discharge element.
2: Resume the interrupted batch by switching on the feeder.
3: Automatic reduction of the flow rate towards the end of the batch.
4: End automatically once the predetermined batch quantity has been reached.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 10 - Schenck Process Group
General Diagram

3.4 Characteristics
Readouts
The display of INTECONT Tersus is divided into 4 parts:

1. You can enter the technical name at the installation site in the header. A rotating symbol on the left
edge shows whether the weighfeeder is on or off.
2. The second line of the display is reserved for event messages.
3. The following two lines show readings that can be selected with the cursor buttons. These lines cor-
respond to the lines of the INTECONT PLUS display.
4. The lower half of the display is used for various visualizations: the large-Scales display of an individual
reading, displaying 4 readings in line font size or displaying as many as 9 adjustable readings in the pa-
rameters block Configuration HMI Values. Their font size can be adapted over 3 levels.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 11 -
General Diagram

Event messages
▪ Events and malfunctions are shown by an alphanumerical shorthand symbol and a title.
▪ The corresponding 'plain text' for all consecutive events can be called up via the operating keyboard.
▪ A distinction is made between alarms (red), warnings that require acknowledgement (orange) and warn-
ings that do not require acknowledgement (yellow). Alarms will shut down the scales, warnings will not.
All alarms are also signaled via a relay output.

Fig. 4: Display - Warning 2

Fig. 5: Display - Warning 1

Fig. 6: Display - Alarm

Operating philosophy
▪ The operator is guided through menus on several levels. Important configuration and calibration
functions are secured via password.

Dialog language for fault messages, operation and service programs


▪ Either DEUTSCH, ENGLISH, FR-FRANCAIS, ES-ESPANOL, IT-ITALIANO, CN-CHINESE,
JP-JAPANESE, RU-RUSSIAN, HU-HUNGARIAN, NL-NETHERLAND as you choice or a language that
can be loaded in (OTHER / XX-NEW).

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 12 - Schenck Process Group
General Diagram

Dimensions
▪ SI units (Metric): kg, kg/h, t, t/h, m and cm
▪ NON SI units (English): lb, lb/h, t, t/h, f and inches

Turning recording the total or setpoint specification on or off


▪ This can be selected with the P02.03 Feeder Start and P02.04 Feedrate Setpoint parameters
(however, only with charging systems).

Mains power failure


▪ Scales data, adjustment data, counter readings and quantity signals not yet issued are retained
indefinitely after a mains power failure, the time is retained for approx. 5 days.

Zeroing
▪ It is set to zero without any material using a program that runs automatically.
▪ Zeroing should be started manually at regular intervals if automatic operation has not been preselected.
▪ The maximum permitted zeroing correction is monitored.

Zero drop out


▪ Suppressing totalizing with measurements around the zero point to ensure that the meter stays constant
at low feed rates. This function can be turned off.

Tare
▪ Taring is an adjustment process that ascertains basic tare. Call-up is password protected.

Batch mode
▪ Batch mode conveys a preset amount of material. The conveying process ends once the batch setpoint
has been reached.
▪ Changing over to dribble feed by reducing prefeeder performance.
▪ The switch-off point and using dribble feed can be automatically adapted.

Display filters
▪ For feed rate, belt load and belt speed.

Maintenance guidelines by showing an event in the display


▪ For the duty cycle of the voltage supply, the operating time of the scales and the next zeroing.

Adjustment
▪ It is not necessary to calibrate the pick-up input. Certain design data have to be keyed in. The system
uses this data to calculate all of the scaling required for the displays. It can be controlled or readjusted
using two different methods.
▪ Control with material: the result of a material inspection is entered into the system and it serves to
correct the measurement result.
▪ Control with a calibration weight: Norming is checked or can also be corrected if the technical data is not
precisely known.
The program is also suited to verifying mechanical changes in later operation.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 13 -
Operation

4 Operation

4.1 Quick guide


Elements of the graphic display:

Line 1: header rotating cross as a progress indicator. The scales are switched on; feed rate and flow
rate are being recorded. In belt-based systems, only the belt load and belt speed are
measured when the device is switched off (single point displayed).
Ɖ : with activated batching mode
local designation of the feeder. This can be changed with EasyServe using the
parameter P01.05.
Line 2: event line event information with a code and plain text
Upper display area two lines of actual values. These lines correspond to the two lines of INTECONT PLUS.

Lower display area Actual values that can be selected for display with buttons 0 - 9. The functions of buttons
4 - 7 depend on the application software and parameterization.

--- Totalizer 1Large value as per the parameter block


Configuration HMI Values

Batch Actual ValueLarge SetpointLarge ---


with bars with bars

FeedrateLarge FeedrateLarge FeedrateLarge


with bars with bars with bars

reduce brightness 4 readings with a bar display increase brightness

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 15 -
Operation

Operating elements:

SCROLL
▪ Pre-select which data will be displayed in the upper line
▪ Select a parameter group or a single parameter

▪ Pre-select the data display of the lower line


▪ Change to the right or left when numbers input

Numerical keys, signs and decimal points for entering parameters.


Number buttons in the home position for selecting display of the actual
… values

DELETE Acknowledge event messages, delete entries

START/STOP Switch on/off if pre-selected

DATA Prepare input, e.g. parameter changes and setpoint


entries

FUNCTION Call up the function distributor, then select the desired


function using the SCROLL keys

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 16 - Schenck Process Group
Operation

ESCAPE Cancel a function or input and return to the actual


value displays

ENTER Activate a function or confirm an entry

4.2 Function block


The function distributor is the point of entry for everything that will be performed on the device. All functions
and dialogs can be called up through it. The function distributor is two-staged.

Call up the function distributor


The most recently selected function will be displayed.

Select the desired function for the first level. This field has a yellow
background.

Change to the second level. The field selected for the first level has an
orange background.

Select the desired function of the second level. This field has a yellow
background.

Select function. Only those functions that can be called up at that moment
will be displayed.

Return to the normal display or abort a function.

Return to the first level.

You will return to the normal display if no key is pressed in the function distributor within 60 seconds.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 17 -
Operation

Functions of the 1st stage of the function distributor:

Setup
Totals
Mode
Calibration
Parameter
Printer Setting
Batch

Configuration and parameter functions are only accessible via password. The password is queried once the
function has been called up.
Access to some functions can be configured in the Dialog Behaviour block. Certain entries may be missing
depending upon this setting.

The appearance at the device:

Fig. 7: Display – function distributor

4.3 Operating in Normal Operation

Switching on the totalizing


Condition:
The external release signal must be pending (selectable), P02.03 Feeder
Start must be set to OP or keyboard mode must be activated.

Turn off of totalizing

The feeder drive can be switched on and off with the keys in this field if the mode of operation and the
parameterization permit it.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 18 - Schenck Process Group
Operation

WARNING
A start signal will actuate the motors!
There is the danger of injury if persons are in the area of the drives. Bulk
solids can be transported and cover the following equipment.
The switch-off command is not an emergency-off, but rather is normal op-
erational shutdown.

Reset the totalizing counter


This function must be activated with the P01.14 or P01.15 parameters.
Call up the function distributor

Totals
Reset Totalizer 1 or
Reset Totalizer 2

Select the function


Note:Totalizer 3 cannot be deleted.

Call up the zeroing program


Call up the function distributor

Calibration
>0< Zero Set

Acknowledge event information

Call up other functions such as displaying event information, adjustment, etc. and return from the func-
tion distributor

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 19 -
Operation

Enter batch setpoint


EnteringBatch Setpoint.

For beltweigher VWF and loss-in-weight feeder VLW:


A query of the Setpoint of the Feedrate will be first made if Feedrate Setpoint
is set to OP or keyboard mode is active.

Key in the numerical value

……
Acknowledge input

This deletes the last character

This interrupts input

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 20 - Schenck Process Group
Service Functions

5 Service Functions

Display Events Setup


Display Check
Service Values /
Standard Values
Start Data Logging /
Stop Data Logging
Clear Data Log File

Service functions help get an overview of the status of the unit and the weighing system.

• Display Events leads to a list of current upcoming events.


• Service Values activates the display of other internal status information in the lower line of the dis-
play Service Values. This line has a grey background. The return from this display takes place from
Standard Values .
• The other functions operate the routines set in the parameter block Data Logging.

5.1 Display Test and Version Number


This function displays the software version and tests the display.

Call up the function block

Setup
Display Check Overlay the software version number
Overlay the Schenck Process Logo
The test ends automatically

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 21 -
Counter functions

6 Counter functions

Reset Totalizer 1
Reset Totalizer 2 Totals
Totalizer Record

▪ Counter 1 and counter 2 can be reset with these functions.


▪ Counter 3 cannot be reset because it documents the total of materials conveyed.

The Totalizer Record function starts a printout of the counter. The printout is made to a file that can be read
using the web server. For beltweighers and legal-for-trade beltweighers a protocol can also be sent to a
connected printer.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 23 -
Mode functions

7 Mode functions
There are functions brought together in the Mode menu for switching over into various operating modes.

Functions: Mode

Volumetric Mode
Volumetric Synchronous
Start Keyboard Mode / Mode
Stop Keyboard Mode
Stop Prefeeder /
Particip. Prefeeder
Start Simulation /
Stop Simulation
Gravimetric

7.1 Types of operation


You can change between these modes of operation with the GravimetricVolumetric Mode and
Volumetric Synchronous functions.

Display:
V is shown in the header and VOL is shown in the service values in volumetric operation. Vis shown in the
header and VOLS. is shown in the service values in volumetric synchronous operation.
There is no separate status display in gravimetric operation, i.e. normal operation.

Characteristics:
All operation functions can be executed
All control inputs and outputs operate as set.

Gravimetric operation:
The actual value for the feed rate is regulated to the specified setpoint.
The maximum possible setpoint equals the nominal feed rate. Message SC01 'Event: Setpoint Limited ' will
be generated by larger inputs.

Volumetric operation:
The drive motor is regulated proportional to the setpoint. The instantaneous belt load has no influence with
belt-based scales.
The feed rate approximately equals the specified setpoint under nominal conditions. The setpoint is limited
to three times the nominal feed rate.
The calibration functions >0< Zero Set, TW: Tare, CW: Span Calibration and LB: Pulses/Belt can only be
called up in volumetric operation.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 25 -
Mode functions

Volumetric synchronous operation:


This mode of operation is a special form of volumetric operation. It ensures a seamless transition when
switching from gravimetric to volumetric operation.

7.2 Keyboard operation ON/OFF


The Start Keyboard Mode function can be used to switch the preselected operating sources for turning
on/off and specifying the setpoint and target batching values to the INTECONT keyboard .
Stop Keyboard Mode will again select the previous sources.
The on-off status and setpoints will be retained when switching to the keyboard from an external source
(e.g. serial). The external signals are effective when switching in the opposite direction.

Display:
One part of the actual value display in the upper display area is the line containing information on the status
and process of the program. Here OP signifies that OP Mode is active.

7.3 Prefeeder

The Particip. Prefeeder or Stop Prefeeder functions determine the impact of INTECONT on the prefeeder.
This function is activated in normal operation and INTECONT takes on controlling the prefeeder. The
material flow is interrupted when it is off and the scale can be tared, etc.

7.4 Simulation
In simulation mode, all functions of the scales can be tested without material during start-up. The scales
cannot be used for normal operation during simulation.

Display:
▪ Event message SY14 Event: Simulation active
▪ One part of the actual value display in the upper display area is the line containing information on the
status and process of the program: Here 'SIM' signifies that Simulation Mode is active.
▪ This function can be turned off again with Stop Simulation in the same fashion.

Characteristics:
1. All operation functions can be executed
2. The actual feed rate is set at the setpoint feed rate for feeder systems. This value will be set as per
P02.02 Nominal Flow Rate for measuring systems.
3. Belt load and speed measuring are active for belt-based systems.
4. All inputs and outputs operate as set.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 26 - Schenck Process Group
Calibration functions

8 Calibration functions
Functions: Calibration

>0< Zero Set


TW: Tare
CW: Span Calibration
Set Time Calibration

8.1 Starting the calibration functions


▪ The adjustment programs that provide basic and subsequent calibration are available in this menu along
with the >0< Zero Set and Set Time functions.
▪ The procedure is the same for all programs.
▪ All of them are protected from unintentional operation with a password. No total will be recorded during
the run time of a program until acknowledgement; analog outputs are set to the offset amount.

Call up the function distributor

Calibration

Select the desired adjustment program

Key in password 7353

Afterwards you will be shown the dialog of the selected adjustment program.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 27 -
Calibration functions

8.2 Tare TW
The taring program records the zero point fault of the measuring system over an adjustable period of time.
This value is used to correct the ongoing measuring results in normal operation. We should distinguish
taring from zeroing.

Taring: Recording basic tare with service and maintenance

Zeroing: Recording the operational zero deviation e,g, from soiling


The maximum correction stroke of the zeroing program is limited while that of the tare program is not.
After taring, the zeroing program bases the permissible correction deviation on the new reference
value.

Conditions:
1. Material may not be flowing. The prefeeder can be controlled with the 'Feeder ON/OFF' function.
2. The mechanical equipment within the scales area must be cleaned. You may leave deposits that will
develop again immediately in regular operation
3. Switch off batch mode

Sequence:

Call up the function block

Calibration
TW: Tare

Abort possible at any time

The display shows the remaining duration of running in % of the total duration of running and the conti-
nuously meaned tare in % of the nominal load when the program is running.
TW: Calibration active is shown in the header.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 28 - Schenck Process Group
Calibration functions

The display shows the difference between the tare and previous taring in % of the nominal load and the
mean of the total tare in % of the nominal belt load after ending the program.
Dev = + : tare has increased
Dev = - : tare has decreased

The TW: wait for Confirmation message in the header reports the end of the program and requests user
input.

The results are accepted and filed in P04.03 Basic Tare parameters. At the same
time, P04.04 Tare Correction is set to zero.

The result is not accepted and the scales are not tared.

8.3 Weight Check CW


You can use this program to control the turndown of the system. For this purpose, the measuring system is
loaded with a known calibration weight and the mean of the load cell load is automatically calculated over a
certain period of time. The result is compared to a preset setpoint and then displayed.
No automatic correction is performed.
Suitable calibration weights are available as accessories.

Preconditions:
1. Tare or zero
2. Key in the calibration weight in P03.04 parameters
3. Attach the calibration weight at the place provided
4. Switch off batch mode

Sequence:

Function Distributor

Calibration
CW: Span Calibration

Abort possible at any time

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 29 -
Calibration functions

While the program is running the remaining running period is shown in the display as a % of the total ad-
justment period along with the continual measuring result Set/Act.
'CW: Calibration active' will be displayed in the header.
The display shows the quantity of material fictitiously fed in and the mean of the Set/Act after ending the
program.
The CW: wait for Confirmation message in the header reports the end of the program and requests user
input.

Exiting the program. Either button may be used AS THE RESULT IS NOT
ACCEPTED AUTOMATICALLY.

8.4 Setting the Time


The date and time are among the Service Values status information for the scale and
they can be changed at any time.

Call up the function block

Calibration
Set Time

Abort possible at any time

Enter the year, month, day, hour, minute and second.


Confirm each entry.
After the seconds have been entered and confirmed, the new time will be
accepted.

Then it shows the new setting for a couple of seconds as Current Time.
The internal clock will run for a further approx. 5 days in case of a mains failure.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 30 - Schenck Process Group
Parameter functions

9 Parameter functions
Functions: Parameter

Read Parameters
Enter Parameters
Print Parameters
Load Factory Defaults
Load Custom Defaults Parameter
Option activate

Display, alter and print the parameter on the device.


Load Custom Defaults will set the device to a defined state that was saved at, for example, setup. The Load
Factory Defaults function will reset completely the parameterization. (Parameters [➙ 43])

Additional functions can be activated by the Option activate function (Set option [➙ 128]).

9.1 Read Parameters


Parameter are changeable characteristics or data with which the device can be adapted to its special weigh-
ing task.
You can find the meaning of the parameters in the detailed parameter description.
The input of parameters is protected by a password. They can inspected without any hazard with the Read
Parameters function. The parameters are broken down into functional blocks and numbered within a block.
Parameters are composed as follows:

Pxx.yy <Text>, where: xx: block number


yy: Number of the parameters in the block
<Text> Explanatory name of the parameters (language-dependent)

Depending on the situation, individual parameters or groups of parameters may be faded


out to highlight the parameters important to an application. Hidden parameters can only be
shown with the EasyServe service software and they can also be cleared there for the dis-
play on the unit wherever necessary. Fading out may result in breaks in the numbering.
Some parameters can be write protected. The write protection can also be configured using
EasyServe.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 31 -
Parameter functions

Reading parameters:

Call up the function block

Parameter
Read Parameters

Scrolling through parameter blocks 1, 2, …


and select the required block.

Scrolling through the parameters within a block

Return to the blocks

Return to normal display

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 32 - Schenck Process Group
Printer functions

10 Printer functions
Functions: Printer Setting

Totalizer Record
Print Parameters
Print Status Report
Batch Record

Printer Set-
ting

When printing with the Batch Record function, the Totalizer Record function adds the batch setpoint and
actual batch value to the print-out and Totalizer Printout is printed out as the heading.
The batch protocol can only be printed after completing the batch. The counter protocol is available at any
time.

The complete parameter list is printed out with the current readings using the Print Parameters function. All
inputs departing from the default readings are marked with an *. The list of all possible event messages and
the current hardware allocation is printed out as an appendix.
The printing procedure can be cancelled at any time.

10.1 Status Report


The Print Status Report can be printed out at any time. It provides information on the events and configura-
tion results that have occurred to date, etc. The Service Values chapter explains the specific data in detail.
The printing procedure can be cancelled at any time.

Software version
Own Address EasyServe address information
IP Address Ethernet address information
OP Mode Status information
Simulation Mode
Feeder On
Volumetric Mode
Summary Alarm
Maintenance Electric Overall duty cycle of mains voltage.
Maintenance Feeder Run Overall duty cycle of the belt conveyor and the device.
Totalizer 1 The readings of the total counter
Totalizer 2
Totalizer 3
The events since Power ON The number and type of events from Power ON or since the last print-out of Print
Status Report.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 33 -
Printer functions

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 34 - Schenck Process Group
Batching functions

11 Batching functions
Functions: Batch

Select Batch / Deselect Batch


Batch Record
Abort Batch
Batch Number
Reload

Batch

11.1 Batching mode


A preselected quantity of material is dispatched in batching mode. When the batch setpoint is reached, the
system is switched off and the feeding process is ended.

Display:
If Batch Mode is selected, the summation symbol Ɖ appears in the header.
Relevant data in the middle and lower display zone: Batch Setpoint, Batch Actual Value and Batch Residual
Amount.
Before starting a batch, Batch Actual Value and Batch Residual Amount show the amounts reached by the
previous batch. Deselecting Batch Mode means that the displays are no longer accessible, although they
appear again with the new preselection.
The format of the display is determined by P02.05 Counter 1 Unit and also by P02.12 Z1-Numberstep,
depending on the application.

Preselecting batching mode


Preselecting the batching mode makes batching possible, although it does not initiate a batch.
The condition: scales OFF and the function is activated.

Call up the function distributor

Batch
Select Batch

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 35 -
Batching functions

Input theBatch Setpoint

A Batch Setpoint query occurs automatically upon preselection or can be manually initiated with after
a batch has been finished (scales OFF).
No entry can be made if batch mode is deselected or if a batch is in process.
No input is possible if the Batch Setpoint is specified with the fieldbus (Batch Setpoint Source P09.06 = FB).

For beltweigher VWF and loss-in-weight A query of the Setpoint of the Feedrate will be first made if Feedrate
feeder VLW only: Setpoint is set to OP or keyboard mode is active.

Skip the input.


The old Setpoint of the Feedrate is maintained. Then Batch
Setpoint Source will be queried automatically.

Input the value


Acknowledge input

Interrupt entry, continue with previous setpoint

Delete incorrectly entered characters

Starting and interrupting

Start the batch and the conveying process begins

Interrupting a batch
The batch is continued with the next start command

Deselect Batch
This function deselects batching mode, i.e. it is taken out of the active
scope of functions. The summation symbol disappears from the header and the batching values can no
longer be called up again. However, they will not be cleared.
Conditions: the batch is ended or cancelled via Abort Batch function, scales OFF.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 36 - Schenck Process Group
Batching functions

Call up the function distributor

Batch
Deselect Batch

Batching mode can be re-activated with the Select Batch function and you can inspect the old batching val-
ues again.
Abort Batch
This function cancels a current batch and the conveying process is ended immediately.
Operation remains in batch mode.
The next start command will begin a new batch; the previous batch will not be resumed.

Call up the function distributor

Batch
Abort Batch

11.2 Record the batch


The result of the batching is sent to a file that can be read using the web server.
For beltweighers and legal-for-trade beltweighers a protocol can also be sent to a connected printer.

▪ The batch has to be ended or cancelled. This function is only available in batching mode.
▪ It can be printed out with the Batch Record function or automatically after every finished batch
(P09.07 Batch Automatic Record = YES).
▪ The printing procedure can be cancelled at any time.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 37 -
Startup operation

12 Startup operation

12.1 Parameter Input


A technical data sheet is part of the scope of delivery. It contains all important nominal and calibration data
acc. specification. We will therefore list only a few important pieces of information and some recommenda-
tions at this point. It makes sense to go through all of the parameters and consider the value entered.

Parameter block Dialog Behaviour:


Dialog language, display units and availability or security of the function block functions. The parameter
values will be converted automatically if the dimensions are changed.

Parameter block Rated Data:


The Device Constant P03.02 parameter is important for adjustment.
The dimension data should be adapted to the Nominal Flow Rate. Flow Rate Units P02.01 resolution should
not be greater than 4 ... 5 decimals for a quiet display.
The output frequency should not be any more than 10 Hz if an external volumeter is connected.

Parameter block Calibration Data:


All calibration and evaluation data are important and must be entered exactly. Most of the details can be
found in the technical data sheets.

Parameter block Calibrat. Results:


No input is needed. Weight Correction P04.01 should be at 1 at initial adjustment. We recommend that
once you have entered the rated data you check whether the load cell becomes overloaded by the rated
feed rate.

12.2 Function Check


1. Turn on the equipment. The switch-on process depends on the preselected Feeder Start P02.03 source.
2. A rotating cross appears in the header as a progress indicator. If not, there is no clearance or the ON
button was not pressed.
3. Take any event messages which appear into account and remove the error.
4. Check the following:
Load cell: The initial non-normed value of the load cell amplifier may not be any more than 2.85 mV/V
even when the weighing platform is at rated load. It must change if the weighing platform is placed under
load (e.g. the calibration weight). If the value is too large, the load cell is overloaded. If the value is nega-
tive, the load cell may be wrongly connected.
The load cell load in percent, sourced from the sum of the load cell nominal capacities, should not be
larger than 100 % with nominal belt load.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 39 -
Startup operation

12.3 Test With Calibration Weight


The test with a calibration weight makes sense because
1. mechanical or electrical faults are possible
2. calibration data can be unreliable (for instance, the leverage is not precisely known) and it is difficult to
measure the belt inclination
3. data may be incorrectly entered

The calibration weight should be between 30 % ... 100 % of the platform nominal load and be accurate.
1. Enter Calibration Weight P03.04.
On beltweighers with parallel leaf-spring guides, the effective calibration weight is the same as the ac-
tual value. In other cases, the effective calibration weight can be taken from the data sheet, or can be
calculated according to the chapter details/data flow images. The inclination of the conveyor belt has no
effect on the effective calibration weight.
2. Call up the CW: Span Calibration program.

Some Possible Causes of Fault:


Warping of the weighing platform, improper alignment, interferences in the load cell cable.
If you suspect any of these faults, repeat the check with a different weight.
Non-linearity is an indication of such faults, linear faults are more likely to be cause by incorrect data.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 40 - Schenck Process Group
Startup operation

12.4 Check with bulk solids


Each test or calibration with calibration weights can only approximate the actual operating conditions. A
highly accurate continuous measurement can only be achieved by making several measurements with bulk
material and a subsequent correction. Material Correction P04.05 is used for correction. The following fig-
ure shows an example of the arrangement for checking belt-based continuous throughput metering.

Fig. 8: Arrangement for verification with bulk material

The following items must be observed:


1. The route from the continuous measuring point to the collecting point for the material has to be clean.
2. If there are any diverters they may not convey any material.
3. If there are any feed screws or air slides between the continuous measuring point and the collecting
point, material should be conveyed for approximately ½ hour before making a check. This will allow the
usual material build-ups to form on the conveying elements.
4. Dedusting should be set to a minimum.
5. The bins or vehicles in which the material is transported onto a (legal-for-trade) commercial scale must
be cleaned and re-weighed (tared) before each filling. The commercial scales must be sufficiently accu-
rate to measure the MW quantity.

The new value Material Correctionnew is calculated from the prior value Material Correctionold out of the MA
meter progress of continuous measurement and the mass MW calculated on the check-scale as follows:
Material Correctionnew = Material Correctionold * MW / MA

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 41 -
Parameters

13 Parameters
The INTECONT Tersus is adapted to each application by means of parameters. No special programing
knowledge is therefore necessary.

Fig. 9: Parameter sets

Parameter set Purpose Activation Preparation and Alteration


Active parameters set A summary of the effec- Always active via EasyServe or on the unit
tive parameters
Factory settings Complete parameters set Use EasyServe or the unit Cannot be changed
Non-alterable basic set- to copy into the active pa-
ting rameter set

Backup set Pre-setting for a group of Use EasyServe or the unit Only using EasyServe in
applications or a setting to copy into the active pa- expert mode
stored during commis- rameter set
sioning
Tab. 1 : Using parameter sets

Note: Parameters not required for an application can be faded out or declared 'read only' using EasyServe
in expert mode. EasyServe compiles a list of visible parameters that form an integral part of the system do-
cumentation. Together with the operating manual they make up the relevant control system documentation
for an application. The parameter list contained in the operating manual contains all of the parameters
regardless of their actual use in an application.
In addition to the parameter set stored in the scales, we recommend that after commissioning you keep a
copy of the parameter set in a mass storage medium using EasyServe.
The parameters are arranged into blocks to for clarity. A parameter is uniquely identified by its block and
number within that block in the respective scales software version, e.g. 'P01.03' means 'parameter block 1,
parameter no.3'.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 43 -
Parameters

Notes:
▪ Gaps can appear between block numbers and parameters within the blocks. In rare cases, the number
of a parameter may change.
▪ Furthermore, each parameter has a unique ID with which it can be addressed via an interface (serial,
fieldbus). This ID can be seen as a 'Tooltip' in EasyServe when passing over the parameter and can be
output in the parameter printout.

13.1 Abbreviations
Source Description

FB Fieldbus
OP Operating panel
DI Digital Input
DO Digital Output
AI Analog Inputs
AO Analog Outputs
LS Logical signal for using internally available signals
Event Event. The reaction to the occurrence of an event can be configured.
W1 Warning 1 (requires acknowledgement)
W2 Warning 2 (does not require acknowledgement)
ALARM Alarm (requires acknowledgement)
IGNORE Ignore: do not show any event message, but switch the corresponding contact outputs
LC Load Cell
I Flow rate
v Belt velocity
VCU VCU 20100 system unit of DISOCONT Tersus. Refer to the BV-H2406 manual for details.
VHM DISOCONT Tersus operating panel. Refer to the BV-H2406 manual for details.
VMO The machine operating console for service work. Refer to the BV-H2488 manual for details.
Tab. 2 : Abbreviations frequently used in parameters

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 44 - Schenck Process Group
Parameters

13.2 Configuring Event Messages


The system monitors a range of both of its own operation and the peripherals. The reaction to a recognized
deviation, that is to say an event, is set by parameter. The parameters are used to assign to each event a
class that will determine this reaction.

Event class Description Impact on Acknowledgement Color on


Feeding required the VHM

Alarm ALARM Stopping feed operation, Yes Red


The scale will be turned off,
Cannot be switched on
Warning 1 W1 Feeder will continue to run Yes Orange
Warning 2 W2 Feeder will continue to run No Yellow
Only display as long as
the event is active
Ignore IG Feeder will continue to run - -
Tab. 3 : Event classes

NOTE: An external binary output channel is set that may have been assigned to the event regard-
less of the event class.
A recently pending alarm- or warning 1-class event will be shown on the operating panel blinking and in
color. The blinking stops when acknowledged. Acknowledged event messages are cleared from the display
for currently pending events when the event is no longer pending. Each event is stored with a time-stamp in
the internal memory for later analysis.

13.3 Parameter Listing

13.3.1 Parameter Overview


VIF20650-001 2842

01 - Dialog Behaviour
Number: Name Default Customer Sys ID
P01.01 [➙ 54] Language * DEUTSCH 4224

P01.02 [➙ 54] Userdefined Text * XX-NEW 5816

P01.03 [➙ 54] Font * UMing 30 6244

P01.04 [➙ 54] Units * Metric 4225

P01.05 [➙ 54] Control * NO 4590

P01.06 [➙ 54] Scale Name * INTECONT Tersus VIF 6238

P01.07 [➙ 54] Password * 10000 4292

P01.08 [➙ 54] 2. Password * 14389 4321

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 45 -
Parameters

P01.09 [➙ 54] Switch Grav./Vol. command * active 4595

P01.10 [➙ 54] Feeder ON/OFF * active 4280

P01.11 [➙ 54] Switch Keyboard-/Normal Mode * active 4282

P01.12 [➙ 54] Batch control * active 4283

P01.13 [➙ 54] >0: Zero ON/OFF * active 4284

P01.14 [➙ 54] Reset Counter 1 * active 4286

P01.15 [➙ 54] Reset Counter 2 * active 4287

P01.16 [➙ 54] Data Log ON/OFF * not active 4309

02 - Rated Data
Number: Name Default Customer Sys ID
P02.01 [➙ 58] Flow Rate Units ------ t/h 4229

P02.02 [➙ 58] Nominal Flow Rate 400 t/h 4226

P02.03 [➙ 58] Feeder Start OP 4241

P02.04 [➙ 58] Feedrate Setpoint OP 4242

P02.05 [➙ 58] Counter 1 Unit ------- t 4230

P02.06 [➙ 58] Pulse Length Total 0 ms 4231

P02.07 [➙ 58] Counter 2 Unit ------- t 4232

P02.08 [➙ 58] Counter 3 Unit ------- t 4233

P02.09 [➙ 58] Relative Setpoint NO 4247

P02.10 [➙ 58] DO: Pulse Counter n/a 4239

P02.11 [➙ 58] Totalizer Increment 10 kg 4254

P02.12 [➙ 58] Z1-Numberstep Automatic 4255

03 - Calibration Data
Number: Name Default Customer Sys ID
P03.01 [➙ 60] LC Characteristic Value * 2.85 mV/V 4257

P03.02 [➙ 60] Device Constant * 0.04 kgh/t 4265

P03.03 [➙ 60] LC Rated Capacity * 220 kg 4258

P03.04 [➙ 60] Calibration Weight * 50 kg 4354

P03.05 [➙ 60] Calibration Time * 30 s 4358

04 - Calibrat. Results
Number: Name Default Customer Sys ID
P04.01 [➙ 61] Weight Correction 1 4359

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 46 - Schenck Process Group
Parameters

P04.02 [➙ 61] Total Tare 0 kg 6147

P04.03 [➙ 61] Basic Tare 0 kg 4355

P04.04 [➙ 61] Tare Correction 0 kg 4356

P04.05 [➙ 61] Material Correction 1 4360

05 - Analog Outputs
Number: Name Default Customer Sys ID
P05.01 [➙ 62] AO: Setpoint n/a 4385

P05.02 [➙ 62] Setpoint Offset 4 mA 4386

P05.03 [➙ 62] Setpoint Range 20 mA 4387

P05.04 [➙ 62] AO: Actual Flow Rate n/a 4388

P05.05 [➙ 62] Flow Rate Offset 4 mA 4389

P05.06 [➙ 62] Flow Rate Range 20 mA 4390

P05.07 [➙ 62] AO: Actual Flow Rate (2nd) n/a 4306

P05.08 [➙ 62] AO: Load n/a 4401

P05.09 [➙ 62] Load Offset 4 mA 4402

P05.10 [➙ 62] Load Range 20 mA 4403

P05.11 [➙ 62] AO: Motor Speed Control n/a 4400

06 - Limit Values
Number: Name Default Customer Sys ID
P06.01 [➙ 64] Limit: Actual Flow Rate MIN 5 % Io 4337

P06.02 [➙ 64] Event: Actual Flow Rate MIN W2 4338

P06.03 [➙ 64] Limit: Actual Flow Rate MAX 120 % Io 4339

P06.04 [➙ 64] Event: Actual Flow Rate MAX W2 4340

P06.05 [➙ 64] Stand-By Limit Value 0 % Io 4290

P06.06 [➙ 64] Event: Stand-By W2 4289

07 - Filters
Number: Name Default Customer Sys ID
P07.01 [➙ 65] Filter: Actual Flow Rate 3s 4328

P07.02 [➙ 65] Filter: Actual Flow Rate analog 3s 4329

P07.03 [➙ 65] Filter: Load 3s 4335

P07.04 [➙ 65] LC Filter 1s 4334

P07.05 [➙ 65] Afterflow Totalizer 3s 4274

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 47 -
Parameters

08 - AUTO Zero Set


Number: Name Default Customer Sys ID
P08.01 [➙ 66] Auto Zero Active NO 4675

P08.02 [➙ 66] Mean Limit Value 1%Q 4676

P08.03 [➙ 66] Zeroing Limit 5%Q 4677

P08.04 [➙ 66] Event: Tare Correction W1 4678

P08.05 [➙ 66] Zero Set Difference 5%Q 6154

P08.06 [➙ 66] Event: Tare Difference > MAX W2 6155

P08.07 [➙ 66] Zero Drop-Out Active NO 4679

P08.08 [➙ 66] Zero Drop-Out Limit 1%Q 4680

09 - Batch Mode
Number: Name Default Customer Sys ID
P09.01 [➙ 68] Correction Amount 0 kg 4451

P09.02 [➙ 68] Adaptation Factor 1 4452

P09.03 [➙ 68] Adaptation Time 3s 4450

P09.04 [➙ 68] Batch Tolerance 100000 kg 4458

P09.05 [➙ 68] Event: Out of Tolerance W1 4459

P09.06 [➙ 68] Batch Setpoint Source OP 4449

P09.07 [➙ 68] Batch Automatic Record NO 4453

P09.08 [➙ 68] Reset print FMZ 1 NO 6165

P09.09 [➙ 68] Reset print FMZ 2 NO 6166

10 - Maintenance interval
Number: Name Default Customer Sys ID
P10.01 [➙ 70] Maintenance Electric 3000 h 4465

P10.02 [➙ 70] Event: Maint. Electric W1 4466

P10.03 [➙ 70] Maintenance Feeder Run 3000 h 4467

P10.04 [➙ 70] Event: Maint.Feeder Run W1 4468

11 - Events
Number: Name Default Customer Sys ID
P11.01 [➙ 71] Event: Power Failure A 4297

P11.02 [➙ 71] Event: Memory A 4302

P11.03 [➙ 71] Event: Error LC Input A 4293

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 48 - Schenck Process Group
Parameters

P11.04 [➙ 71] Event: Run Disabled W1 4246

P11.05 [➙ 71] Event: LC Input > MAX A 4295

P11.06 [➙ 71] Event: LC Input < MIN A 4294

P11.07 [➙ 71] Event: Simulation active W2 6202

P11.08 [➙ 71] Event: Setpoint Limited W1 4296

P11.09 [➙ 71] Event: External Event 1 A 4417

P11.10 [➙ 71] Event: External Event 2 A 4430

P11.11 [➙ 71] Event: License Violation A 4303

12 - Rate controller
Number: Name Default Customer Sys ID
P12.01 [➙ 74] Controller Type Continuous 4701

P12.02 [➙ 74] P-Component KP 0.02 mA/% 4369

P12.03 [➙ 74] I-Component TN 3s 4370

P12.04 [➙ 74] Time Deviation 20 s 4298

P12.05 [➙ 74] Threshold Deviation 5% 4299

P12.06 [➙ 74] Factor Deviation 1 4320

P12.07 [➙ 74] Event: Deviation W1 4300

P12.08 [➙ 74] Deviation abs. max. 100 % 6255

P12.09 [➙ 74] Event: Controller Limited W1 4301

P12.10 [➙ 74] Lower Limit 0 mA 4371

P12.11 [➙ 74] Upper Limit 20 mA 4372

P12.12 [➙ 74] Controller Magnitude Offset 0 mA 4373

P12.13 [➙ 74] Position at STOP 0 4374

P12.14 [➙ 74] Volumetric Start-Up 0s 4272

P12.15 [➙ 74] Setpoint Offset 0 mA 4244

P12.16 [➙ 74] Filter: Deviation 3s 4333

P12.17 [➙ 74] Setpoint Range 20 mA 4243

P12.18 [➙ 74] Store NO 4376

P12.19 [➙ 74] Bypass 10 mA 4375

P12.20 [➙ 74] Setpoint Filter 1st Ord 0s 4378

P12.21 [➙ 74] Setpoint Filter 2nd Ord 2s 4379

P12.22 [➙ 74] KP Adaptation 1 4644

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 49 -
Parameters

P12.23 [➙ 74] Setpoint Threshold 0 % Io 4805

P12.24 [➙ 74] S: P-Component 0.033 s/% 4687

P12.25 [➙ 74] S: I-Component 3s 4688

P12.26 [➙ 74] S: Threshold Response 0.1 % 4689

P12.27 [➙ 74] Compensation Element 0 1/s 4690

13 - Linearization
Number: Name Default Customer Sys ID
P13.01 [➙ 81] Linearization ON NO 4577

P13.02 [➙ 81] Linearization S1 25 % Q 4681

P13.03 [➙ 81] Linearization I1 25 % Q 4579

P13.04 [➙ 81] Linearization S2 50 % Q 4682

P13.05 [➙ 81] Linearization I2 50 % Q 4581

P13.06 [➙ 81] Linearization S3 75 % Q 4683

P13.07 [➙ 81] Linearization I3 75 % Q 4583

P13.08 [➙ 81] Linearization S4 100 % Q 4684

P13.09 [➙ 81] Linearization I4 100 % Q 4585

P13.10 [➙ 81] Event: Linearization Error W2 4586

14 - Digital Inputs
Number: Name Default Customer Sys ID
P14.01 [➙ 83] Source Run Enable * DI 4245

P14.02 [➙ 83] DI: Batch Terminate * n/a 4454

P14.03 [➙ 83] DI: Acknowledge Events * DI 4419

P14.04 [➙ 83] DI: Start * n/a 6207

P14.05 [➙ 83] DI: External Event 1 * n/a 4418

P14.06 [➙ 83] DI: External Event 2 * n/a 4431

P14.07 [➙ 83] DI: Reset Totalizer 1 * n/a 5414

P14.08 [➙ 83] DI: Reset Totalizer 2 * n/a 5415

P14.09 [➙ 83] DI: Volumetric Mode * n/a 4421

P14.10 [➙ 83] DI: Volumetric synchron * n/a 4941

15 - Digital Outputs
Number: Name Default Customer Sys ID
P15.01 [➙ 85] DO: ALARM DO 4436

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 50 - Schenck Process Group
Parameters

P15.02 [➙ 85] DO: Start Prefeeder DO 4435

P15.03 [➙ 85] DO: Scale Start DO 4433

P15.04 [➙ 85] DO: Actual Flow Rate MIN DO 4438

P15.05 [➙ 85] DO: Actual Flow Rate MAX DO 4439

P15.06 [➙ 85] DO: Batch Running n/a 4455

P15.07 [➙ 85] DO: Full Feed n/a 4457

P15.08 [➙ 85] DO: Dribble Feed n/a 4456

P15.09 [➙ 85] DO: Keyboard Mode n/a 4462

P15.10 [➙ 85] DO: Volumetric Mode n/a 4444

P15.11 [➙ 85] DO: Deviation DO 4437

16 - Communication EasyServe
Number: Name Default Customer Sys ID
P16.01 [➙ 87] Own Address 1 4520

P16.02 [➙ 87] Baud Rate 38400 4521

P16.03 [➙ 87] Format Data 8-N-1 6189

17 - Communication Fieldbus
Number: Name Default Customer Sys ID
P17.01 [➙ 88] Protocol Type NO 4528

P17.02 [➙ 88] Timeout Host 5s 4529

P17.03 [➙ 88] Event: Cyclic Communication A 4530

P17.04 [➙ 88] Event: Acyclic Communication W2 5680

P17.05 [➙ 88] Check in Keyboard Mode YES 6234

P17.06 [➙ 88] Compatibility DISOCONT Master NO 6287

P17.07 [➙ 88] Word Sequence I:std/L:std 6246

P17.08 [➙ 88] Byte Sequence High - Low 6245

P17.09 [➙ 88] Configuration FIXED_8_8 4661

P17.10 [➙ 88] Address 1 4531

P17.11 [➙ 88] Resolution 4096 4533

P17.12 [➙ 88] Baud rate 9600 4535

P17.13 [➙ 88] Data Format 8-O-1 4656

P17.14 [➙ 88] Physics RS232 6186

P17.15 [➙ 88] Address 16 4539

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 51 -
Parameters

P17.16 [➙ 88] FLOAT-Format IEEE 4540

P17.17 [➙ 88] Compatiblity INTECONT NO 4788

P17.18 [➙ 88] Identifier format BYTE 6190

P17.19 [➙ 88] PA32 compatible NO 4660

P17.20 [➙ 88] Address 63 4541

P17.21 [➙ 88] Baud rate 125K 4542

P17.22 [➙ 88] Access Rights Limitation FB NO 4786

P17.23 [➙ 88] Remote IP Address FB 192.168.240.250 4787

18 - Fixed mode configuration


Number: Name Default Customer Sys ID
P18.01 [➙ 93] ID Preset Value 1 320 6247

P18.02 [➙ 93] ID Preset Value 2 352 6248

P18.03 [➙ 93] ID Preset Value 3 384 6249

P18.04 [➙ 93] ID Preset Value 4 594 6250

P18.05 [➙ 93] ID Preset Value 5 0 6251

P18.06 [➙ 93] ID Preset Value 6 0 6252

P18.07 [➙ 93] ID Preset Value 7 0 6253

P18.08 [➙ 93] ID Preset Value 8 0 6254

P18.09 [➙ 93] ID Read Value 1 752 6256

P18.10 [➙ 93] ID Read Value 2 784 6257

P18.11 [➙ 93] ID Read Value 3 1552 6258

P18.12 [➙ 93] ID Read Value 4 1872 6259

P18.13 [➙ 93] ID Read Value 5 1874 6260

P18.14 [➙ 93] ID Read Value 6 1882 6261

P18.15 [➙ 93] ID Read Value 7 1904 6262

P18.16 [➙ 93] ID Read Value 8 1896 6263

19 - Ethernet
Number: Name Default Customer Sys ID
P19.01 [➙ 95] IP Address 192.168.240.1 6235

P19.02 [➙ 95] Net Mask 255.255.255.0 6236

P19.03 [➙ 95] Gateway 0.0.0.0 6237

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 52 - Schenck Process Group
Parameters

20 - Data Logging
Number: Name Default Customer Sys ID
P20.01 [➙ 96] Hourly Total Time 0 min 5743

P20.02 [➙ 96] Daily Total Time 0 min 5744

P20.03 [➙ 96] Logger cycle time 1 min 6288

P20.04 [➙ 96] Data Log Value 1 752 6289

P20.05 [➙ 96] Data Log Value 2 1872 6290

P20.06 [➙ 96] Data Log Value 3 1874 6291

P20.07 [➙ 96] Data Log Value 4 1882 6292

P20.08 [➙ 96] Data Log Value 5 1894 6293

P20.09 [➙ 96] Data Log Value 6 1896 6294

P20.10 [➙ 96] Data Log Value 7 1898 6295

P20.11 [➙ 96] Data Log Value 8 0 6296

P20.12 [➙ 96] Data Log Value 9 0 6297

P20.13 [➙ 96] Data Log Value 10 0 6298

21 - Configuration HMI Values


Number: Name Default Customer Sys ID
P21.01 [➙ 98] HMI Value 01 2004 6299

P21.02 [➙ 98] HMI Value 02 1882 6300

P21.03 [➙ 98] HMI Value 03 1942 6301

P21.04 [➙ 98] HMI Value 04 1874 6302

P21.05 [➙ 98] HMI Value 05 0 6303

P21.06 [➙ 98] HMI Value 06 0 6304

P21.07 [➙ 98] HMI Value 07 0 6305

P21.08 [➙ 98] HMI Value 08 0 6306

P21.09 [➙ 98] HMI Value 09 0 6307

P21.10 [➙ 98] HMI Value 10 0 6308

22 - Flow Gate
Number: Name Default Customer Sys ID
P22.01 [➙ 99] S: DO Open Flow Gate n/a 4702

P22.02 [➙ 99] S: DO Close Flow Gate n/a 4703

P22.03 [➙ 99] AI: Position Flow Gate n/a 4691

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 53 -
Parameters

P22.04 [➙ 99] AI: Offset 4 mA 4692

P22.05 [➙ 99] AI: Range 20 mA 4693

P22.06 [➙ 99] AO: Position Flow Gate n/a 4694

P22.07 [➙ 99] AO: Offset 4 mA 4695

P22.08 [➙ 99] AO: Range 20 mA 4696

P22.09 [➙ 99] Event: MIN Flow Gate W2 4697

P22.10 [➙ 99] Position MIN Flow Gate n/a 4698

P22.11 [➙ 99] Event: MAX Flow Gate W2 4699

P22.12 [➙ 99] Position MAX Flow Gate n/a 4700

23 - Additional device
Number: Name Default Customer Sys ID
P23.01 [➙ 102] DO: Agitator ON n/a 4654

P23.02 [➙ 102] START Agitator 0 % Io 4572

13.3.2 Parameter Details

13.3.2.1 Parameter Block 01 - Dialog Behaviour


The parameters of this group define system behavior towards the operator and set access authorization.

P01.01 Language Default: DEUTSCH


Alternative: DEUTSCH
ENGLISH
OTHER
Device dialog language. User-defined texts can be used if OTHER is selected. Texts can
be written and loaded using EasyServe.

P01.02 Userdefined Text Default: XX-NEW


Alternative: FR-FRANCAIS
ES-ESPANOL
IT-ITALIANO
CN-CHINESE
JP-JAPANESE
RU-RUSSIAN
HU-HUNGARIAN
NL-NETHERLAND
XX-NEW
Direct switching between several built-in languages.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 54 - Schenck Process Group
Parameters

P01.03 Font Default: UMing 30


Alternative: UMing 30
SAZ 30
Adjustable character representation. The current selection offers the versions of UMing30
for Chinese and SAZ30 for Japanese symbols.

P01.04 Units Default: Metric


Alternative: Metric
English
Switches display and parameter entry units from metric (SI units) to non-metric systems
(English). All values entered will be converted automatically.

P01.05 Control Default: NO


Alternative: NO
YES
Switch between feed rate regulation and simple measuring.

YES: metering, feed-rate regulating system


NO: measuring system

P01.06 Scale Name Default: INTECONT Tersus VIF

Letters and characters can be used. The name appears in the upper row of the operating
console and when searching through networks for controllers.

Remark: The characters ";" and "=" are not accepted. During the saving procedure these
characters will automatically be deleted.

P01.07 Password Default: 10000


Min: 1000 Max: 9999
Password 1 for access protection of certain functions on the operator panel as per the fol-
lowing parameters. Usually the 1st password is used for the service personnel and the 2nd
password for operating personnel with particular privileges. The password keyed in is
shown encoded for protection. The password can be reset using EasyServe if it should be
forgotten.
The password set at the factory: 7353

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 55 -
Parameters

P01.08 2. Password Default: 14389


Min: 1000 Max: 9999
Password 2 for access protection for certain functions on the operator panel as per the
following parameters. Usually the 1st password is used for the service personnel and the
2nd password for operating personnel with particular privileges. The password entered is
shown encoded on the screen. The password can be reset using EasyServe if it should be
forgotten.
The password set at the factory: 2889

P01.09 Switch Grav./Vol. command Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.10 Feeder ON/OFF Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

Using this parameters, access to the basic function prefeeder ON/OFF can be controlled.
The following options are available:
active: Access is always permitted.
not active: Access is never allowed. This function is not visible in the block.
Password: Access is available with the standard password.
2nd password: Access is available with the 2nd password.
Confirm: The access must be confirmed for security reasons.

Note: The prefeeder also has to be activated via parameters.

P01.11 Switch Keyboard-/Normal Mode Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 56 - Schenck Process Group
Parameters

P01.12 Batch control Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.13 >0: Zero ON/OFF Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for the function at the operating console.

P01.14 Reset Counter 1 Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.15 Reset Counter 2 Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.16 Data Log ON/OFF Default: not active


Alternative: active
not active
Password
2.Password
Confirm
Enables functions Start Data Logging , Stop Data Logging and Clear Data Log File.
Parameters see block Data Logging.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 57 -
Parameters

13.3.2.2 Parameter
Parameter Block 02 - Rated Data

P02.01 Flow Rate Units Default: ------ t/h


Alternative: ------ kg/h
----.- kg/h
---.-- kg/h
--.--- kg/h
------ t/h
----.- t/h
---.-- t/h
--.--- t/h
------ kg/s
----.- kg/s
---.-- kg/s
--.--- kg/s
----- kg/min
-----.- kg/min
----.-- kg/min
---.--- kg/min
Display format for setpoint and actual feed rate values.

P02.02 Nominal Flow Rate Default: 400 t/h


Min: 0.0001 t/h Max: 230000 t/h
The nominal flow rate is a characteristic value of the scale that acts as a reference value for
threshold values and service displays.

P02.03 Feeder Start Default: OP


Alternative: OP
FB
DI
Specifies the device that will turn on the scales.

The digital input is flank-controlled, i.e., the ON signal must be removed and then reapplied
if the scale becomes inoperative because of something like an alarm.

P02.04 Feedrate Setpoint Default: OP


Alternative: OP
FB
AI
Determines which signal input gives the flow rate setpoint.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 58 - Schenck Process Group
Parameters

P02.05 Counter 1 Unit Default: ------- t


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 1.

P02.06 Pulse Length Total Default: 0 ms


Min: 0 ms Max: 10000 ms
Duration of an external totalizing counter output impulse.

The weighting of a pulse (WI) is defined by P02.11 Totalizer Increment.

If the impulse duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.

The output frequency f is approximately Nominal Flow Rate:


f [Hz] = P02.02 / 3600 * P02.11

The output frequency must be ≤ 10 Hz if an external counter is connected.

P02.07 Counter 2 Unit Default: ------- t


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 2

P02.08 Counter 3 Unit Default: ------- t


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 3.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 59 -
Parameters

P02.09 Relative Setpoint Default: NO


Alternative: NO
YES
YES: The external absolute setpoints of the fieldbus (FB) or analog output (AI) can be eva-
luated relatively with the keyboard.

The value for the plant can be adapted through P12.15 Setpoint Offset as the starting value
and P12.17 Setpoint Range as the final value.

P02.10 DO: Pulse Counter Default: n/a


Alternative: n/a
DO
DO: Selecting the physical output for triggering an external pulse counter for the measured
quantity. Bear in mind the limitations on speed and life cycle when selecting a relay output
and set the weight equivalent for a pulse in P02.11 Totalizer Increment. The duration of the
impulse is set by P02.06 Pulse Length Total.

P02.11 Totalizer Increment Default: 10 kg


Min: 0 kg Max: 100000 kg
Weight equivalent of an impulse at the output for the external counter as per P02.10 DO:
Pulse Counter.
The DO: Pulse Counter is blocked when setting the valence '0'.

P02.12 Z1-Numberstep Default: Automatic


Alternative: Automatic
2 kg
5 kg
20 kg
50 kg
200 kg
500 kg
0.02 t
0.05 t
0.2 t
0.5 t
Determines the increment value for counter 1 and all batch values. Parameter P02.05
Counter 1 Unit applies for "Automatic".
The increment value only applies to the local display and for printouts.

13.3.2.3 Parameter Block 03 - Calibration Data

P03.01 LC Characteristic Value Default: 2.85 mV/V


Min: 0.01 mV/V Max: 9.9999 mV/V
Characteristic value (transmission factor) of the (main) load cell.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 60 - Schenck Process Group
Parameters

P03.02 Device Constant Default: 0.04 kgh/t


Min: 0.001 kgh/t Max: 1 kgh/t
This parameter describes the transfer response of the meter from the mass flow rate to the
measuring force in kg. You can find this value in the instrument's datasheet.

P03.03 LC Rated Capacity Default: 220 kg


Min: 0.5 kg Max: 220000 kg
The total of the load cell rated loads for recording the weight.

P03.04 Calibration Weight Default: 50 kg


Min: 0.001 kg Max: 22000 kg
The calibration weight serves to control the weighing system. so that the calibration pro-
gram CW: Span Calibration is run without bulk solids flowing.

The test weight as it acts on the load cell is keyed in.

P03.05 Calibration Time Default: 30 s


Min: 1 s Max: 60 s
Duration of the adjustment program.

13.3.2.4 Parameter Block 04 - Calibrat. Results

P04.01 Weight Correction Default: 1


Min: 0.5 Max: 2

P04.02 Total Tare Default: 0 kg


Min: 0 kg Max: 10000 kg
Total Tare = Basic Tare + Tare Correction

P04.03 Basic Tare Default: 0 kg


Min: 0 kg Max: 10000 kg
The result of the TW: Tare calibration program in accordance with the dead weight without
the flow of bulk solids.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 61 -
Parameters

P04.04 Tare Correction Default: 0 kg


Min: -1000 kg Max: 1000 kg
The results of the >0< Zero Set calibration program or automatic zero setting.

P04.05 Material Correction Default: 1


Min: 0.5 Max: 2
The correction factor for the measured flow rate ascertained with a check measurement
using bulk solids. This parameter can be set manually or by automatic check measurement
(KME) with DISOCONT Tersus.

Also refer to: the appendix with measuring the flow rate

13.3.2.5 Parameter Block 05 - Analog Outputs


The parameters in this group select the control source for the analog output channels. On the VCU 20104
controller only one analog channel is available and it is set to feedrate feedback by default.

P05.01 AO: Setpoint Default: n/a


Alternative: n/a
AO
Analog output channel for the flow rate set value.

Also refer to: P05.02 Setpoint Offset, P05.03 Setpoint Range

P05.02 Setpoint Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output current for the value of the flow rate set value of 0 %.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.01 AO: Setpoint

P05.03 Setpoint Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output current for the value of a flow rate set value of 100 %.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.01 AO: Setpoint

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 62 - Schenck Process Group
Parameters

P05.04 AO: Actual Flow Rate Default: n/a


Alternative: n/a
AO
Analog output channel for the actual flow rate.

Also refer to: P05.05 Flow Rate Offset, P05.06 Flow Rate Range

P05.05 Flow Rate Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output current for the value of the actual flow rate of 0 %.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.04 AO: Actual Flow Rate

P05.06 Flow Rate Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output current for the value of the actual flow rate of 100 %.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.04 AO: Actual Flow Rate

P05.07 AO: Actual Flow Rate (2nd) Default: n/a


Alternative: n/a
AO

P05.08 AO: Load Default: n/a


Alternative: n/a
AO
The definition of the output channel for the load measured.

Also refer to: P05.09 Load Offset, P05.10 Load Range

P05.09 Load Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output current for a platform load of 0 %.

Also refer to: P05.08 AO: Load

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 63 -
Parameters

P05.10 Load Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output current for a platform load of 100 % of the nominal load (service value).

Also refer to: P05.08 AO: Load

P05.11 AO: Motor Speed Control Default: n/a


Alternative: n/a
AO
Analog output channel for the actuating variable Y of the feed rate regulator.

Also refer to:


- the parameters in the 'regulator' block
- the regulator diagram in the appendices

13.3.2.6 Parameter Block 06 - Limit Values


The parameters of this group define the limits for process values and specify the event classes of the asso-
ciated events.

Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.

P06.01 Limit: Actual Flow Rate MIN Default: 5 % Io


Min: -10 % Io Max: 200 % Io
Lower threshold for the actual feed rate.

Reference : P02.02 Nominal Flow Rate

P06.02 Event: Actual Flow Rate MIN Default: W2


Event Group: LO Number: 02

The actual feed rate is lower than the minimum value P06.01 Limit: Actual Flow Rate MIN.

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low

P06.03 Limit: Actual Flow Rate MAX Default: 120 % Io


Min: -10 % Io Max: 200 % Io
Upper threshold for the actual feed rate.

Reference : P02.02 Nominal Flow Rate

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 64 - Schenck Process Group
Parameters

P06.04 Event: Actual Flow Rate MAX Default: W2


Event Group: HI Number: 02

Actual feed rate higher than the maximum value set in P06.03 Limit: Actual Flow Rate MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too large

P06.05 Stand-By Limit Value Default: 0 % Io


Min: 0 % Io Max: 100 % Io
If the controller magnitude is below the threshold value, the feed drive is switched off to
protect the motor from overheating.

Also refer to: P06.06 Event: Stand-By

P06.06 Event: Stand-By Default: W2


Event Group: SC Number: 02

Scales are in standby operation, i.e. the controller magnitude to the feed drive is smaller
than the threshold value set in P06.05 Stand-By Limit Value. The feeder drive is switched
off. The 'running' state will still be displayed.

This function protects the motor from overheating at very low speeds or when idling.

Actions:
Key in the larger setpoint and check P06.05 Stand-By Limit Value.

13.3.2.7 Parameter Block 07 - Filters


The parameters of this group define the time constants of the filters for measurement and display.
All filters are of the 1st order (exponentially), i.e. approximately 2/3 of the final value is reached after the
time set if there is an abrupt change in the signal.
Long times result in a smooth, slowly-updating display.

P07.01 Filter: Actual Flow Rate Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for the display and for outputs of the actual flow rate at the operating
element, EasyServe and fieldbus. Has no effect on the feeder regulation.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 65 -
Parameters

P07.02 Filter: Actual Flow Rate analog Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for the 'actual flow rate' analog output. The filter can have an impact on
the control characteristics with an externally closed control circuit through the analog value.

P07.03 Filter: Load Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for the display of the load on the load cell. The filter only has an impact
on the display, not on the further processing of the signal for determining the flow rate and
quantity measured.

P07.04 LC Filter Default: 1 s


Min: 0 s Max: 600 s
The load cell filters affects all load cell related measuring values. In general this value
should be left at the factory setting.

Note: filtering the load cell signal also effects the regulating action.

P07.05 Afterflow Totalizer Default: 3 s


Min: 0 s Max: 2000 s
For this time after shutting off, the scale continues to record the resulting quantity conveyed
through the afterflow of bulk solids when the drives run out.

13.3.2.8 Parameter Block 08 - AUTO Zero Set

P08.01 Auto Zero Active Default: NO


Alternative: NO
YES
Preselection of the automatic zeroing system that corrects the zero point after each belt
circuit with an empty belt.

See also:
P08.03 Zeroing Limit
P08.04 Event: Tare Correction
#$
P08.02 Mean Limit Value

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 66 - Schenck Process Group
Parameters

P08.02 Mean Limit Value Default: 1 % Q


Min: 0 % Q Max: 10 % Q
Second precondition for the automatic zeroing system. Determines the max. permitted
mean value of the belt load via two subsequent belt circuits.

Reference: Nominal Belt Load (service value)

See also:
P08.01 Auto Zero Active
P08.03 Zeroing Limit
#$

P08.03 Zeroing Limit Default: 5 % Q


Min: 0 % Q Max: 100 % Q
Maximum permissible value of the sum of all zeroing operations of the manual or automatic
zeroing system.

Reference: Nominal Belt Load (Service value)

P08.04 Event: Tare Correction Default: W1


Event Group: CA Number: 06

The tare value calculated by the automatic zeroing system is in excess of


P08.03 Zeroing Limit.
The value is not accepted.

P08.05 Zero Set Difference Default: 5 % Q


Min: 0 % Q Max: 100 % Q
Permitted sum of the difference between two consequent zero setting interventions into the
manual or automatic zeroing system.

P08.06 Event: Tare Difference > MAX Default: W2


Event Group: CA Number: 12

P08.05 Zero Set Difference is past.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 67 -
Parameters

P08.07 Zero Drop-Out Active Default: NO


Alternative: NO
YES
The zero drop out function sets the display of the flow rate to zero when the load drops
below the threshold value in P08.07 Zero Drop-Out Active. This prevents the totalizing
counter from running on if measuring continues for a longer period while no bulk material
flows. This suppresses small, unavoidable tare errors.

YES: activate the Zero Drop Out system.


NO: Zero Drop Out has no effect. The small operating range is displayed at the measured
value.

P08.08 Zero Drop-Out Limit Default: 1 % Q


Min: 0 % Q Max: 10 % Q
Recording the total is suppressed with measurements within this limit around the zero point
to ensure that the counter remains constant when the belt is idle.
No feature appears on the display.

Reference: Nominal Belt Load (service value)

13.3.2.9 Parameter Block 09 - Batch Mode


The parameters of this group define and optimize behavior in batch mode. Batching mode is used to ensure
that the feeder turns off independantly after conveying a preset quantity.

Also refer to the chapter in the manual:


'General Diagram' → 'Batching'
'Appendix' → 'Batch Operation Control'

P09.01 Correction Amount Default: 0 kg


Min: -1000000 kg Max: 220000 kg
The start of the adaptation time is shifted by this quantity. An adaptation time = 0 corres-
ponds to a pre-threshold.
The correction quantity should be set to 0 for initial startup. The value of Correction Amount
is adapted after each batch if P09.02 Adaptation Factor is not equal to zero so that the
defect of the next batch is minimized.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 68 - Schenck Process Group
Parameters

P09.02 Adaptation Factor Default: 1


Min: 0 Max: 1
The application point of the switch-off function is adapted automatically so that the system
is better adapted to the actual conditions for the next batch.

Adaptation Factor = 0 : no adaptation


Adaptation Factor = 1 : full adaptation

Interim values result in filtered adjustment; this should be used in particular for systems with
poor reproducibility.
The result of the event is stored in P09.01 Correction Amount.

P09.01 NEW = P09.01 OLD - Batch Residual Amount * P09.02

P09.03 Adaptation Time Default: 3 s


Min: 0 s Max: 3600 s
Establishes the duration of the entire dribble feed phase.

P09.04 Batch Tolerance Default: 100000 kg


Min: 0 kg Max: 1000000 kg
If the batch lies outside of the tolerance range, the maximum alteration of
the correction quantity at adaptation is the entered tolerance value. Also, an event is identi-
fied.

Also refer to: P09.05 Event: Out of Tolerance

P09.05 Event: Out of Tolerance Default: W1


Event Group: MF Number: 06

The batch result is outside the tolerance range.

Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces

P09.06 Batch Setpoint Source Default: OP


Alternative: OP
FB
Establish the source that will determine the batch.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 69 -
Parameters

P09.07 Batch Automatic Record Default: NO


Alternative: NO
YES
YES: automatic print after each completed batch.
NO: Printout of the batch can only be made via menu.

The printout can be made only after a batch has ended automatically or manually. The
printout is stored to a file that can be read using the Web-Server.

P09.08 Reset print FMZ 1 Default: NO


Alternative: NO
YES
YES: Clearing counter 1 when the next batch starts
(if the batch has been recorded).
NO: Counter 1 can only be deleted via the operating function.

P09.09 Reset print FMZ 2 Default: NO


Alternative: NO
YES
as P09.08 for counter 2.

13.3.2.10 Parameter Block 10 - Maintenance interval


The parameters of this group define maintenance intervals and the internal accuracy analysis function.

P10.01 Maintenance Electric Default: 3000 h


Min: 1 h Max: 10000 h
Indication of maintenance work that may need to be performed, dependent on the duty
cycle of the power supply. This parameter defines the interval between maintenance work.

Also refer to: P10.02 Event: Maint. Electric

P10.02 Event: Maint. Electric Default: W1


Event Group: SC Number: 04

The sum of the times during which the mains voltage is on is greater than the time P10.01
Maintenance Electric.

A message occurs after each expired time interval. The message may indicate service work
required.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 70 - Schenck Process Group
Parameters

P10.03 Maintenance Feeder Run Default: 3000 h


Min: 1 h Max: 10000 h
Indication of maintenance work that may need to be performed, dependent on the duty
cycle of the scales (scales ON). This parameter defines the interval between maintenance
work.

Also refer to: P10.04 Event: Maint.Feeder Run

P10.04 Event: Maint.Feeder Run Default: W1


Event Group: SC Number: 03

The sum of the runtimes of the conveying elements is greater than the time P10.03 Main-
tenance Feeder Run.

A message occurs after each expired time interval. The message may indicate service work
required.

13.3.2.11 Parameter Block 11 - Events

P11.01 Event: Power Failure Default: A


Event Group: WE Number: 01

This event is identified once the power supply is restored.

The scales will not switch on automatically, regardless of the event class. The event must
first be acknowledged and the command to start given again before the scales will restart.

P11.02 Event: Memory Default: A


Event Group: SY Number: 01

The program and parameters memory are checked cyclically. An error has occurred during
that. The scales will no longer function correctly.

Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 71 -
Parameters

P11.03 Event: Error LC Input Default: A


Event Group: CA Number: 01

The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.

Measures:
- check the cabling and the load cell
- check the load cell

Note:
The power supply must be switched off and on again if the scales cannot be switched on
even after the error has been rectified.

P11.04 Event: Run Disabled Default: W1


Event Group: IL Number: 01

No release signal from the source determined by P14.01 Source Run Enable.

If this event is pending then the downstream transport equipment is most likely not switched
on.

P11.05 Event: LC Input > MAX Default: A


Event Group: HI Number: 01

The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.

Measuring range end:


125 % for load cells with 2.85 mV/V
175 % for load cells with 2 mV/V

Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 72 - Schenck Process Group
Parameters

P11.06 Event: LC Input < MIN Default: A


Event Group: LO Number: 01

The load cell load is less than 3 % of the sum of the load cell nominal loads.

Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell

P11.07 Event: Simulation active Default: W2


Event Group: SY Number: 14

Simulation operation is on.

P11.08 Event: Setpoint Limited Default: W1


Event Group: SC Number: 01

Cause of the event:


Depending on the respective mode of operation:
a) The setpoint is limited to P02.02 Nominal Flow Rate in gravimetric operation.
b) The setpoint is limited to three times the value of P02.02 Nominal Flow Rate in volume-
tric operation.

P11.09 Event: External Event 1 Default: A


Event Group: SC Number: 05

External interference signal at fault input 1.

Possible cause: depends on the external cabling. Usually: an error in the main drive

P11.10 Event: External Event 2 Default: A


Event Group: SC Number: 06

External interference signal at fault input 2.

Possible cause: depends on the external cabling.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 73 -
Parameters

P11.11 Event: License Violation Default: A


Event Group: SY Number: 09

13.3.2.12 Parameter Block 12 - Rate controller

P12.01 Controller Type Default: Continuous


Alternative: Continuous
Stepping
Choose a controller model

Continuous: The controller generally calculates a continuous controller magnitude as an


analogous value. If position-controlled prefeeders are used, the position has to be con-
trolled externally according to the specifications from the continuous value.

Stepping: The controller controls the position of a position-controlled prefeeder with the
digital Open and Close outputs.

Also refer to: the appendix for details on the controller models

P12.02 P-Component KP Default: 0.02 mA/%


Min: 0 mA/% Max: 1000 mA/%
Proportional component of the feed rate regulator.

Special case: KP = 0 results in an I-regulator

Reference value: P02.02 Nominal Flow Rate

Also refer to:


A regulator block diagram can be found in the appendices

P12.03 I-Component TN Default: 3 s


Min: 0 s Max: 60000 s
Controller readjusting time.

TN is the reciprocal value of the integration constants KI, i.e. a larger value means a slower
controller.
KI = 1/TN
TN in %/(mA/s)

Reference value: P02.02 Nominal Flow Rate

TN = 0 results in a proportional controller.

Also refer to:


A regulator block diagram can be found in the appendix

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 74 - Schenck Process Group
Parameters

P12.04 Time Deviation Default: 20 s


Min: 0 s Max: 600 s
Duration for which a control deviation above the threshold in P12.05 Threshold Deviation
will be tolerated. The event 'control deviation' is identified once the time has been ex-
ceeded.

Simultaneously P12.04 Time Deviation functions as a time constant for the filter that con-
tains the value of the control deviation. A 'control deviation' event is also identified if the
filtered result exceeds the threshold value P12.08 Deviation abs. max..

Also refer to:


P12.05 Threshold Deviation
P12.06 Factor Deviation
P12.08 Deviation abs. max.
P12.07 Event: Deviation

P12.05 Threshold Deviation Default: 5 %


Min: 0 % Max: 100 %
Maximum permissible control deviation.
Reference: P02.02 Nominal Flow Rate.

Also refer to: P12.04 Time Deviation, P12.07 Event: Deviation

P12.06 Factor Deviation Default: 1


Min: 0 Max: 1
An event message as per P12.07 Event: Deviation will be identified if the absolute value of
the control deviation for the duration P12.04 Time Deviation is greater than the threshold
P12.05 Threshold Deviation.
With a setpoint of 100%, the effective threshold is always determined by the parameter
P12.05 Threshold Deviation. For lower setpoints the threshold can be reduced with para-
meter P12.06 Factor Deviation.
Examples:
P12.06 = 0 : Effective threshold = P12.05 × Setpoint / P02.02
P12.06 = 1 : Effective threshold = P12.05

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 75 -
Parameters

P12.07 Event: Deviation Default: W1


Event Group: HI Number: 05

Maximum Deviation exceeded. The actual feed rate has deviated to far from the setpoint
over too long a period of time.

Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder

- the controller has at times come against its limits


- error in the electronics
- check the cable to the external output regulator and to the motor. Check the output regu-
lator settings (current limiting, speed range)

- calibration error: during initial calibration the regulator was set at such a critical value that
minor changes in the overall properties of the system lead to unreliable operation.

Also refer to: P12.08 Deviation abs. max., P12.06 Factor Deviation, P12.05 Threshold Dev-
iation, P12.04 Time Deviation

P12.08 Deviation abs. max. Default: 100 %


Min: 0.1 % Max: 1000 %
The amount of the control deviation will be filtered (filter time constant: P12.04 Time Devia-
tion). If the filter output exceeds the limit set here a 'control deviation' event will be identified
(P12.07 Event: Deviation). The filter is reset when the scales are switched off.

P12.09 Event: Controller Limited Default: W1


Event Group: CO Number: 01

The Controller Magnitude of the feed rate regulator has reached the upper response thre-
shold. After a time message HI05 (P12.07) will be output.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.

Step to take: check the material discharge and the Controller Magnitude (service value Y).
At Nominal Flow Rate Y should be between about 10...14 mA.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 76 - Schenck Process Group
Parameters

P12.10 Lower Limit Default: 0 mA


Min: 0 mA Max: 20 mA
Lower limit for the regulator actuating variable.

If transfer is made with currents from 4 ... 20 mA, the parameter should be set at least to
4 mA. P12.12 Controller Magnitude Offset must be set to a value equal to or greater than
P12.10 Lower Limit.

Also refer to: P12.12 Controller Magnitude Offset

P12.11 Upper Limit Default: 20 mA


Min: 0 mA Max: 20 mA
Upper limit for the regulator actuating variable.

With inputs lower than 20 mA the limit depends on the size of the threshold value.

Also refer to:


A description of the effect of the upper limit can be found in the appendices

P12.12 Controller Magnitude Offset Default: 0 mA


Min: 0 mA Max: 20 mA
Offset of the actuating variable by a constant value. The offset takes effect before the limi-
tation of the actuating variable.

Generally the same values are chosen for P12.12 Controller Magnitude Offset as for
P12.10 Lower Limit.
Optimization:
- fill the feeder hopper with bulk material
- calculate the actuating variable Y1, the value at which the discharge unit begins to work
- calculate the actuating variable Y2, the value at which reduction of the feed is suspended.
For feeders that are operated with feed rate setpoints of 0:
P12.12 Controller Magnitude Offset = Y2
All other feeders:
P12.12 Controller Magnitude Offset = Y1

Note: P12.12 Controller Magnitude Offset must be equal to or greater than P12.10 Lower
Limit.

P12.13 Position at STOP Default: 0


Alternative: 0
Lower Limit
If the scales are switched off the actuating variable can be set to 0 or to the offset value
P12.10 Lower Limit.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 77 -
Parameters

P12.14 Volumetric Start-Up Default: 0 s


Min: 0 s Max: 3600 s
Length of time it takes to begin volumetric operation once the scales have been switched
on. If selected, feeding will switch to gravimetric operation once the startup time has past.

This function improves the startup with an empty feeder.


The optional speed controller is also active during startup.

P12.15 Setpoint Offset Default: 0 mA


Min: 0 mA Max: 200 mA
Input current offset for an analog setpoint of 0 % of Nominal Flow Rate.

This parameter takes effect only if P02.04 Feedrate Setpoint has been set to AI.

P12.16 Filter: Deviation Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for all displays and printouts of the control deviation.

P12.17 Setpoint Range Default: 20 mA


Min: 0 mA Max: 200 mA
Input current for the analog setpoint of 100 % of the Nominal Flow Rate.

The range and offset parameters take effect only if P02.04 Feedrate Setpoint has been set
to AI.

P12.18 Store Default: NO


Alternative: NO
YES
YES-A
Saving the control magnitude before turning off the scale. The next start will begin with this
value.

NO: do not save


YES: save
YES-A: only save if the scale has not broken down due to an alarm

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 78 - Schenck Process Group
Parameters

P12.19 Bypass Default: 10 mA


Min: 0 mA Max: 20 mA
The constant for the setpoint bypass (also refer to the controller figure in the appendix). The
bypass instantaneously passes on a portion of the flow rate setpoint to the controller magni-
tude to the feed drive. This parameter contains the current at which the prefeeder just sup-
plies the nominal flow rate (P02.02 Nominal Flow Rate).

Setting: operate the feeder volumetrically and set the bypass so that actual flow rate = set-
point. This value should be approximately 10 ... 15 mA. Otherwise the external flow rate
controller should be adjusted.

P12.20 Setpoint Filter 1st Ord Default: 0 s


Min: 0 s Max: 6000 s
The time constant for a 1st-order filter in the setpoint branch. Does not function for the by-
pass.

To prevent overshoot, the setpoint is decoupled from the actual controller


through a reconstruction of the controlled member. The setpoint filters P12.20 and P12.21
delay the controller while the bypass comes to the controller magnitude output without a
delay.

The filter is switched off with P12.20 = 0.

Also refer to: the controller figure in the appendix

P12.21 Setpoint Filter 2nd Ord Default: 2 s


Min: 0 s Max: 6000 s
The time constant for a second filter in the setpoint branch. Does not function for the by-
pass.

To prevent overshoot, the setpoint is decoupled from the actual controller


through a reconstruction of the controlled member. The setpoint filters P12.20 and P12.21
delay the controller while the bypass comes to the controller magnitude output without a
delay.

The filter is switched off with P12.21 = 0.

Also refer to: the controller figure in the appendix

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 79 -
Parameters

P12.22 KP Adaptation Default: 1


Min: 0 Max: 2
Setpoint-dependent review of the proportional component of the regulator.

This parameter is used to optimize the regulation action for small setpoints.

For example:
KP control= 1 : KP is independent of the setpoint

KP control = 0: KP decreases in proportion to the setpoint

KP control = 2: KP increases in proportion to the setpoint

P12.23 Setpoint Threshold Default: 0 % Io


Min: 0 % Io Max: 100 % Io
This parameter can be used separately to set the control for start-up and normal operation.
Below the target value threshold in P12.23, the control deviation is multiplied with the factor
adjusted in P12.22 KP Adaptation before entering into the controller. The factor is set to 1
above the threshold.

Examples:
Target value threshold = 0: The proportional component is evaluated independant of the
setpoint as described with parameter P12.22.

Target value threshold > 0%: The controller input is evaluated with the parameter P12.22
below this threshold. The controller input remains unaffected by P12.22 above this thre-
shold.

Reference value: P02.02 Nominal Flow Rate

P12.24 S: P-Component Default: 0.033 s/%


Min: 0 s/% Max: 1000 s/%

P12.25 S: I-Component Default: 3 s


Min: 0 s Max: 60000 s

P12.26 S: Threshold Response Default: 0.1 %


Min: 0 % Max: 1000 %

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 80 - Schenck Process Group
Parameters

P12.27 Compensation Element Default: 0 1/s


Min: 0 1/s Max: 60000 1/s
The compensation element is an additional integrator in the control deviation branch that
only
functions in gravimetric operation. It is used to
• overcoming the trigger threshold.
• reducing contouring errors with monotonically changing malfunctions.
• avoid the remaining control deviations with a non-symmetrical
control element and cyclical malfunctions.

The input and output of the compensation element are limited to 5 %. The parameter gives
the integration constant.

Special case: P12.27=0: The integrator is cleared.

Configuration for the compensation element to correct contouring errors. There might be
contouring errors if the volumetric flow rate depends on the level of a bin and the bin is
emptied.

13.3.2.13 Parameter Block 13 - Linearization


The parameters of this group define the characteristic curve of a non-linear external component and offset
its effect.

P13.01 Linearization ON Default: NO


Alternative: NO
YES
Load measuring can be linearized with this parameters.
The 4 linearization points can be determined by calibration with calibration weights or using
material. Not required or not measured points must be laid either outside the measuring
range or must be interpolated.

Consider the location of the linearization in the signal processing (--> appendix).
Detailed calibration instructions are in the appendix.

P13.02 Linearization S1 Default: 25 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 1:
Actual belt load, e.g. determined using calibration weights or by material measurement.

P13.03 Linearization I1 Default: 25 % Q


Min: 0.01 % Q Max: 1000 % Q

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 81 -
Parameters

P13.04 Linearization S2 Default: 50 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 2.
Otherwise as P13.02 Linearization S1

P13.05 Linearization I2 Default: 50 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 2.
Refer to P13.03 Linearization I1 for a description

P13.06 Linearization S3 Default: 75 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 3.
Otherwise as P13.02 Linearization S1

P13.07 Linearization I3 Default: 75 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 3.
Refer to P13.03 Linearization I1 for a description

P13.08 Linearization S4 Default: 100 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 4.
Otherwise as P13.02 Linearization S1

P13.09 Linearization I4 Default: 100 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 4.
Refer to P13.03 Linearization I1 for a description

P13.10 Event: Linearization Error Default: W2


Event Group: CA Number: 05

Not a monotonically increasing curve.

A monotonically increasing compensation curve is monitored when:


- linearization is switched on,
- a parameter is altered

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 82 - Schenck Process Group
Parameters

13.3.2.14 Parameter Block 14 - Digital Inputs


The parameters in this group are used to associate various controller functions with specific digital input
channels and to associate events with those functions. Most of the functions specified in this group are hard
wired on the controller and cannot be changed.

P14.01 Source Run Enable Default: DI IT.DI3 High


Alternative: DI
FB
n/a
Determines the signal input that gives the scales release signal. This input is generally
used for interlocking with downstream transport equipment.

The setting 'n/a' means that no release is required.

P14.02 DI: Batch Terminate Default: n/a


Alternative: n/a
DI
Digital input signal for stopping a current batch.

P14.03 DI: Acknowledge Events Default: DI IT.DI1 High


Alternative: DI
n/a
Digital input for acknowledging event messages.

Caution: the level is static and may not be on permanently (otherwise continuous acknowl-
edgement).

P14.04 DI: Start Default: n/a


Alternative: n/a
DI
If OP is selected as the turn-on source, the digital input that the scale can be started with
using a turn-on impulse can be configured here in parallel to the ON/OFF buttons on the
keyboard.
The scale is turned off by an impulse on the digital input P14.01 Source Run Enable.

P14.05 DI: External Event 1 Default: n/a


Alternative: n/a
DI
Input 1 for an external interference signal.

The input is also linked to the internal interference logic (block: interlocking).

Also refer to: P11.09 Event: External Event 1

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 83 -
Parameters

P14.06 DI: External Event 2 Default: n/a


Alternative: n/a
DI
Input 2 for an external interference signal.

The input is also linked to the internal interference logic (block: interlocking).

Also refer to: P11.10 Event: External Event 2

P14.07 DI: Reset Totalizer 1 Default: n/a


Alternative: n/a
DI
Digital input for canceling totalizing counter 1. The positive flank is the actuator.

P14.08 DI: Reset Totalizer 2 Default: n/a


Alternative: n/a
DI
Digital input for clearing totalizing counter 2. The positive flank takes effect.

P14.09 DI: Volumetric Mode Default: n/a


Alternative: n/a
DI
Digital input for switching the scales to volumetric operation, not synchronized with previous
operation.

Also refer to: P14.10 DI: Volumetric synchron

P14.10 DI: Volumetric synchron Default: n/a


Alternative: n/a
DI
Switches to volumetric operation while the actuating variable continues continuously. The
actuating variable is calculated as an average of the actuating variable obtained during
regular operation. Alterations to the feed rate setpoint automatically adjust the actuating
variable.

Also refer to: P14.09 DI: Volumetric Mode

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 84 - Schenck Process Group
Parameters

13.3.2.15 Parameter Block 15 - Digital Outputs


The parameters in this group are used to associate various controller functions with specific digital output
channels. Most of the functions specified in this group are hard wired at assembly.

P15.01 DO: ALARM Default: DO IT.DO3 Low


Alternative: DO
n/a
The output becomes active if any alarm is triggered (common alarm). The scales have
failed.

P15.02 DO: Start Prefeeder Default: DO IT.DO6 High


Alternative: DO
n/a
The digital output for turning the prefeeder on or off.

P15.03 DO: Scale Start Default: DO IT.DO7 High


Alternative: DO
n/a
Sends a start command to the feeder's main drive.

P15.04 DO: Actual Flow Rate MIN Default: DO IT.DO4 Low


Alternative: DO
n/a
The output signal becomes active if the feed rate falls below the minimum feed rate (P06.01
Limit: Actual Flow Rate MIN).

The contact output is independent of the event class.

P15.05 DO: Actual Flow Rate MAX Default: DO IT.DO2 Low


Alternative: DO
n/a
The output signal becomes active when the maximum feed rate (P06.03 Limit: Actual Flow
Rate MAX) is exceeded.

The contact output is independent of the event class.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 85 -
Parameters

P15.06 DO: Batch Running Default: n/a


Alternative: n/a
DO
The output becomes active if a batch is run.
The signal is active at the start of the batch and deactivated again when the batch has been
completed. It remains active if batch operation is continuous.

P15.07 DO: Full Feed Default: n/a


Alternative: n/a
DO
The output becomes active in the full feed phase.

P15.08 DO: Dribble Feed Default: n/a


Alternative: n/a
DO
The output becomes active in the dribble feed phase.

P15.09 DO: Keyboard Mode Default: n/a


Alternative: n/a
DO
The output becomes active when keyboard mode is preselected.

(The DISOCONT Tersus is operated using the operating console VHM or EasyServe).

P15.10 DO: Volumetric Mode Default: n/a


Alternative: n/a
DO
The output becomes active if the scales are switched to a volumetric mode.

P15.11 DO: Deviation Default: DO IT.DO5 Low


Alternative: DO
n/a
The output signal becomes active when the monitoring activates the control deviation
(P12.07 Event: Deviation).

This contact output is independent of the event class.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 86 - Schenck Process Group
Parameters

13.3.2.16 Parameter Block 16 - Communication EasyServe


The parameters of this group define the parameters for serial communication with EasyServe via RS232 or
RS485. These parameters have no function if EasyServe is connected via Ethernet.

P16.01 Own Address Default: 1


Min: 1 Max: 254
Relevant only for EasyServe connection via RS232 or RS485.

All devices connected to the communicatio bus must have disjunct addresses.

Also refer to: P16.02 Baud Rate, P16.03 Format Data

P16.02 Baud Rate Default: 38400


Alternative: 38400
Relevant only for EasyServe connection via RS232 or RS485.

Data transfer speed. This parameter is used for information only. The speed cannot be
changed.

P16.03 Format Data Default: 8-N-1


Alternative: 8-N-1
Relevant only for EasyServe connection via RS232 or RS485.

Formats the serial data. The value is used for information only and cannot be altered.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 87 -
Parameters

13.3.2.17 Parameter Block 17 - Communication Fieldbus


The parameters of this group define the communication procedure to be used to a higher-level plant control
system and configure the data link.

Details on the fieldbus interface can be found in the following manuals:


DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P17.01 Protocol Type Default: NO


Alternative: NO
Modbus-RTU
PROFIBUS DP
DeviceNet
Modbus-TCP
Ethernet/IP
Type of communication protocol. Some types of fieldbus need their respective fieldbus
card.

DISOCONT Tersus: Further details on card installation can be found in the system manual
BV-H2406. Manual 'Data Communication' (BV-H2448) contains further information on the
data structures.
INTECONT Tersus: Manual 'Data Communication' (BV-H2474) contains further information
on the data structures.

NO: Modbus-TCP can be used to read but write-accesses will not be processed.

Modbus-RTU: RS232, RS422 or RS485 interface; fieldbus interface card VSS 28020 must
be installed.

PROFIBUS DP: Fieldbus interface card VPB 28020 must be installed.

DeviceNet: Fieldbus interface card VCB 28020 must be installed.

Modbus-TCP: Complete communication (read/write) using Ethernet and the main VCU
RJ45 plug.

Ethernet/IP: Communication via Ethernet and the RJ45 plug on the main VCU.

The red-coded RJ45 socket X96 may not be used for communication with the host comput-
er.

P17.02 Timeout Host Default: 5 s


Min: 1 s Max: 600 s
Monitors the interface

A telegram from the host system will be expected within the time set if the timeout value in
P17.02 is greater than zero.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 88 - Schenck Process Group
Parameters

P17.03 Event: Cyclic Communication Default: A


Event Group: SY Number: 08

Cyclical serial communication with the higher-order plant control system has been inter-
rupted for longer than the timeout-period in P17.02.

To rectify: check cable connections.

P17.04 Event: Acyclic Communication Default: W2


Event Group: SY Number: 10

Incorrect data in the noncyclical communication from the host computer.

Possible cause: poor programming of the host computer

P17.05 Check in Keyboard Mode Default: YES


Alternative: NO
YES
To be able to use keyboard mode as emergency operation if coupling fails (without having
to log off the fieldbus coupling), this parameter can be used
to deactivate fieldbus communication monitoring in keyboard mode.
This allows the scales to be operated even if the fieldbus link fails.

P17.06 Compatibility DISOCONT Master Default: NO


Alternative: NO
YES
Compatibility setting for the predecessor electronics systems DISOCONT or INTECONT
PLUS.

NO: Not completely compatible


YES: compatible, but with restricted data link compatibility for new functions

P17.07 Word Sequence Default: I:std/L:std


Alternative: I:std/L:std
I:swp/L:std
I:std/L:swp
I:swp/L:swp
The parameter determines the word sequence within a double word.

I → denotes IEEE 754 values (floating-point values)


L → denotes LONG values (4 byte integer values)
std → will not swap the word order
swp → will swap the word order

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 89 -
Parameters

P17.08 Byte Sequence Default: High - Low


Alternative: High - Low
Low - High
Determines the byte sequence in a data word.

P17.09 Configuration Default: FIXED_8_8


Alternative: NO_PARA_ID_3_6
PARA_ID_2_4
PARA_ID_3_6
FIXED_8_8
FIXED_4_4
The configuration of the content of the data of the fieldbus telegrams. You can find a de-
tailed description in the manuals for data communication:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

The contents of the data have to be set on the scale and opposite point in a way that is
compatible to one another!

P17.10 Address Default: 1


Min: 1 Max: 254
Address of the device as a slave at the modbus.
Each address may be used at a bus once only.

P17.11 Resolution Default: 4096


Min: 1 Max: 32767
The maximum resolution in analog format or integer format of the measured value trans-
ferred.
The resolution is related to the nominal value of the respective process value.

P17.12 Baud rate Default: 9600


Alternative: 2400
4800
9600
19200
38400
Data transfer rate at Modbus-RTU.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 90 - Schenck Process Group
Parameters

P17.13 Data Format Default: 8-O-1


Alternative: 8-O-1
8-E-1
8-N-1
Modbus-RTU always uses an 11-bit character frame.

Example: 8-O-1 means:


1 start bit, 8 data bit, odd parity, 1 stop bit

N = No parity
O = Odd parity
E = Even parity

P17.14 Physics Default: RS232


Alternative: RS485-2-wire
RS485-4-wire
RS232
Selects the electrical interface type (Modbus RTU)

P17.15 Address Default: 16


Min: 0 Max: 126
Address of the slave at the PROFIBUS

P17.16 FLOAT-Format Default: IEEE


Alternative: IEEE
SIEMENS-KG
Information on the formats for all setpoints, measuring values and floating point parame-
ters.

P17.17 Compatiblity INTECONT Default: NO


Alternative: NO
YES
Compatibility to earlier PROFIBUS-Versions of INTECONT PLUS.
Relevant for replacement by INTECONT Tersus.

YES: Ident-No. 0524 is valid and GSD-file of INTECONT PLUS has to be used.

NO: Ident-No. 0C9B is valid and GSD-file of INTECONT Tersus has to be used.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 91 -
Parameters

P17.18 Identifier format Default: BYTE


Alternative: BYTE
WORD

The configuration bytes correspond to INTECONT PLUS if the parameter is on bytes. Oth-
erwise, the data are written in words. Consistency always refers to a data word or double
data word.

This parameter together with P17.19 PA32 compatible guarantees that there is no problem
exchanging with PROFIBUS Master in an existing system without having to adapt Master.

P17.19 PA32 compatible Default: NO


Alternative: NO
YES
YES: It is filled with ZERO bytes to 32 bytes with a defined data scope <32 bytes

P17.20 Address Default: 63


Min: 0 Max: 63
The address of the weighing electronics on DeviceNet

P17.21 Baud rate Default: 125K


Alternative: 125K
250K
500K
Data transfer rate of the DeviceNet.

P17.22 Access Rights Limitation FB Default: NO


Alternative: NO
FIRST WRITE
REMOTE IP
Determines for network protocol Modbus-TCP which master system may intervene as a
controller:

NO: No restrictions

FIRST WRITE: The subscriber that transmits the first write access gets the control rights.
The other subscribers may read only.

REMOTE IP: Control commands from the subscriber with the IP address given in P17.23
Remote IP Address FB only will be carried out.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 92 - Schenck Process Group
Parameters

P17.23 Remote IP Address FB Default: 192.168.240.250

IP address of the subscriber with control rights for Modbus-TCP.

Also refer to: P17.22 Access Rights Limitation FB

13.3.2.18 Parameter Block 18 - Fixed mode configuration


configuration
Configuration of the data in fieldbus communication 'FIXED' mode that were exchanged with the host com-
puter via serial interface.

Also refer to: P17.09 Configuration

For the available data and their Ids see the separated communication manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P18.01 ID Preset Value 1 Default: 320

Selecting the first control command with ID 320 (decimal) in the Fieldbus telegram. It can-
not be changed in this parameter.

The following values in the telegram can be configured as per the ID list in the 'data com-
munication' manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P18.02 ID Preset Value 2 Default: 352

Corresponds to P18.01 ID Preset Value 1

P18.03 ID Preset Value 3 Default: 384

Corresponds to P18.01 ID Preset Value 1

P18.04 ID Preset Value 4 Default: 594

Corresponds to P18.01 ID Preset Value 1

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 93 -
Parameters

P18.05 ID Preset Value 5 Default: 0

Corresponds to P18.01 ID Preset Value 1

P18.06 ID Preset Value 6 Default: 0

Corresponds to P18.01 ID Preset Value 1

P18.07 ID Preset Value 7 Default: 0

Corresponds to P18.01 ID Preset Value 1

P18.08 ID Preset Value 8 Default: 0

Corresponds to P18.01 ID Preset Value 1

P18.09 ID Read Value 1 Default: 752

Selecting the first value to be read from weighing electronics in the fieldbus telegram. The
number of the value (ID) can be found in the Data Communication manual:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P18.10 ID Read Value 2 Default: 784

As P18.09 ID Read Value 1

P18.11 ID Read Value 3 Default: 1552

As P18.09 ID Read Value 1

P18.12 ID Read Value 4 Default: 1872

As P18.09 ID Read Value 1

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 94 - Schenck Process Group
Parameters

P18.13 ID Read Value 5 Default: 1874

As P18.09 ID Read Value 1

P18.14 ID Read Value 6 Default: 1882

As P18.09 ID Read Value 1

P18.15 ID Read Value 7 Default: 1904

As P18.09 ID Read Value 1

P18.16 ID Read Value 8 Default: 1896

As P18.09 ID Read Value 1

13.3.2.19 Parameter Block 19 - Ethernet


The parameters in this group control the Ethernet ports. It is necessary to provide inputs when EasyServe, a
VHM operating element or a host computer is supposed to be connected via Ethernet.
You can find information on the selection of addresses in the BV-H2406 manual.

P19.01 IP Address Default: 192.168.240.1

IP address of the weighing electronics. If the control system is integrated into an Ethernet
network, the address must be chosen in agreement with the network administrator. In iso-
lated networks we recommend the factory setting 192.168.240.x. "x" allows for selection of
the system on the bus.

P19.02 Net Mask Default: 255.255.255.0

The net mask setting is based on the local network type.


In general the following setting is used: 255.255.255.0

See also: P19.02 Net Mask, system manual BV-H2406

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 95 -
Parameters

P19.03 Gateway Default: 0.0.0.0

Generally no input is required. Typical value: 0.0.0.0

13.3.2.20 Parameter Block 20 - Data Logging


The parameters in this group configure the recording of process data. The recorded data are available at the
operating panel and can be easily accessed via Ethernet on the controller homepage.

P20.01 Hourly Total Time Default: 0 min


Min: -1 min Max: 59 min
Moment at which the totalizing counter begins logging in minutes from the start of a full
hour.

P20.02 Daily Total Time Default: 0 min


Min: -1 min Max: 1439 min
Moment at which the totalizing counter begins logging in minutes from the start of a day.

P20.03 Logger cycle time Default: 1 min


Min: 1 min Max: 1439 min
Logging cycle time for the Data Log Values selected by P20.04 ... P20.13.

P20.04 Data Log Value 1 Default: 752

Select the process value for recording. You can find the identification number of a value in
the 'data communication' manual.

Also refer to:


P20.03 Logger cycle time
These manuals:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P20.05 Data Log Value 2 Default: 1872

Similar to P20.04 Data Log Value 1

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 96 - Schenck Process Group
Parameters

P20.06 Data Log Value 3 Default: 1874

Similar to P20.04 Data Log Value 1

P20.07 Data Log Value 4 Default: 1882

Similar to P20.04 Data Log Value 1

P20.08 Data Log Value 5 Default: 1894

Similar to P20.04 Data Log Value 1

P20.09 Data Log Value 6 Default: 1896

Similar to P20.04 Data Log Value 1

P20.10 Data Log Value 7 Default: 1898

Similar to P20.04 Data Log Value 1

P20.11 Data Log Value 8 Default: 0

Similar to P20.04 Data Log Value 1

P20.12 Data Log Value 9 Default: 0

Similar to P20.04 Data Log Value 1

P20.13 Data Log Value 10 Default: 0

Similar to P20.04 Data Log Value 1

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 97 -
Parameters

13.3.2.21 Parameter Block 21 - Configuration HMI Values


The parameters in this group define the process variables to be displayed on the 'Values' page of the oper-
ating panel (HMI, OP) for a DISOCONT Tersus.
On an INTECONT Tersus these values can be called up with the '9' key.

EasyServe can be used for easy configuration or the settings can be made with the help of the allocation
map in the data description of the serial interface in the operating panel.

You can find the characteristic values (ID) belonging to the process variables in the manual on data com-
munication:
DISOCONT Tersus: BV-H2448
INTECONT Tersus: BV-H2474
DISOCONT Tersus Software VCF2017x: BV-H2468

P21.01 HMI Value 01 Default: 2004

Identification number (ID) of the desired process variable.

P21.02 HMI Value 02 Default: 1882

Identification number (ID) of the desired process variable.

P21.03 HMI Value 03 Default: 1942

Identification number (ID) of the desired process variable.

P21.04 HMI Value 04 Default: 1874

Identification number (ID) of the desired process variable.

P21.05 HMI Value 05 Default: 0

Identification number (ID) of the desired process variable.

P21.06 HMI Value 06 Default: 0

Identification number (ID) of the desired process variable.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 98 - Schenck Process Group
Parameters

P21.07 HMI Value 07 Default: 0

Identification number (ID) of the desired process variable.

P21.08 HMI Value 08 Default: 0

Identification number (ID) of the desired process variable.

P21.09 HMI Value 09 Default: 0

Identification number (ID) of the desired process variable.

P21.10 HMI Value 10 Default: 0

Identification number (ID) of the desired process variable.

13.3.2.22 Parameter Block 22 - Flow Gate


The parameters of this group are only relevant if the prefeeder is designed as a position-regulated feed gate
for the bulk solids to the feeder scale.

P22.01 S: DO Open Flow Gate Default: n/a


Alternative: n/a
DO
Only relevant if # = "Stepping".

The definition of the output channels for opening the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).

P22.02 S: DO Close Flow Gate Default: n/a


Alternative: n/a
DO
Only relevant if # = "Stepping".

The definition of the output channel for closing the position-controlled prefeeder. With
DISOCONT Tersus the output should be on the main VCU (local bus address 1).

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 99 -
Parameters

P22.03 AI: Position Flow Gate Default: n/a


Alternative: n/a
AI
The definition of the input channel for the feedback signal for the position of the prefeeder.

Also refer to:


P22.04 AI: Offset
P22.05 AI: Range

P22.04 AI: Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The input current at the 'just closed' position of the feed gate.

P22.05 AI: Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The input current for the nominal position is 100 %. There should be a material flow of 100
% of the nominal operating range P02.02 Nominal Flow Rate at the nominal position under
nominal conditions for the bulk solids.

P22.06 AO: Position Flow Gate Default: n/a


Alternative: n/a
AO
The definition of the analog output channel with the information on the position of the pre-
feeder to external equipment. Norming via P22.07 AO: Offset and P22.08 AO: Range

P22.07 AO: Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output current for the 0 % prefeeder position is opened ('just closed').

P22.08 AO: Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output current for the 100 % prefeeder position is opened ('just completely closed').

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 100 - Schenck Process Group
Parameters

P22.09 Event: MIN Flow Gate Default: W2


Event Group: CO Number: 02

The event is identified when the prefeeder has run past the limit switch for the minimum
position. It is used to protect the mechanical equipment.

Possible causes:
Defects in the prefeeder control unit

Actions:
Check the control unit.

P22.10 Position MIN Flow Gate Default: n/a


Alternative: n/a
DI
The definition of the input channel for the signal from the limit switch on the prefeeder for
the minimum open position.

P22.11 Event: MAX Flow Gate Default: W2


Event Group: CO Number: 03

The event is identified when the prefeeder has run past the limit switch for the maximum
position. It is used to protect the mechanical equipment.

Possible causes:
Defects in the prefeeder control unit

Actions:
Check the control unit.

P22.12 Position MAX Flow Gate Default: n/a


Alternative: n/a
DI
The definition of the input channel for the signal of the limit switch on the prefeeder for the
maximum open position.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 101 -
Parameters

13.3.2.23 Parameter Block 23 - Additional device

P23.01 DO: Agitator ON Default: n/a


Alternative: n/a
DO
Defines the output channel used to switch on the agitator in the feeder hopper.

Also refer to: P23.02 START Agitator

P23.02 START Agitator Default: 0 % Io


Min: 0 % Io Max: 100 % Io
Threshold value at which the agitator is switched on. The agitator is switched on by P23.01
DO: Agitator ON 30 seconds after the setpoint has exceeded the threshold for a feeder in
an on-state. The agitator switches off with no delay when the feeder is switched off.

Reference: Flow Rate Units

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 102 - Schenck Process Group
Event messages

14 Event messages

DANGER
Events register abnormal states, e.g. malfunctions or exceeded thre-
shold values.
A running feeder can be a hazard to people or to property.
The cause of event messages must be corrected before events are ac-
knowledged!

Event messages are grouped together.


Group Identifier Event Domain

SY Internally monitoring the control system


SC Irregularities in operator control or peripheral control
WE Fault in the external power electronics
WM Fault in the mechanical system
MF Fault in the bulk material flow
IL Messages from interlocking with system control
CO Internal controller malfunction message
CA Adjustment fault
HI Threshold value exceeded upwards
LO Threshold value exceeded downwards
Tab. 4 : Event groups

Note:
In the following list, parameters related to the indicated event are shown in parentheses.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 103 -
Events

15 Events

15.1 Events Details

15.1.1 Event Group: Calibration


CA01 Event: Error LC Input (P11.03)
The load cell cable is improperly connected, not connected or has been interrupted.
The load cell may be faulty.

Measures:
- check the cabling and the load cell
- check the load cell

Note:
The power supply must be switched off and on again if the scales cannot be switch-
ed on even after the error has been rectified.

CA05 Event: Linearization Error (P13.10)


Not a monotonically increasing curve.

A monotonically increasing compensation curve is monitored when:


- linearization is switched on,
- a parameter is altered

CA06 Event: Tare Correction (P08.04)


The tare value calculated by the automatic zeroing system is in excess of
P08.03 Zeroing Limit.
The value is not accepted.

CA12 Event: Tare Difference > MAX (P08.06)


P08.05 Zero Set Difference is past.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 105 -
Events

15.1.2 Event Group: Controller


CO01 Event: Controller Limited (P12.09)
The Controller Magnitude of the feed rate regulator has reached the upper response
threshold. After a time message HI05 (P12.07) will be output.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.

Step to take: check the material discharge and the Controller Magnitude (service
value Y). At Nominal Flow Rate Y should be between about 10...14 mA.

CO02 Event: MIN Flow Gate (P22.09)


The event is identified when the prefeeder has run past the limit switch for the mini-
mum position. It is used to protect the mechanical equipment.

Possible causes:
Defects in the prefeeder control unit

Actions:
Check the control unit.

CO03 Event: MAX Flow Gate (P22.11)


The event is identified when the prefeeder has run past the limit switch for the maxi-
mum position. It is used to protect the mechanical equipment.

Possible causes:
Defects in the prefeeder control unit

Actions:
Check the control unit.

15.1.3 Event Group: Electrical System


WE01 Event: Power Failure (P11.01)
This event is identified once the power supply is restored.

The scales will not switch on automatically, regardless of the event class. The event
must first be acknowledged and the command to start given again before the scales
will restart.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 106 - Schenck Process Group
Events

15.1.4 Event Group: Interlock


IL01 Event: Run Disabled (P11.04)
No release signal from the source determined by P14.01 Source Run Enable.

If this event is pending then the downstream transport equipment is most likely not
switched on.

15.1.5 Event Group: Material Flow


MF06 Event: Out of Tolerance (P09.05)
The batch result is outside the tolerance range.

Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces

15.1.6
15.1.6 Event Group: MAX
HI01 Event: LC Input > MAX (P11.05)
The load acting on the load cell is greater than 110 % of the sum of the nominal
loads of the load cells.

Measuring range end:


125 % for load cells with 2.85 mV/V
175 % for load cells with 2 mV/V

Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell

HI02 Event: Actual Flow Rate MAX (P06.04)


Actual feed rate higher than the maximum value set in P06.03 Limit: Actual Flow
Rate MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too large

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 107 -
Events

HI05 Event: Deviation (P12.07)


Maximum Deviation exceeded. The actual feed rate has deviated to far from the
setpoint over too long a period of time.

Possible causes:
- material has been incorrectly handled:
- the bulk material is flowing irregularly or cannot be discharged satisfactorily
- arching in the feed hopper
- there is a backup on the discharge side
- a large quantity of material continues to trickle from the feeder

- the controller has at times come against its limits


- error in the electronics
- check the cable to the external output regulator and to the motor. Check the output
regulator settings (current limiting, speed range)

- calibration error: during initial calibration the regulator was set at such a critical
value that minor changes in the overall properties of the system lead to unreliable
operation.

Also refer to: P12.08 Deviation abs. max., P12.06 Factor Deviation, P12.05 Thre-
shold Deviation, P12.04 Time Deviation

15.1.7 Event Group: MIN


LO01 Event: LC Input < MIN (P11.06)
The load cell load is less than 3 % of the sum of the load cell nominal loads.

Possible causes:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell

LO02 Event: Actual Flow Rate MIN (P06.02)


The actual feed rate is lower than the minimum value P06.01 Limit: Actual Flow Rate
MIN.

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too low

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 108 - Schenck Process Group
Events

15.1.8 Event Group: Sequence Monitoring


SC01 Event: Setpoint Limited (P11.08)
Cause of the event:
Depending on the respective mode of operation:
a) The setpoint is limited to P02.02 Nominal Flow Rate in gravimetric operation.
b) The setpoint is limited to three times the value of P02.02 Nominal Flow Rate in
volumetric operation.

SC02 Event: Stand-By (P06.06)


Scales are in standby operation, i.e. the controller magnitude to the feed drive is
smaller than the threshold value set in P06.05 Stand-By Limit Value. The feeder
drive is switched off. The 'running' state will still be displayed.

This function protects the motor from overheating at very low speeds or when idling.

Actions:
Key in the larger setpoint and check P06.05 Stand-By Limit Value.

SC03 Event: Maint.Feeder Run (P10.04)


The sum of the runtimes of the conveying elements is greater than the time P10.03
Maintenance Feeder Run.

A message occurs after each expired time interval. The message may indicate ser-
vice work required.

SC04 Event: Maint. Electric (P10.02)


The sum of the times during which the mains voltage is on is greater than the time
P10.01 Maintenance Electric.

A message occurs after each expired time interval. The message may indicate ser-
vice work required.

SC05 Event: External Event 1 (P11.09)


External interference signal at fault input 1.

Possible cause: depends on the external cabling. Usually: an error in the main drive

SC06 Event: External Event 2 (P11.10)


External interference signal at fault input 2.

Possible cause: depends on the external cabling.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 109 -
Events

15.1.9 Event Group: System Message


SY01 Event: Memory (P11.02)
The program and parameters memory are checked cyclically. An error has occurred
during that. The scales will no longer function correctly.

Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.

SY08 Event: Cyclic Communication (P17.03)


Cyclical serial communication with the higher-order plant control system has been
interrupted for longer than the timeout-period in P17.02.

To rectify: check cable connections.

SY09 Event: License Violation (P11.11)

SY10 Event: Acyclic Communication (P17.04)


Incorrect data in the noncyclical communication from the host computer.

Possible cause: poor programming of the host computer

SY14 Event: Simulation active (P11.07)


Simulation operation is on.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 110 - Schenck Process Group
Hardware and technical data

16 Hardware and technical data

16.1 Technical Data and Replacement Parts

Display LCD graphic display with adjustable brightness


Keyboard 22 buttons
Supply voltage 24 VDC +50 % / -25 %, max. 20 VA
Temperature range Operating temperature: -40 °C … +60 °C
Bearing temperature: -40 °C … +80 °C
Legal for trade operation: -10 °C … +40 °C
Electromagnetic ambient E2 (OIML D11)
conditions
Scales connection Power supply: 6 V alternating voltage
Load cell impedance: R min 80 Ω
Length of cable: max. 1000 m
The housing Built-in IP54 control panel case with optional retainers for IP65
Binary inputs 5 optocouplers 18 … 36 VDC, model 5 mA
1 NAMUR, and 1 NAMUR/voltage 0.04 … 3,000 Hz
Binary outputs 8 relays, max. 230 V, 8 A ohm. / 1 A inductive
Impulse output 1 optocoupler for totalizing counter 24 V, 0.1 A, max. 10 Hz
Analog outputs 2 x 0(4) ... 20 mA, load max. 500 Ω, galvanically separated
Analog input Current 0(4) ... 20 mA or voltage 0 ... 10 V, input impedance 100 Ω, galvanically
isolated
Serial interfaces Interface 1: EasyServe
Interface 2: Printer
Interface 3: Large-scale display
VNT0650 power supply 85 ... 264 VAC / 24 VDC, 1.1 A
Internal (optional)
Fieldbus (optional) Can be selected from: Modbus, PROFIBUS DP, DeviceNet, Ethernet/IP
Analog signal card 2 analog outputs 0(4) ... 20 mA, load max. 500 Ω,
(optional) VEA 20451 galvanically separated, joint potential reference
2 analog inputs 0(4) ... 20 mA or 0 ... 10 V voltage, input impedance 100 Ω,
galvanically separated, joint potential reference

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 111 -
Hardware and technical data

Wall-Mounted Housing IP65 wall-mounted housing, 380 mm x 300 mm x 236 mm


Power supply 85 ... 264 VAC / 24 VDC, 2 A
Power supply, external, desk-top 85 ... 264 VAC / 24 VDC, 1.25 A
model
Event printer Printer with RS232 serial interface and system cable
Large-scale displays Can be selected from: VLD 20100 (LED, 100 mm);
VLZ 20045 (LCD, 45 mm); VLZ 20100 (LCD, 100 mm)
Control cubicles and Control cubicles and equipment frames for several
equipment frames INTECONT Tersus units with or without feed

Description Model Material Nummer


Front-of-panel unit with VWF 20650 software for the weighfeeder VEG 20650
Basic equipment V082001.B01
with Modbus option V082001.B02
with PROFIBUS option V082001.B03
with DeviceNet option V082001.B04
with Ethernet/IP option V082001.B05

Front-of-panel unit with VBW 20650 software for the belt weigher VEG 20650
Basic equipment V082002.B01
with Modbus option V082002.B02
with PROFIBUS option V082002.B03
with DeviceNet option V082002.B04
with Ethernet/IP option V082002.B05

Front-of-panel unit with VLW 20650 software for the loss-in-weight feeder VEG 20650
Basic equipment V082003.B01
with Modbus option V082003.B02
with PROFIBUS option V082003.B03
with DeviceNet option V082003.B04
with Ethernet/IP option V082003.B05

Front-of-panel unit with VMC 20650 software for MULTICOR VEG 20650
Basic equipment V082004.B01
with Modbus option V082004.B02
with PROFIBUS option V082004.B03
with DeviceNet option V082004.B04
with Ethernet/IP option V082004.B05

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 112 - Schenck Process Group
Hardware and technical data

Front-of-panel unit with VIF 20650 software for MULTISTREAM VEG 20650
Basic equipment V082005.B01
with Modbus option V082005.B02
with PROFIBUS option V082005.B03
with DeviceNet option V082005.B04
with Ethernet/IP option V082005.B05

Front-of-panel unit with VBW 20660 software for legal-for-trade belt weigh- VEG 20650
er
Basic equipment V082007.B01
with Modbus option V082007.B02
with PROFIBUS option V082007.B03
with DeviceNet option V082007.B04
with Ethernet/IP option V082007.B05

Modbus VSS 28020 V081902.B01


PROFIBUS VPB 28020 V081901.B01
DeviceNet VCB 28020 V081903.B01
Ethernet/IP clearance VET 20700 V040035.B01

Further Options
Installed power supply and mounting set V082050.B01
Analog signal card with 2 analog inputs and 2 analog outputs VEA 20451 V054098.B01
IP65 protection type for front-side control panel installation V082039.B01

Software
EasyServe VPC 20150 E144541.01

Large-scale displays
Large-scale 5-digit display, LED, 100 mm digit height VLD 20100 V090252.B01
Large-scale 6-digit display, LCD, 45 mm digit height VLZ 20045 V067304.B01
Large-scale 5-digit display, LCD, 100 mm digit height VLZ 20100 V066611.B01

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 113 -
Hardware and technical data

16.2 Connection Diagrams

Fig. 10: Connection diagram for voltage supply

Fig. 11: LC connection diagram and tachometer

Fig. 12: Connection diagram for inputs and outputs 1

Fig. 13: Connection diagram for inputs and outputs 2

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 114 - Schenck Process Group
Hardware and technical data

Fig. 14: Serial interface connection diagram

Fig. 15: Modbus connection diagram

Fig. 16: PROFIBUS connection diagram

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 115 -
Hardware and technical data

Fig. 17: DeviceNet connection diagram

16.3 Replacing INTECONT PLUS with INTECONT Tersus


Tersus
In the beginning, INTECONT PLUS equipment was produced as the FIP model and then as the VEG 206xx
model starting in 2003.
INTECONT Tersus as the follow-up unit was also kept very similar to its predecessors in terms of its hard-
ware connections.
The EasyServe adjustment program (VPC 20150) can be used for INTECONT Tersus from version 19
which makes it possible to conveniently change over from VEG to INTECONT Tersus.
The following tables show the connector pin assignment of FIP, VEG and INTECONT Tersus opposite one
another for all physical signals.

Power Supply
Signal FIP and
VEG and
INTECONT Tersus

0V X2 1
24 V in X2 2

0V X2 3
24 V out X2 4

Load cell
Signal FIP VEG INTECONT Tersus

OUT1 X5 3 X7 3 X10 3
REF1 X5 4 X7 4 X10 4
IN2 X5 5 X7 6 X10 6
IN1 X5 6 X7 5 X10 5
REF2 X5 7 X7 7 X10 7
OUT2 X5 8 X7 8 X10 8

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 116 - Schenck Process Group
Hardware and technical data

Digital Outputs, DO
Signal FIP VEG INTECONT Tersus

DO1 X1 1,2
DO2 X1 3,4
DO3 X1 5,6
DO4 X6 1,2 X8 1,2 X13 9,10
DO5 X6 3,4 X8 3,4 X13 7,8
DO6 X6 5,6 X8 5,6 X13 5,6
DO7 X6 7,8 X8 7,8 X13 3,4
DO8 X6 9,10 X8 9,10 X13 1,2

Digital Inputs, DI
Signal FIP VEG INTECONT Tersus

DI1 X3 1,2 X3 1,2 X4 1,2


DI2 X9 1,2 X3 3,4 X4 3,4
DI3 X9 3,4 X6 6,7 X4 5,6
DI4 X9 1,2
DI5 X9 3,4
Namur sensor DI6 X3 5,6 DI6 X3 5,6 DI4-N X9 1,2 Namur
Namur tachometer 1 DI7 X5 1,2 X7 1,2 DI5-N X10 1,2
Open collector tachometer —- —- DI5-T X9 3,4
1 DI6 X12 3,4
DI7 X12 1,2
X3 3,4
Vol. Synchronous

Analog outputs AO
Signal FIP VEG INTECONT Tersus

A01 X9 9,10 X6 4,5 X8 4,5


A02 X9 11,12 X9 5,6 X12 8,9

AO3 —- —- Optional VEA X30


AO4 —- —- Optional VEA X30

Analog inputs AI
Signal FIP VEG INTECONT Tersus

AI1 X11 1,2,3 X6 1,2,3 X8 1,2,3

AI2 —- —- Optional VEA X30


AI3 —- —- Optional VEA X30

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 117 -
Hardware and technical data

Printer
Signal FIP VEG INTECONT Tersus

Shield X8 1 X10 1 X7 1
TX X8 2 X10 2 X7 2
RX X8 3 X10 3 X7 3

Large-scale display
Signal FIP VEG INTECONT Tersus

Shield —- —- X11
TX —- —- Pin assignment
RX —- —- after RSxxx selec-
tion

EasyServe
Signal FIP VEG INTECONT
Tersus

Shield —- X4 5 or X5 1 X6 1
TX —- X4 2 or X5 2 X6 2
RX —- X4 3 or X5 3 X6 3

Pulse output
Signal FIP VEG INTECONT Tersus

24 V X9 5 X6 8 —-
Open collector X9 6 X6 9 X3 1
Open Emitter X9 7 X6 10 —-
0V X9 8 X6 11 X3 2

Fieldbus connection (Modbus, PROFIBUS and DeviceNet)


Signal FIP VEG INTECONT Tersus

Separate field- —- X20 X20


bus card

Modbus is connected to X7 with FIP

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 118 - Schenck Process Group
Hardware and technical data

16.4 PROFIBUS Module (VPB8020)


The module may be attached to the base card of the device to make an interface with the PROFIBUS.
Module properties

Isolation: Optocoupler
Power supply: +5 VDC internal
Electricity supply: max. 310 mA
Connector to bus activation: XP1: D-Sub 9-pole
XP3: Terminal 5-pole

Arrangement of the components

Fig. 18: VPB8020 PROFIBUS module layout

Settings

W100 Determining the power supply:


The platform W100 always remains in position 2 - 3
W150 Bus termination:
The bus termination resistances must be activated at the first and last station of the bus. This is
W151 done by setting all three jumpers on the board (W150, W151, W152) to position 1 - 2. By default
W152 the resistances are not activated (position 2 - 3).

Bus address:
The addresses are set using parameters.

Pin XP1 XP3


Signal Signal
*)
1 - B, RxD/TxD-P
**)
2 - A, RxD/TxD-N
*) ***)
3 B, RxD/TxD-P DGND (0 V)
***)
4 CNTR-P (Control-P) VP (+5 V)
***)
5 DGND (0 V) SHIELD
***)
6 VP (+5 V) -
7 - -

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 119 -
Hardware and technical data

Pin XP1 XP3


Signal Signal
**)
8 A, RxD/TxD-N -
9 - -
The SHIELD -
housing
Tab. 5 : 'Bus activation' connector
*)
Wire color red
**)
Wire color green
***)
Bus termination supply

LEDs H110, H120


There is one identical-function double-LED (H110, H120) for each connection to the bus activation
(XP1, XP3).
Example H110:

Fig. 19: Light-emitting diodes – VPB8020 front view

Status Display

Off Not online/no power supply


Green Online, data transfer
Green, flashing Online, clear mode
Red, flashing (1 Hz) Parameterization fault
Red, blinking (2 Hz) Configuration error
Tab. 6 : LED 'Operating Mode' (below)

Status Display

Off No power supply or not initialized


Green Initialized
Green, flashing Initialized, result of diagnostic test pending
Red Exception error
Tab. 7 : LED 'Status' (above)

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 120 - Schenck Process Group
Hardware and technical data

16.5 DeviceNet Module (VCB8020)


The module can be attached to the mainboard to create an interface to the DeviceNet.
Module properties

Galvanic isolation Optocoupler


Power Supply +5 VDC internal
Power supply max. 250 mA
Plug connector to the bus activation XC1: Terminal 5-pole
XC3: Terminal 5-pole

Arrangement of the components

Fig. 20: VCB8020 DeviceNet module layout

Settings

W100 Determining the power supply:


The platform W100 always remains in position 2 - 3
W160 Bus termination:
The bus termination resistances must be activated at the first and last station of the bus. This is
done by applying the W160 jumper to the position 1 - 2.
By default the resistances are not activated (position 2 - 3).
Bus address and Baud rate:
Both values are set using parameters.

Pin XC1 XC3


Signal Signal
1 V-
2 CAN_L
Ditto:
3 Shielding
4 CAN_H
5 V+
Tab. 8 : 'Bus activation' connector

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 121 -
Hardware and technical data

LEDs H110, H120


There is one identical-function double-LED (H110, H120) for each connection to the bus activation (XC1,
XC3).
Example H110:

Fig. 21: VCB8020:XC1 DeviceNet module front view

Network status Display

Off Not online/no power supply


Green Online, one or more connections established
Green, flashing Online, no connection
Red Critical connection error
Red, flashing (1 Hz) One or more connections have been timed out
Alternating red-green Self-test
Tab. 9 : LED 'Network Status' (above)

Module status Display

Off No power supply


Green Exchange of user data
Green, flashing Incorrect configuration
Red Non-repairable error
Red, flashing Repairable error
Alternating red-green Self-test
Tab. 10 : LED 'Module Status' (below)

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 122 - Schenck Process Group
Hardware and technical data

16.6 Modbus Interface VSS8020


The interface card is an isolated, serial interface. The type of the interface is set using control unit parame-
ters and using jumpers in the plug. Both plugs are electrically parallel.
Module properties

Galvanic isolation Optocoupler


Power Supply +5 VDC internal
Power supply Max. 250 mA
Plug connector to the bus activation XS2: Terminal 7-pole
XS3: Terminal 7-pole
Tab. 11 : Modbus module properties

Arrangement of the components

Fig. 22: VSS8020 Modbus module layout drawing

Serial interfaces pin assignment


Pin RS232 RS422 RS485

1 GND GND GND


2 TX Tx B RTx B
3 RX Rx B Jumper to pin 2
4 Rx A Jumper to pin 5
5 Tx A RTx A
6 Jumper to pin 4 for bus termination
7 Jumper to pin 3 for bus termination
Tab. 12 : Modbus serial interface pin assignment

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 123 -
Hardware and technical data

16.7 LED diagnosis


Status LED Color Function

LNK Green Ethernet is connected


FDX Yellow Full Duplex
100 Red 100 MBaud (otherwise 10 MBaud)
ADR Green Measuring hardware is active
IDL Yellow The processor's idling time, flashes during operation
DIA Red Unused
PWR Green Power OK
SYC Yellow System cycle, flashes during operation
ERR Red Fault display, set by the system software

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 124 - Schenck Process Group
Web server functions

17 Web server functions

17.1 Web Server


The unit is equipped with a web server that provides a homepage for the scale. This homepage is available
in English only.
Conditions:
▪ The PC has an Ethernet link to the device.

Establishing a connection:
▪ Enter into the address bar of the browser the IP address of the control unit.

Various data from the controller can be called up in the left-hand navigation bar.
Navigation entry Function

HMI Display actual values in two variants and three sizes.


Events Most recent stored events (alarms, warnings, etc.)
Parameter changes Most recent parameter alterations
Command log Logs a list of certain commands, e.g. start/stop
Totalizer hourly Table of hourly-saved totalizing integrators/counters.
The minute after the full hour at which the saving occurs can be set in P20.01.
Totalizer daily Table of daily-saved totalizing integrators/counters
The time of saving from 00:00 h is set in P20.02.
Totalizer Table of totalizing integrators/counters saved on the command
Data logger 1 / 2 Table of the measured values recorded. The sampling interval can be set using
P20.03. Up to 10 process variables can be recorded; these can be selected using
P20.04 - P20.13. Recording can be activated in the operating field 'Mode'.
Tab. 13 : Function calls on the controller website

Memory depth is approx. 1,000 entries. All entries are recorded with the entry time. The table is refreshed
only when it is called up. The values can be exported into a PC file for analysis with standard programs us-
ing select-copy-paste.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 125 -
Web server functions

The event display is highlighted by a colored rectangle. There are 3 colors, each of which has a different
meaning.

There is no event. Green display

An event class WARNING 1 or WARNING 2 is pending. Opera- Yellow display


tion may be affected.

There is an ALARM class event pending. No operation currently Red display


possible.

17.2
17.2 System Information
The system data are provided here. You can find files such as the software version, hardware version, IP
address. "Serial No." or "MAC-ID" are the names of the serial number on the CPU board.
Together with the 'mainboard' data, this data also supplies the user with the 'fieldbus' configurations and
settings. In particular the amount of bytes for the read and transmitted data.
This page is still undergoing development and may differ from the image shown here.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 126 - Schenck Process Group
Appendix

18 Appendix

18.1 Service Values


Detailed information on the system is contained in the service table. The call-up does not interfere with any
weigh functions.

Call up the function block

Setup
Service Values

Scroll through the service values

Exit the service values

Setup
Standard Values

Readouts:

Vxx 2065y-yyy Software version

2011-08-01 08:01:58 Date and time


VOL OP Operating mode when active
(VOL = volumetric, OP = keyboard mode)
DO = 1 1 1 0 0 0 0 0 Relay Outputs Switching State "1" = Contact closed
"0" = Contact open
DI = 1 1 1 1 - 0 1 Inputs Switching State "1" = Contact closed
"0" = Contact open

additional for Namur signals "+" Short circuit


"-" Cable breakage
"1" = Sensor covered
"0" = Sensor clear
Additional for legal for trade "1" = Calibration switch active
belt weighers "0" = Calibration switch inactive
Analog Output 1 4.15 mA Output current of the analog output 1
Time Voltage ON: 22 h Duty cycle of power supply
Monitoring: parameters P10.01

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 127 -
Appendix

Time Feeder ON: 19 h Duty cycle of scales and belt conveyor.


Monitoring: parameters P10.03
Tachometer 1 96.655 Hz velocity sensor input frequency.
The frequency must be within the range 0.04 ... 3000 Hz.
Utilization LC 30.988 % Load on load cells sourced from the sum of the load cell nominal ca-
pacities.
The weigh cells are overloaded if the values exceed 100 %.
The message H4: LC Input > MAX occurs upwards of 110 %.
Loadcell 1 0.383257 mV/V Non-standardized output value of the weigh cell amplifier (gross).
The value is recorded before the belt influence compensation function
and before the delay at the dispatch point.
CSUM: Flash 1 Check sum of the scale software
CSUM: Flash calc. 1 Check sum of scales software. recalculated
Controller Magnitude 1.44 mA Controller output as specification for the drive
Actual Tare 27.000 kg/m Currently stored tare value
Temperature 22.5 °C Current temperature in the equipment
Deviation abs. 0.03 % Current value of the controller deviation
Ethernet/IP: OK OK if Ethernet/IP option is cleared; otherwise NO

The values listed are exemplary.

18.2 Set option


There is the option of clearing fieldbus coupling Ethernet/IP by software. This unit issues an unambiguous
ID (the MAC address). An activation code is generated from this ID that is then keyed into the unit. If the
optional activation is required on devices which have already been delivered, the data is transferred to the
Schenck process, and the generated activation code is reported back.
The Option activate function is only accessible when the fieldbus protocol is on NO or Ethernet/IP.

Call up the function block

Parameter
Option activate

Key in password


Abort possible at any time

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 128 - Schenck Process Group
Appendix

The MAC-ID (example: 00:15:84:01:03:ee) and selected option


(example:Ethernet/IP) are shown.

If there is no clearance, memorize the value and report to Schenck Process.


Code: Key in the clearance code from Schenck Process
Ethernet/IP Message after input of a valid activation code or error message
and abort

18.3 Test Connector

A basic function control of the INTECONT can be carried out using a simple test connector. In this way an
error can be limited between the load cell with wiring and electrical equipment.
1. Connect the connector as shown in the diagram
2. Disconnect load cell connector X7 and plug in the test connector instead

The dimensioned resistances given result in the following service values:


1. Load cell signal (lc) approx.1.1 mV/V
2. Load cell usage factor (aw) approx. 55 % if C03 = 2 mV/V and approx. 39 % if C03 = 2.85 mV/V
If lc is in the listed areas, the pick-up input is free of errors.

Note:
With other resistances R1 and R2, the LC Raw is calculated to 500 * R2 / R1 [mV/V].
The test plug is available as an accessory.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 129 -
Appendix

18.4 Sources of setpoints and switch signals


Setpoint can be set and feed on and off commands can come from different sources.

kg/h Pe kg/h P

SETPOINT

1s
ANALOG A
D GRA : I0
VOL : 3xF0
SERIAL S
CONTROLLER
KEYBOARD
(EasyServe) T
P02.04
P02.09

Tr
1 KEYBOARD
Pr 1/100 MODE
%
START/STOP CONTROLLER
CONTROL MAGNITUDE Y
P02.03 ZERO
SERIAL S
FEEDER RUNNING
&
KEYBOARD T ST

CONTACT K START PREFEEDER

RELEASE ALARM
STAND-BY

Fig. 23: The setting value and turn-on sources

The sources are preselected with parameters in the 'Control Sources' group.
You can use the Keyboard mode function to change over between the preselected sources and the
keyboard (Keyboard Mode ON/OFF).
Parameters Function Field

P02.03 Switch-on source Keyboard (OP)


Serial (FB)
Contact (DI)
P02.04 Setpoint source Keyboard (OP)
Serial (FB)
Analog input (AI)
P02.09 Relative Setpoint Switched off (NO)
Evaluation via keyboard
(YES)

The effective setpoint is displayed on the operating panel. The setpoint input field is only available if the
inputs from the operating panel are allowed by parameter.
A new window for entering the relative component will open when the setpoint field is touched if the relative
setpoint qualifier was pre-selected with the operating panel.
Setpoint Synchronization:
The external setpoint will be taken if the source of the setpoint is switched from an external source to the
keyboard (OP). The external source has its effect in the opposite direction.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 130 - Schenck Process Group
Appendix

On/Off Synchronization:
The on/off switch status is retained when switching from an external source to the keyboard (OP). The
external source has its effect in the opposite direction.
Mains Power Off:
The keyboard setpoints are stored.

Fig. 24: VWF switch-on sequence

Time Condition

1 Feeding does not begin with the on command since the all-clear signal has not been given.
2 To start, the scale requires the rising slope of a start command.
3 Feeding is started with the rising slope.
4 Feed rate control will operate in volumetric mode during the startup time defined in P12.14 (also refer to:
Volumetric / (Volumetric Synchronous) / Gravimetric Modes of Regulator Operation).
5 Changing over in normal gravimetrically controlled feeding operation (assuming gravimetric mode was pre-
viously selected). Control stays in volumetric mode (assuming it was previously selected by the operator).
6 Feeding will be switched off if there is no all-clear signal (or if the switch on command was removed).
7 The feed rate will continue being calculated for the time set in P07.05 in order to capture the last trickling
material. Calculation will then stop; the counter will retain the value previously reached even if the fill level in
the hopper changes.
Tab. 14 : The states and points in time in the flow chart

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 131 -
Appendix

Parameters Function

P12.14 Duration of volumetric startup time


P07.05 Duration of continuing feed rate calculation once feeding has been switched off (stopping
time counter)
P02.03 Source of the on signal
P14.01 Source of the all-clear signal
P15.03 Scale signal output switched on
Tab. 15 : Relevant parameters

What to do if there is an alarm:


The feeder drive is switched off immediately if an alarm is triggered. The feed rate will continue being calcu-
lated for the time set in P07.05.
Measurement and displays:
The platform load will always be calculated and displayed. The feed rate will only be calculated with the
feeder switched on and during the stopping time (P07.05).

18.5 Measuring the flow rate

Fig. 25: A simplified signal flow diagram

LC Load cell D Rotation point

Q The load on the load cell CW Calibration Weight

a The distance between the 'calibration weight' b The distance between the 'force application
and the 'fulcrum' load cell and the fulcrum'

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 132 - Schenck Process Group
Appendix

Ua The load cell output voltage aw [%] The load cell utilization in % of its rated ca-
pacity

Qm The measured load in kg Iu [kg/h] The measured flow rate in kg/h before linea-
rization and correction

LIN Lineariser I [kg/h] The measured flow rate

Q [kg] The measured load on the load cell CWT The CW: Span Calibration calibration pro-
gram

Parameter Name Meaning

P03.01 LC Characteristic Value The transmission factor of the load cell according
to the data sheet
P03.03 LC Rated Capacity The total of the rated capacities of the load cells
used according to the data sheet
P03.02 Device Constant The transmission factor of the mass flow → force
according to the data sheet
P04.01 Weight Correction Optional correction factor after a calibration
weight check
P04.03 Basic Tare Tare as the result of the TW: Tare calibration
program
P04.04 Tare Correction The zero setting results of the >0< Zero Set cali-
bration program
P03.04 Calibration Weight Effective calibration weight
P04.05 Material Correction Correction via material control or automatic con-
trol
Tab. 16 : Relevant parameters

18.6 Flow
Flow rate regulation
A flow rate controller is only available when P01.05 is set to YES.
The flow rate is controlled via volumetric discharge performance of the feeder before the measuring unit.
The machine adjusts this performance so that the measured mass flow corresponds to setting feed rate
value.
Different types of feeder are used. Two different controller models are available for this. The controller
model is selected via P12.01.
The control- P12.01 Controller magni- The feeder model
ler model tude

Constant Continuous 0 (4) ... 20 mA A continuously rotating feeder such as a helix or starwheel, …
controller The feed gate with built-in pneumatic or electric position control
The parameter has no effect in the Flow Gate block
Step control- Stepping OPEN and CLOSE The feed gate driven by a motor with position feedback
ler contacts The parameters in the Flow Gate block configure the characteris-
tics
Tab. 17 : Controller models and how they are used

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 133 -
Appendix

18.6.1 Constant controller


The following figure shows a simplified schematic diagram of the control circuit for operating a mass flow
feeder.

Fig. 26: A simplified signal flow diagram

PF Volumetric feeder Q [kg/h] The measured load on the load cell

I [kg/h] Actual flow rate P [kg/h] Flow rate setpoint

Xd [%] The deviation in percent of the nominal Event Event identification


flow rate (P02.02)

OFF Behavior when feeding is switched off K The value of the VHM input keyboard

V The value from serial fieldbus coupling A The value from the analog input

VOL Volumetric/gravimetric operational mode Measure Refer to Measuring the flow rate (measure) for
switch signal processing

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 134 - Schenck Process Group
Appendix

Parameter Name Meaning

P02.02 Nominal Flow Rate The nominal flow rate from the data sheet
P02.04 Feedrate Setpoint Select the input cable for the setpoint flow rate
P12.14 Volumetric Start-Up The duration of start-up operations after feeding has been
switched on
P07.04 LC Filter The filter for the load cell signal
P12.02 P-Component KP The proportion of the PI controller
P12.03 I-Component TN PI controller readjusting time
P12.10 Lower Limit The lower limit of the controller magnitude
P12.11 Upper Limit The upper limit of controller magnitude dependant on the set-
point (see below for details)
P12.12 Controller Magnitude Offset Raising the controller magnitude
P12.13 Position at STOP The definition of the behavior of the controller magnitude when
feeding is switched off
P12.19 Bypass The setpoint-bypass constant
P12.18 Store The definition of the integral component's behavior when feed-
ing is switched off
P12.20 Setpoint Filter 1st Ord The time constant of the 1st setpoint filter
P12.21 Setpoint Filter 2nd Ord The time constant of the 2nd setpoint filter
P12.27 Compensation Element Compensation for avoiding contouring errors
P12.22 KP Adaptation Controlling velocity depending upon the setpoint
P12.23 Setpoint Threshold The setpoint threshold below which the P12.22 is effective
Tab. 18 : Relevant parameters

PI controller with bypass details


The central control unit consists of a PI controller for the flow rate of the model

The standard PI controller is also equipped with a setpoint bypass (P12.19). The bypass quickly carries out
setpoint jumps even if the controller is set slowly. Beyond this, the bypass allows controlled (volumetric)
operation.
To prevent overshoot, the setpoint is decoupled from the actual controller through a reconstruction of the
controlled member (P12.20 and P12.21). The controller is also equipped with controller magnitude limitation
(P12.10 and P12.11) dependant upon the setpoint. The controller is stopped and an event is identified
(message) when reaching the lower or upper controller magnitude limit.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 135 -
Appendix

The relationship between the controller parameters and the actuating variable is shown schematically in the
following diagram.

Parameter Special case


value

KP = 0 I-controller: TN is the reciprocal value of the integration constants,


i.e., the larger value = the slower controller KI = 1/TN in % / (mA/s)
TN = 0 P-controller: I-portion will be deleted
KP=TN=0 Controller output = controller increase
Tab. 19 : Special cases for KP and TN parameters

Parameters Effect
P12.14 The duration of volumetric start-up operation once the scale has been switched on in
Volumetric Start-Up seconds

P12.18 NO: The I-proportion is not stored when switching off


Store YES: The I-proportion is stored when switched off and has an impact when starting up
YES-A: The I-proportion is stored when switched off and has an impact when starting
up when feeding is not switched off by an alarm.
P12.19 One value is superimposed additively on the actuating variable, proportionally to the
Bypass preset setpoint. This parameter gives the bypass value for the nominal setpoint.

P12.20 The filters delay the setpoint for the controller while the bypass comes to the controller
Setpoint Filter 1st Ord magnitude output without a delay.
This has the purpose of approximately adjusting the time characteristics of the con-
P12.21 trolled member to prevent the actual value from overshooting on setpoint jumps.
Setpoint Filter 2nd Ord
P12.27 This additional constant integral member in the control deviation branch can have the
Compensation Element following favorable effects:
Contouring errors brought about by monotonous variable malfunctions (such as control
measurement equipment).
Constant control deviations with actuators with a non-symmetric effect.
The compensation element only has an impact in gravimetric operation and
P12.27 parameters ≠ zero. The input and output are limited to ± 5 %.
P12.22 This parameter can be used to evaluate the proportional component of the controller
KP Adaptation depending upon the flow rate set value.
KP Adaptation = 1 : KP is independent on the setpoint
KP Adaptation = 0 : KP decreases in proportion to the setpoint
KP Adaptation = 2 : KP increases in proportion to the setpoint
P12.23 The upper limit for evaluating the control deviation by the setpoint as per P12.22
Setpoint Threshold
Tab. 20 : Set-up notes for parameters in the constant controller

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 136 - Schenck Process Group
Appendix

Condition Characteristics

Change in the parameter The I component is not converted when parameters are changed which means that
values there might be jumps in the controller magnitude Y. If these jumps cannot be tolerated,
there should only be major changes in the (P12.19) bypass when feeding is switched
off.
Network connection The stored values in the I component and in the filters are set to zero.
Switch off feeding Stored components of the setpoint filter are set to zero. The value of the I component
is determined by P12.18.
Starting up feeding The feeder is switched on when all conditions are met.
The controller magnitude is set to the value of the setpoint bypass. The rise in P12.12
and the stored I component of the controller overlap one another consecutively as per
P12.18.
The setpoint filter starts working simultaneously from zero.
The flow rate controller works according to P12.14 in volumetric operation during the
start-up period. After the start-up period, the controller ts released and gravimetric
operation begins.
Standby The drive for protecting the motor is switched off if the internal controller magnitude
drops below the limit set in P06.05 longer than three seconds. The controller magni-
tude is set to the lower value corresponding to P12.12. It continues to report outwards
that feeding is in progress.
The controller does not function and the I component of the flow rate controller is de-
leted or stays stored depending upon P12.18.
Measurement remains active.
It switches to normal operation if the internal controller magnitude exceeds the limits
set in P06.05.
Gravimetric operating mode The actual flow rate value is set to the effective setpoint through the material feeder.
Volumetric operating mode Only the setpoint bypass and rise act as a controller magnitude. The feeder is con-
trolled proportional to the setpoint. The I component of the controller is deleted regard-
less of the P12.18 while the setpoint filters continue to run.
Volumetrically synchronous In contrast to volumetric operation, switching synchronously from gravimetric to volu-
operation type metric makes it possible to switch over from the gravimetric operating mode without a
bump by including the current controller output value.
Simulation The control circuit is closed internally in simulation operation. The measured values Q
and n are also simulated (Q=Qnominal, n = nominal speed).
The simulated value is shown as the flow rate. The controller magnitude Y is propor-
tional to the setpoint and is 10 mA specifying the nominal setpoint.
Operating modes, switching sources on/off and setpoint sources function as usual in
simulation operation.
The task: testing the plant, especially the control processes. Learning operation.
The characteristics in the The components stored in the controller are set to zero when selectively switching off
'Prefeeder – Stop' mode the feeder just as when switching off feeding. However, totalizing continues to functi-
on.
Tab. 21 : Characteristics in special operational states

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 137 -
Appendix

Monitoring control deviation


The control deviation is displayed and monitored in gravimetric operation only.
The display, but not the monitoring system input, is filtered by parameter P12.16.
Event message 'P12.04' will be triggered if the value of the error signal Xd exceeds the limit value S1 for a
duration defined in parameter Event: Deviation. Monitoring will restart if the error signal falls below the
threshold during this time.
At the same time, the control deviation value is filtered (filter time in parameter P12.04) and the filter output
is monitored. Event 'Event: Deviation' will be identified if the filter output exceeds the threshold value S2.
Threshold values S1 and S2 can be adapted to the current feed rate setpoint by means of the following
formulas:
S1 = P12.05 * [P12.06 + (1 - P12.06) * Feed rate setpoint / P02.02]
S2 = P12.08 * [P12.06 + (1 - P12.06) * Feed rate setpoint / P02.02]
The following diagram illustrates the relationship using with examples for threshold value S1.

P Feed rate setpoint V Limit value S1 or S2


LIM Limit Value in P12.05 or. P12.08 F Influence Factor P12.06

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 138 - Schenck Process Group
Appendix

8.6.2 Step controller


The controller functions as a three-point switch to moving position-controlled flow gates OPEN and
CLOSED and feed gates, etc. The controller model is switched on via P12.01 = Stepping and is only availa-
ble for feeding systems (P01.05 = YES).

Fig. 27: The simplified signal flow diagram of the stepping controller

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 139 -
Appendix

Parameters Effect

P12.24 The proportional component (P component) of the stepping controller.


The reference quantity is the nominal flow rate in P02.02
P12.25 Readjusting time
This is the time when the same controller magnitude change is caused by the I component as by
the P component.
P12.26 The trigger threshold in % of P02.02
The trigger threshold should be greater than the smallest possible step of the actuator.
The feeder stands still if the control deviation is smaller than the trigger threshold.
P12.27 The time constant of the compensation element
The compensation element contains an additional integrator (refer to constant controller) to bal-
ance out contouring errors dependant upon bin levels. The compensation element only functions
in gravimetric operation.
The compensation element is ineffective at P12.27 = 0.
Tab. 22 : The control parameters for the step controller

Value Meaning

Network ON Delete all elements to be stored


(the controller and compensation integrator)
Scale OFF The 'feeder ON' contact is reset and all elements to be stored are
deleted.
Scales ON The scale begins to work until the elapse of the start-up period in
volumetric operation.
Afterwards, it switches over to gravimetric regulation.
Volumetric operation Switch M to 'vol/start-up'
The feeder is set to a position proportional to the setpoint. The
compensation integrator is deleted and becomes ineffective.
Gravimetric operation Switch M to 'grav.' (drawn position).
The actual flow rate value is set to the effective setpoint through the
position of the feeder.
The compensation integrator is active.
Tab. 23 : Switching and operational states

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 140 - Schenck Process Group
Appendix

The internal structure of the step controller

Fig. 28: The feed gate control logic

The EXTERNAL part is not a component of the machine. It only shows a proposal for producing "local circui-
try" for connecting up to a model FAE8202 power unit.

Drawing elements Meaning

Switch menu The operating elements of the control unit or in EasyServe


Min The limit switch for the MIN feeder position
Max The limit switch for the MAX feeder position
Tab. 24 : Some signals of the control logic

The 'Open', 'Stop' and 'Closed' switch positions are only available with manual control of the feeder.
The Min and Max limit switches keep the limit positions of the feeder from being overrun.

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 141 -
Appendix

18.7 Linearization
Before adjusting linearization, it is necessary to calibrate the measuring equipment with linearization
(P13.01 = NO) switched off. Then call up the tare function without bulk solids after keying in the relevant
parameters. Afterwards, it is necessary to make an initial measurement with bulk solids at a feed rate as
high as possible to check the proportionality factor P04.01 Weight Correction between the measurement
and feed rate (and readjust wherever necessary).
Linearization should be carried out at k (k < 5) measuring points with differing flow rates I(k) in the flow rate
zone relevant to production. We recommend distributing the points I(k) with equal spaces over the relevant
zone. There is an additional point at flow rate = zero that is automatically adjusted by taring without a flow of
bulk solids. The curve is continued at a constant gradient above the highest point. This is why the two high-
est points should be sufficiently far apart from another to correctly define the gradient.
Furthermore, the points in both axes have to be rising monotonically.

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 142 - Schenck Process Group
Index

Index
>0 Zero ON/OFF ............................................................................................................................................................. 57
2. Password ..................................................................................................................................................................... 56
Abbreviations ................................................................................................................................................................... 44
About This Manual ............................................................................................................................................................. 1
Access Rights Limitation FB............................................................................................................................................. 92
acknowledge event information ........................................................................................................................................ 19
Activation code ............................................................................................................................................................... 128
Adaptation Factor ............................................................................................................................................................. 69
Adaptation Time ............................................................................................................................................................... 69
Additional device ............................................................................................................................................................ 102
Address ................................................................................................................................................................ 90, 91, 92
Afterflow Totalizer ............................................................................................................................................................ 66
AI Offset ........................................................................................................................................................................ 100
AI Position Flow Gate .................................................................................................................................................... 100
AI Range ....................................................................................................................................................................... 100
An overview of the INTECONT Tersus............................................................................................................................... 7
Analog Outputs ................................................................................................................................................................ 62
AO Actual Flow Rate ....................................................................................................................................................... 63
AO Actual Flow Rate (2nd).............................................................................................................................................. 63
AO Load .......................................................................................................................................................................... 63
AO Motor Speed Control ................................................................................................................................................. 64
AO Offset ...................................................................................................................................................................... 100
AO Position Flow Gate .................................................................................................................................................. 100
AO Range ..................................................................................................................................................................... 100
AO Setpoint ..................................................................................................................................................................... 62
Appendix ........................................................................................................................................................................ 127
Auto Zero Active ............................................................................................................................................................... 66
AUTO Zero Set .................................................................................................................................................... 66, 67, 68
Automatic control ............................................................................................................................................................... 9
Basic Tare ........................................................................................................................................................................ 61
Batch Automatic Record................................................................................................................................................... 70
Batch control .................................................................................................................................................................... 57
Batch Mode ...................................................................................................................................................................... 68
Batch Setpoint Source...................................................................................................................................................... 69
Batch Tolerance ............................................................................................................................................................... 69
Batching ........................................................................................................................................................................... 10
Batching functions ............................................................................................................................................................ 35
Batching mode ................................................................................................................................................................. 35
Baud rate.................................................................................................................................................................... 90, 92
Baud Rate ........................................................................................................................................................................ 87
Bypass ............................................................................................................................................................................. 79
Byte Sequence ................................................................................................................................................................. 90
CA01 Event Error LC Input........................................................................................................................................... 105
CA05 Event Linearization Error .................................................................................................................................... 105
CA06 Event Tare Correction ........................................................................................................................................ 105
CA12 Event Tare Difference > MAX............................................................................................................................. 105
Calibrat. Results ......................................................................................................................................................... 61, 62
Calibration ...................................................................................................................................................................... 105
Calibration Data ......................................................................................................................................................... 60, 61
Calibration functions ......................................................................................................................................................... 27
calibration switch ............................................................................................................................................................ 127
Calibration Switch .......................................................................................................................................................... 127
Calibration Time ............................................................................................................................................................... 61
Calibration Weight ............................................................................................................................................................ 61
call up the zeroing program .............................................................................................................................................. 19
Characteristics ................................................................................................................................................................. 11
Check in Keyboard Mode ................................................................................................................................................. 89
Check with bulk solids ...................................................................................................................................................... 41
CO01 Event Controller Limited ..................................................................................................................................... 106
CO02 Event MIN Flow Gate ......................................................................................................................................... 106
CO03 Event MAX Flow Gate........................................................................................................................................ 106
Communication EasyServe .............................................................................................................................................. 87
Communication Fieldbus .................................................................................................................................................. 88

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 143 -
Index

Compatibility DISOCONT Master ..................................................................................................................................... 89


Compatiblity INTECONT .................................................................................................................................................. 91
Compensation Element .................................................................................................................................................... 81
Configuration .................................................................................................................................................................... 90
Configuration HMI Values ................................................................................................................................................ 98
Configuring Event Messages ........................................................................................................................................... 45
Connection Diagrams ..................................................................................................................................................... 114
Constant controller ......................................................................................................................................................... 134
Control.............................................................................................................................................................................. 55
Control operating modes .................................................................................................................................................. 10
Controller........................................................................................................................................................................ 106
Controller Magnitude Offset ............................................................................................................................................. 77
Controller Type................................................................................................................................................................. 74
Correction Amount ........................................................................................................................................................... 68
Counter 1 Unit .................................................................................................................................................................. 59
Counter 2 Unit .................................................................................................................................................................. 59
Counter 3 Unit .................................................................................................................................................................. 59
Counter functions ............................................................................................................................................................. 23
Daily Total Time ............................................................................................................................................................... 96
Damaged / Defective Electrical Components ..................................................................................................................... 6
DATA................................................................................................................................................................................ 16
Data Format ..................................................................................................................................................................... 91
Data Log ON/OFF ............................................................................................................................................................ 57
Data Log Value 1 ............................................................................................................................................................. 96
Data Log Value 10 ........................................................................................................................................................... 97
Data Log Value 2 ............................................................................................................................................................. 96
Data Log Value 3 ............................................................................................................................................................. 97
Data Log Value 4 ............................................................................................................................................................. 97
Data Log Value 5 ............................................................................................................................................................. 97
Data Log Value 6 ............................................................................................................................................................. 97
Data Log Value 7 ............................................................................................................................................................. 97
Data Log Value 8 ............................................................................................................................................................. 97
Data Log Value 9 ............................................................................................................................................................. 97
Data Logging .................................................................................................................................................................... 96
DELETE ........................................................................................................................................................................... 16
Deviation abs. max........................................................................................................................................................... 76
Device Constant ............................................................................................................................................................... 61
DeviceNet Module (VCB8020) ....................................................................................................................................... 121
DI Acknowledge Events .................................................................................................................................................. 83
DI Batch Terminate ......................................................................................................................................................... 83
DI External Event 1 ......................................................................................................................................................... 83
DI External Event 2 ......................................................................................................................................................... 84
DI Reset Totalizer 1 ........................................................................................................................................................ 84
DI Reset Totalizer 2 ........................................................................................................................................................ 84
DI Start ............................................................................................................................................................................ 83
DI Volumetric Mode ......................................................................................................................................................... 84
DI Volumetric synchron ................................................................................................................................................... 84
Dialog Behaviour .............................................................................................................................................................. 54
Digital Inputs .................................................................................................................................................................... 83
Digital Outputs.................................................................................................................................................................. 85
Display Test and Version Number.................................................................................................................................... 21
DO Actual Flow Rate MAX .............................................................................................................................................. 85
DO Actual Flow Rate MIN ............................................................................................................................................... 85
DO Agitator ON ............................................................................................................................................................. 102
DO ALARM ..................................................................................................................................................................... 85
DO Batch Running .......................................................................................................................................................... 86
DO Deviation ................................................................................................................................................................... 86
DO Dribble Feed ............................................................................................................................................................. 86
DO Full Feed ................................................................................................................................................................... 86
DO Keyboard Mode ........................................................................................................................................................ 86
DO Pulse Counter ........................................................................................................................................................... 60
DO Scale Start ................................................................................................................................................................ 85
DO Start Prefeeder ......................................................................................................................................................... 85
DO Volumetric Mode ....................................................................................................................................................... 86
duty cycle ....................................................................................................................................................................... 127
Electrical System............................................................................................................................................................ 106

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 144 - Schenck Process Group
Index

ENTER ............................................................................................................................................................................. 17
Enter setpoint ................................................................................................................................................................... 20
ESCAPE........................................................................................................................................................................... 17
Ethernet............................................................................................................................................................................ 95
Ethernet/IP ..................................................................................................................................................................... 128
Event Actual Flow Rate MAX .................................................................................................................................. 65, 107
Event Actual Flow Rate MIN ................................................................................................................................... 64, 108
Event Acyclic Communication ................................................................................................................................. 89, 110
Event Controller Limited .......................................................................................................................................... 76, 106
Event Cyclic Communication................................................................................................................................... 89, 110
Event Deviation ....................................................................................................................................................... 76, 108
Event Error LC Input ............................................................................................................................................... 72, 105
Event External Event 1 ............................................................................................................................................ 73, 109
Event External Event 2 ............................................................................................................................................ 73, 109
Event LC Input < MIN .............................................................................................................................................. 73, 108
Event LC Input > MAX............................................................................................................................................. 72, 107
Event License Violation ........................................................................................................................................... 74, 110
Event Linearization Error ......................................................................................................................................... 82, 105
Event Maint. Electric................................................................................................................................................ 70, 109
Event Maint.Feeder Run ......................................................................................................................................... 71, 109
Event MAX Flow Gate ........................................................................................................................................... 101, 106
Event Memory ......................................................................................................................................................... 71, 110
Event MIN Flow Gate ............................................................................................................................................ 101, 106
Event Out of Tolerance ........................................................................................................................................... 69, 107
Event Power Failure ................................................................................................................................................ 71, 106
Event Run Disabled ................................................................................................................................................ 72, 107
Event Setpoint Limited ............................................................................................................................................ 73, 109
Event Simulation active ........................................................................................................................................... 73, 110
Event Stand-By ....................................................................................................................................................... 65, 109
Event Tare Correction ............................................................................................................................................. 67, 105
Event Tare Difference > MAX.................................................................................................................................. 67, 105
Event Group: Calibration ................................................................................................................................................ 105
Event Group: Controller.................................................................................................................................................. 106
Event Group: Electrical System ...................................................................................................................................... 106
Event Group: Interlock.................................................................................................................................................... 107
Event Group: Material Flow ............................................................................................................................................ 107
Event Group: MAX ......................................................................................................................................................... 107
Event Group: MIN .......................................................................................................................................................... 108
Event Group: Sequence Monitoring ............................................................................................................................... 109
Event Group: System Message ...................................................................................................................................... 110
Event messages ............................................................................................................................................................. 103
Events ............................................................................................................................................................................ 105
Events ............................................................................................................................................................ 71, 72, 73, 74
Events Details ................................................................................................................................................................ 105
Factor Deviation ............................................................................................................................................................... 75
Feeder ON/OFF ............................................................................................................................................................... 56
Feeder Start ..................................................................................................................................................................... 58
Feedrate Setpoint............................................................................................................................................................. 58
Fig. 1: Basic diagram of the ITE inputs and outputs ........................................................................................................... 8
Fig. 10: Connection diagram for voltage supply ............................................................................................................. 114
Fig. 11: LC connection diagram and tachometer............................................................................................................ 114
Fig. 12: Connection diagram for inputs and outputs 1 .................................................................................................... 114
Fig. 13: Connection diagram for inputs and outputs 2 .................................................................................................... 114
Fig. 14: Serial interface connection diagram .................................................................................................................. 115
Fig. 15: Modbus connection diagram ............................................................................................................................. 115
Fig. 16: PROFIBUS connection diagram ........................................................................................................................ 115
Fig. 17: DeviceNet connection diagram.......................................................................................................................... 116
Fig. 18: VPB8020 PROFIBUS module layout................................................................................................................. 119
Fig. 19: Light-emitting diodes – VPB8020 front view ...................................................................................................... 120
Fig. 2: The MULTISTREAM measuring principle ............................................................................................................... 9
Fig. 20: VCB8020 DeviceNet module layout .................................................................................................................. 121
Fig. 21: VCB8020:XC1 DeviceNet module front view .................................................................................................... 122
Fig. 22: VSS8020 Modbus module layout drawing......................................................................................................... 123
Fig. 23: The setting value and turn-on sources .............................................................................................................. 130
Fig. 24: VWF switch-on sequence .................................................................................................................................. 131
Fig. 25: A simplified signal flow diagram ........................................................................................................................ 132

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 145 -
Index

Fig. 26: A simplified signal flow diagram ........................................................................................................................ 134


Fig. 27: The simplified signal flow diagram of the stepping controller ............................................................................ 139
Fig. 28: The feed gate control logic ................................................................................................................................ 141
Fig. 3: Feeding ................................................................................................................................................................. 10
Fig. 4: Display - Warning 2 ............................................................................................................................................... 12
Fig. 5: Display - Warning 1 ............................................................................................................................................... 12
Fig. 6: Display - Alarm ...................................................................................................................................................... 12
Fig. 7: Display – function distributor ................................................................................................................................. 18
Fig. 8: Arrangement for verification with bulk material ...................................................................................................... 41
Fig. 9: Parameter sets ...................................................................................................................................................... 43
Filter Actual Flow Rate .................................................................................................................................................... 65
Filter Actual Flow Rate analog ........................................................................................................................................ 66
Filter Deviation ................................................................................................................................................................ 78
Filter Load ....................................................................................................................................................................... 66
Filters ............................................................................................................................................................................... 65
Five Safety Rules of Electrical Engineering........................................................................................................................ 6
Fixed mode configuration ................................................................................................................................................. 93
FLOAT-Format ................................................................................................................................................................. 91
Flow Gate ......................................................................................................................................................................... 99
Flow Rate Offset .............................................................................................................................................................. 63
Flow Rate Range ............................................................................................................................................................. 63
Flow rate regulation ........................................................................................................................................................ 133
Flow Rate Units ................................................................................................................................................................ 58
Font .................................................................................................................................................................................. 55
Format Data ..................................................................................................................................................................... 87
FUNCTION....................................................................................................................................................................... 16
Function block .................................................................................................................................................................. 17
Function Check ................................................................................................................................................................ 39
function distributor ............................................................................................................................................................ 19
Functional mode................................................................................................................................................................. 9
Gateway ........................................................................................................................................................................... 96
General Diagram ................................................................................................................................................................ 7
Gravimetric Mode ............................................................................................................................................................. 10
Hardware and technical data.......................................................................................................................................... 111
HI01 Event LC Input > MAX ......................................................................................................................................... 107
HI02 Event Actual Flow Rate MAX ............................................................................................................................... 107
HI05 Event Deviation.................................................................................................................................................... 108
HMI Value 01 ................................................................................................................................................................... 98
HMI Value 02 ................................................................................................................................................................... 98
HMI Value 03 ................................................................................................................................................................... 98
HMI Value 04 ................................................................................................................................................................... 98
HMI Value 05 ................................................................................................................................................................... 98
HMI Value 06 ................................................................................................................................................................... 98
HMI Value 07 ................................................................................................................................................................... 99
HMI Value 08 ................................................................................................................................................................... 99
HMI Value 09 ................................................................................................................................................................... 99
HMI Value 10 ................................................................................................................................................................... 99
Hourly Total Time ............................................................................................................................................................. 96
I-Component TN............................................................................................................................................................... 74
ID Preset Value 1 ............................................................................................................................................................. 93
ID Preset Value 2 ............................................................................................................................................................. 93
ID Preset Value 3 ............................................................................................................................................................. 93
ID Preset Value 4 ............................................................................................................................................................. 93
ID Preset Value 5 ............................................................................................................................................................. 94
ID Preset Value 6 ............................................................................................................................................................. 94
ID Preset Value 7 ............................................................................................................................................................. 94
ID Preset Value 8 ............................................................................................................................................................. 94
ID Read Value 1 ............................................................................................................................................................... 94
ID Read Value 2 ............................................................................................................................................................... 94
ID Read Value 3 ............................................................................................................................................................... 94
ID Read Value 4 ............................................................................................................................................................... 94
ID Read Value 5 ............................................................................................................................................................... 95
ID Read Value 6 ............................................................................................................................................................... 95
ID Read Value 7 ............................................................................................................................................................... 95
ID Read Value 8 ............................................................................................................................................................... 95
Identifier format ................................................................................................................................................................ 92

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 146 - Schenck Process Group
Index

IL01 Event Run Disabled.............................................................................................................................................. 107


Interlock.......................................................................................................................................................................... 107
IP Address........................................................................................................................................................................ 95
Keyboard operation ON/OFF ........................................................................................................................................... 26
KP Adaptation .................................................................................................................................................................. 80
Language ......................................................................................................................................................................... 54
LC Characteristic Value.................................................................................................................................................... 60
LC Filter............................................................................................................................................................................ 66
LC Rated Capacity ........................................................................................................................................................... 61
LED diagnosis ................................................................................................................................................................ 124
Limit Actual Flow Rate MAX ............................................................................................................................................ 64
Limit Actual Flow Rate MIN ............................................................................................................................................. 64
Limit Values...................................................................................................................................................................... 64
Linearization ................................................................................................................................................................... 142
Linearization ..................................................................................................................................................................... 81
Linearization I1 ................................................................................................................................................................. 81
Linearization I2 ................................................................................................................................................................. 82
Linearization I3 ................................................................................................................................................................. 82
Linearization I4 ................................................................................................................................................................. 82
Linearization ON .............................................................................................................................................................. 81
Linearization S1 ............................................................................................................................................................... 81
Linearization S2 ............................................................................................................................................................... 82
Linearization S3 ............................................................................................................................................................... 82
Linearization S4 ............................................................................................................................................................... 82
LO01 Event LC Input < MIN ......................................................................................................................................... 108
LO02 Event Actual Flow Rate MIN ............................................................................................................................... 108
Load Offset....................................................................................................................................................................... 63
Load Range...................................................................................................................................................................... 64
Logger cycle time ............................................................................................................................................................. 96
Lower Limit ....................................................................................................................................................................... 77
Maintenance Electric ........................................................................................................................................................ 70
Maintenance Feeder Run ................................................................................................................................................. 71
Maintenance interval ........................................................................................................................................................ 70
Material Correction ........................................................................................................................................................... 62
Material Flow .................................................................................................................................................................. 107
MAX ............................................................................................................................................................................... 107
Mean Limit Value ............................................................................................................................................................. 67
Measuring principle ............................................................................................................................................................ 9
Measuring the flow rate .................................................................................................................................................. 132
MF06 Event Out of Tolerance ...................................................................................................................................... 107
MIN................................................................................................................................................................................. 108
Modbus Interface VSS8020 ........................................................................................................................................... 123
Mode functions ................................................................................................................................................................. 25
MULTISTREAM block circuit diagram ................................................................................................................................ 8
Net Mask .......................................................................................................................................................................... 95
Nominal Flow Rate ........................................................................................................................................................... 58
Operating in Normal Operation ........................................................................................................................................ 18
operating sources ............................................................................................................................................................. 26
Operation ......................................................................................................................................................................... 15
Output current ................................................................................................................................................................ 127
Own Address.................................................................................................................................................................... 87
P01 - Dialog Behaviour .................................................................................................................................................... 54
P01.01 - Language ........................................................................................................................................................... 54
P01.02 - Userdefined Text ............................................................................................................................................... 54
P01.03 - Font ................................................................................................................................................................... 55
P01.04 - Units .................................................................................................................................................................. 55
P01.05 - Control ............................................................................................................................................................... 55
P01.06 - Scale Name ....................................................................................................................................................... 55
P01.07 - Password ........................................................................................................................................................... 55
P01.08 - 2. Password ....................................................................................................................................................... 56
P01.09 - Switch Grav./Vol. command .............................................................................................................................. 56
P01.10 - Feeder ON/OFF ................................................................................................................................................. 56
P01.11 - Switch Keyboard-/Normal Mode ........................................................................................................................ 56
P01.12 - Batch control ...................................................................................................................................................... 57
P01.13 - >0 Zero ON/OFF............................................................................................................................................... 57
P01.14 - Reset Counter 1................................................................................................................................................. 57

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 147 -
Index

P01.15 - Reset Counter 2................................................................................................................................................. 57


P01.16 - Data Log ON/OFF.............................................................................................................................................. 57
P02 - Rated Data ................................................................................................................................................. 58, 59, 60
P02.01 - Flow Rate Units ................................................................................................................................................. 58
P02.02 - Nominal Flow Rate ............................................................................................................................................ 58
P02.03 - Feeder Start ....................................................................................................................................................... 58
P02.04 - Feedrate Setpoint .............................................................................................................................................. 58
P02.05 - Counter 1 Unit.................................................................................................................................................... 59
P02.06 - Pulse Length Total ............................................................................................................................................. 59
P02.07 - Counter 2 Unit.................................................................................................................................................... 59
P02.08 - Counter 3 Unit.................................................................................................................................................... 59
P02.09 - Relative Setpoint................................................................................................................................................ 60
P02.10 - DO Pulse Counter............................................................................................................................................. 60
P02.11 - Totalizer Increment ............................................................................................................................................ 60
P02.12 - Z1-Numberstep .................................................................................................................................................. 60
P03 - Calibration Data ................................................................................................................................................ 60, 61
P03.01 - LC Characteristic Value ..................................................................................................................................... 60
P03.02 - Device Constant ................................................................................................................................................ 61
P03.03 - LC Rated Capacity............................................................................................................................................. 61
P03.04 - Calibration Weight ............................................................................................................................................. 61
P03.05 - Calibration Time................................................................................................................................................. 61
P04 - Calibrat. Results ............................................................................................................................................... 61, 62
P04.01 - Weight Correction .............................................................................................................................................. 61
P04.02 - Total Tare .......................................................................................................................................................... 61
P04.03 - Basic Tare ......................................................................................................................................................... 61
P04.04 - Tare Correction .................................................................................................................................................. 62
P04.05 - Material Correction ............................................................................................................................................ 62
P05 - Analog Outputs ....................................................................................................................................................... 62
P05.01 - AO Setpoint ...................................................................................................................................................... 62
P05.02 - Setpoint Offset ................................................................................................................................................... 62
P05.03 - Setpoint Range .................................................................................................................................................. 62
P05.04 - AO Actual Flow Rate ........................................................................................................................................ 63
P05.05 - Flow Rate Offset ................................................................................................................................................ 63
P05.06 - Flow Rate Range ............................................................................................................................................... 63
P05.07 - AO Actual Flow Rate (2nd) ............................................................................................................................... 63
P05.08 - AO Load ........................................................................................................................................................... 63
P05.09 - Load Offset ........................................................................................................................................................ 63
P05.10 - Load Range ....................................................................................................................................................... 64
P05.11 - AO Motor Speed Control .................................................................................................................................. 64
P06 - Limit Values ............................................................................................................................................................ 64
P06.01 - Limit Actual Flow Rate MIN .............................................................................................................................. 64
P06.02 - Event Actual Flow Rate MIN ............................................................................................................................. 64
P06.03 - Limit Actual Flow Rate MAX ............................................................................................................................. 64
P06.04 - Event Actual Flow Rate MAX ............................................................................................................................ 65
P06.05 - Stand-By Limit Value ......................................................................................................................................... 65
P06.06 - Event Stand-By ................................................................................................................................................. 65
P07 - Filters ...................................................................................................................................................................... 65
P07.01 - Filter Actual Flow Rate ...................................................................................................................................... 65
P07.02 - Filter Actual Flow Rate analog .......................................................................................................................... 66
P07.03 - Filter Load ......................................................................................................................................................... 66
P07.04 - LC Filter ............................................................................................................................................................. 66
P07.05 - Afterflow Totalizer .............................................................................................................................................. 66
P08 - AUTO Zero Set ........................................................................................................................................... 66, 67, 68
P08.01 - Auto Zero Active ................................................................................................................................................ 66
P08.02 - Mean Limit Value ............................................................................................................................................... 67
P08.03 - Zeroing Limit ...................................................................................................................................................... 67
P08.04 - Event Tare Correction ....................................................................................................................................... 67
P08.05 - Zero Set Difference............................................................................................................................................ 67
P08.06 - Event Tare Difference > MAX ........................................................................................................................... 67
P08.07 - Zero Drop-Out Active ......................................................................................................................................... 68
P08.08 - Zero Drop-Out Limit ........................................................................................................................................... 68
P09 - Batch Mode ............................................................................................................................................................ 68
P09.01 - Correction Amount ............................................................................................................................................. 68
P09.02 - Adaptation Factor .............................................................................................................................................. 69
P09.03 - Adaptation Time................................................................................................................................................. 69
P09.04 - Batch Tolerance................................................................................................................................................. 69

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 148 - Schenck Process Group
Index

P09.05 - Event Out of Tolerance ..................................................................................................................................... 69


P09.06 - Batch Setpoint Source ....................................................................................................................................... 69
P09.07 - Batch Automatic Record .................................................................................................................................... 70
P09.08 - Reset print FMZ 1 .............................................................................................................................................. 70
P09.09 - Reset print FMZ 2 .............................................................................................................................................. 70
P10 - Maintenance interval............................................................................................................................................... 70
P10.01 - Maintenance Electric ......................................................................................................................................... 70
P10.02 - Event Maint. Electric ......................................................................................................................................... 70
P10.03 - Maintenance Feeder Run .................................................................................................................................. 71
P10.04 - Event Maint.Feeder Run ................................................................................................................................... 71
P11 - Events................................................................................................................................................... 71, 72, 73, 74
P11.01 - Event Power Failure ......................................................................................................................................... 71
P11.02 - Event Memory................................................................................................................................................... 71
P11.03 - Event Error LC Input ......................................................................................................................................... 72
P11.04 - Event Run Disabled .......................................................................................................................................... 72
P11.05 - Event LC Input > MAX ...................................................................................................................................... 72
P11.06 - Event LC Input < MIN ....................................................................................................................................... 73
P11.07 - Event Simulation active .................................................................................................................................... 73
P11.08 - Event Setpoint Limited ...................................................................................................................................... 73
P11.09 - Event External Event 1 ..................................................................................................................................... 73
P11.10 - Event External Event 2 ..................................................................................................................................... 73
P11.11 - Event License Violation .................................................................................................................................... 74
P12 - Rate controller .............................................................................................................. 74, 75, 76, 77, 78, 79, 80, 81
P12.01 - Controller Type .................................................................................................................................................. 74
P12.02 - P-Component KP ............................................................................................................................................... 74
P12.03 - I-Component TN ................................................................................................................................................ 74
P12.04 - Time Deviation ................................................................................................................................................... 75
P12.05 - Threshold Deviation ........................................................................................................................................... 75
P12.06 - Factor Deviation................................................................................................................................................. 75
P12.07 - Event Deviation................................................................................................................................................. 76
P12.08 - Deviation abs. max. ........................................................................................................................................... 76
P12.09 - Event Controller Limited ................................................................................................................................... 76
P12.10 - Lower Limit ........................................................................................................................................................ 77
P12.11 - Upper Limit ........................................................................................................................................................ 77
P12.12 - Controller Magnitude Offset ............................................................................................................................... 77
P12.13 - Position at STOP ............................................................................................................................................... 77
P12.14 - Volumetric Start-Up ........................................................................................................................................... 78
P12.15 - Setpoint Offset ................................................................................................................................................... 78
P12.16 - Filter Deviation .................................................................................................................................................. 78
P12.17 - Setpoint Range .................................................................................................................................................. 78
P12.18 - Store .................................................................................................................................................................. 78
P12.19 - Bypass ............................................................................................................................................................... 79
P12.20 - Setpoint Filter 1st Ord ........................................................................................................................................ 79
P12.21 - Setpoint Filter 2nd Ord ....................................................................................................................................... 79
P12.22 - KP Adaptation .................................................................................................................................................... 80
P12.23 - Setpoint Threshold............................................................................................................................................. 80
P12.24 - S P-Component ................................................................................................................................................ 80
P12.25 - S I-Component.................................................................................................................................................. 80
P12.26 - S Threshold Response ..................................................................................................................................... 80
P12.27 - Compensation Element ..................................................................................................................................... 81
P13 - Linearization ........................................................................................................................................................... 81
P13.01 - Linearization ON ................................................................................................................................................ 81
P13.02 - Linearization S1 ................................................................................................................................................. 81
P13.03 - Linearization I1 .................................................................................................................................................. 81
P13.04 - Linearization S2 ................................................................................................................................................. 82
P13.05 - Linearization I2 .................................................................................................................................................. 82
P13.06 - Linearization S3 ................................................................................................................................................. 82
P13.07 - Linearization I3 .................................................................................................................................................. 82
P13.08 - Linearization S4 ................................................................................................................................................. 82
P13.09 - Linearization I4 .................................................................................................................................................. 82
P13.10 - Event Linearization Error .................................................................................................................................. 82
P14 - Digital Inputs ........................................................................................................................................................... 83
P14.01 - Source Run Enable............................................................................................................................................ 83
P14.02 - DI Batch Terminate ........................................................................................................................................... 83
P14.03 - DI Acknowledge Events .................................................................................................................................... 83
P14.04 - DI Start ............................................................................................................................................................. 83

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 149 -
Index

P14.05 - DI External Event 1 ........................................................................................................................................... 83


P14.06 - DI External Event 2 ........................................................................................................................................... 84
P14.07 - DI Reset Totalizer 1 .......................................................................................................................................... 84
P14.08 - DI Reset Totalizer 2 .......................................................................................................................................... 84
P14.09 - DI Volumetric Mode .......................................................................................................................................... 84
P14.10 - DI Volumetric synchron ..................................................................................................................................... 84
P15 - Digital Outputs ........................................................................................................................................................ 85
P15.01 - DO ALARM ....................................................................................................................................................... 85
P15.02 - DO Start Prefeeder ........................................................................................................................................... 85
P15.03 - DO Scale Start .................................................................................................................................................. 85
P15.04 - DO Actual Flow Rate MIN ................................................................................................................................. 85
P15.05 - DO Actual Flow Rate MAX ............................................................................................................................... 85
P15.06 - DO Batch Running ............................................................................................................................................ 86
P15.07 - DO Full Feed .................................................................................................................................................... 86
P15.08 - DO Dribble Feed ............................................................................................................................................... 86
P15.09 - DO Keyboard Mode .......................................................................................................................................... 86
P15.10 - DO Volumetric Mode ........................................................................................................................................ 86
P15.11 - DO Deviation .................................................................................................................................................... 86
P16 - Communication EasyServe .................................................................................................................................... 87
P16.01 - Own Address ..................................................................................................................................................... 87
P16.02 - Baud Rate .......................................................................................................................................................... 87
P16.03 - Format Data ....................................................................................................................................................... 87
P17 - Communication Fieldbus ........................................................................................................................................ 88
P17.01 - Protocol Type..................................................................................................................................................... 88
P17.02 - Timeout Host ..................................................................................................................................................... 88
P17.03 - Event Cyclic Communication ............................................................................................................................ 89
P17.04 - Event Acyclic Communication........................................................................................................................... 89
P17.05 - Check in Keyboard Mode .................................................................................................................................. 89
P17.06 - Compatibility DISOCONT Master ...................................................................................................................... 89
P17.07 - Word Sequence ................................................................................................................................................. 89
P17.08 - Byte Sequence .................................................................................................................................................. 90
P17.09 - Configuration ..................................................................................................................................................... 90
P17.10 - Address ............................................................................................................................................................. 90
P17.11 - Resolution .......................................................................................................................................................... 90
P17.12 - Baud rate ........................................................................................................................................................... 90
P17.13 - Data Format ....................................................................................................................................................... 91
P17.14 - Physics .............................................................................................................................................................. 91
P17.15 - Address ............................................................................................................................................................. 91
P17.16 - FLOAT-Format................................................................................................................................................... 91
P17.17 - Compatiblity INTECONT .................................................................................................................................... 91
P17.18 - Identifier format .................................................................................................................................................. 92
P17.19 - PA32 compatible................................................................................................................................................ 92
P17.20 - Address ............................................................................................................................................................. 92
P17.21 - Baud rate ........................................................................................................................................................... 92
P17.22 - Access Rights Limitation FB .............................................................................................................................. 92
P17.23 - Remote IP Address FB ...................................................................................................................................... 93
P18 - Fixed mode configuration ....................................................................................................................................... 93
P18.01 - ID Preset Value 1............................................................................................................................................... 93
P18.02 - ID Preset Value 2............................................................................................................................................... 93
P18.03 - ID Preset Value 3............................................................................................................................................... 93
P18.04 - ID Preset Value 4............................................................................................................................................... 93
P18.05 - ID Preset Value 5............................................................................................................................................... 94
P18.06 - ID Preset Value 6............................................................................................................................................... 94
P18.07 - ID Preset Value 7............................................................................................................................................... 94
P18.08 - ID Preset Value 8............................................................................................................................................... 94
P18.09 - ID Read Value 1 ................................................................................................................................................ 94
P18.10 - ID Read Value 2 ................................................................................................................................................ 94
P18.11 - ID Read Value 3 ................................................................................................................................................ 94
P18.12 - ID Read Value 4 ................................................................................................................................................ 94
P18.13 - ID Read Value 5 ................................................................................................................................................ 95
P18.14 - ID Read Value 6 ................................................................................................................................................ 95
P18.15 - ID Read Value 7 ................................................................................................................................................ 95
P18.16 - ID Read Value 8 ................................................................................................................................................ 95
P19 - Ethernet .................................................................................................................................................................. 95
P19.01 - IP Address ......................................................................................................................................................... 95
P19.02 - Net Mask ........................................................................................................................................................... 95

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 150 - Schenck Process Group
Index

P19.03 - Gateway ............................................................................................................................................................ 96


P20 - Data Logging .......................................................................................................................................................... 96
P20.01 - Hourly Total Time .............................................................................................................................................. 96
P20.02 - Daily Total Time ................................................................................................................................................. 96
P20.03 - Logger cycle time............................................................................................................................................... 96
P20.04 - Data Log Value 1 ............................................................................................................................................... 96
P20.05 - Data Log Value 2 ............................................................................................................................................... 96
P20.06 - Data Log Value 3 ............................................................................................................................................... 97
P20.07 - Data Log Value 4 ............................................................................................................................................... 97
P20.08 - Data Log Value 5 ............................................................................................................................................... 97
P20.09 - Data Log Value 6 ............................................................................................................................................... 97
P20.10 - Data Log Value 7 ............................................................................................................................................... 97
P20.11 - Data Log Value 8 ............................................................................................................................................... 97
P20.12 - Data Log Value 9 ............................................................................................................................................... 97
P20.13 - Data Log Value 10 ............................................................................................................................................. 97
P21 - Configuration HMI Values ....................................................................................................................................... 98
P21.01 - HMI Value 01 ..................................................................................................................................................... 98
P21.02 - HMI Value 02 ..................................................................................................................................................... 98
P21.03 - HMI Value 03 ..................................................................................................................................................... 98
P21.04 - HMI Value 04 ..................................................................................................................................................... 98
P21.05 - HMI Value 05 ..................................................................................................................................................... 98
P21.06 - HMI Value 06 ..................................................................................................................................................... 98
P21.07 - HMI Value 07 ..................................................................................................................................................... 99
P21.08 - HMI Value 08 ..................................................................................................................................................... 99
P21.09 - HMI Value 09 ..................................................................................................................................................... 99
P21.10 - HMI Value 10 ..................................................................................................................................................... 99
P22 - Flow Gate ............................................................................................................................................................... 99
P22.01 - S DO Open Flow Gate ...................................................................................................................................... 99
P22.02 - S DO Close Flow Gate ..................................................................................................................................... 99
P22.03 - AI Position Flow Gate ..................................................................................................................................... 100
P22.04 - AI Offset.......................................................................................................................................................... 100
P22.05 - AI Range ......................................................................................................................................................... 100
P22.06 - AO Position Flow Gate ................................................................................................................................... 100
P22.07 - AO Offset ........................................................................................................................................................ 100
P22.08 - AO Range ....................................................................................................................................................... 100
P22.09 - Event MIN Flow Gate ...................................................................................................................................... 101
P22.10 - Position MIN Flow Gate ................................................................................................................................... 101
P22.11 - Event MAX Flow Gate .................................................................................................................................... 101
P22.12 - Position MAX Flow Gate .................................................................................................................................. 101
P23 - Additional device................................................................................................................................................... 102
P23.01 - DO Agitator ON............................................................................................................................................... 102
P23.02 - START Agitator................................................................................................................................................ 102
PA32 compatible .............................................................................................................................................................. 92
Parameter Block 01 - Dialog Behaviour ........................................................................................................................... 54
Parameter Block 02 - Rated Data .................................................................................................................................... 58
Parameter Block 03 - Calibration Data ............................................................................................................................. 60
Parameter Block 04 - Calibrat. Results ............................................................................................................................ 61
Parameter Block 05 - Analog Outputs .............................................................................................................................. 62
Parameter Block 06 - Limit Values ................................................................................................................................... 64
Parameter Block 07 - Filters ............................................................................................................................................. 65
Parameter Block 08 - AUTO Zero Set .............................................................................................................................. 66
Parameter Block 09 - Batch Mode ................................................................................................................................... 68
Parameter Block 10 - Maintenance interval...................................................................................................................... 70
Parameter Block 11 - Events............................................................................................................................................ 71
Parameter Block 12 - Rate controller ............................................................................................................................... 74
Parameter Block 13 - Linearization .................................................................................................................................. 81
Parameter Block 14 - Digital Inputs .................................................................................................................................. 83
Parameter Block 15 - Digital Outputs ............................................................................................................................... 85
Parameter Block 16 - Communication EasyServe ........................................................................................................... 87
Parameter Block 17 - Communication Fieldbus ............................................................................................................... 88
Parameter Block 18 - Fixed mode configuration .............................................................................................................. 93
Parameter Block 19 - Ethernet ......................................................................................................................................... 95
Parameter Block 20 - Data Logging ................................................................................................................................. 96
Parameter Block 21 - Configuration HMI Values .............................................................................................................. 98
Parameter Block 22 - Flow Gate ...................................................................................................................................... 99
Parameter Block 23 - Additional device.......................................................................................................................... 102

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 151 -
Index

Parameter Details ............................................................................................................................................................ 54


Parameter functions ......................................................................................................................................................... 31
Parameter Input ............................................................................................................................................................... 39
Parameter Listing ............................................................................................................................................................. 45
Parameter Overview ........................................................................................................................................................ 45
Parameters....................................................................................................................................................................... 43
Password ......................................................................................................................................................................... 55
P-Component KP ............................................................................................................................................................. 74
Physics ............................................................................................................................................................................. 91
Position at STOP.............................................................................................................................................................. 77
Position MAX Flow Gate ................................................................................................................................................ 101
Position MIN Flow Gate.................................................................................................................................................. 101
Prefeeder ......................................................................................................................................................................... 26
Printer functions ............................................................................................................................................................... 33
PROFIBUS Module (VPB8020)...................................................................................................................................... 119
Protocol Type ................................................................................................................................................................... 88
Pulse Length Total ........................................................................................................................................................... 59
Quick guide ...................................................................................................................................................................... 15
Rate controller ........................................................................................................................ 74, 75, 76, 77, 78, 79, 80, 81
Rated Data ........................................................................................................................................................... 58, 59, 60
Read Parameters ............................................................................................................................................................. 31
Record the batch .............................................................................................................................................................. 37
regulated .......................................................................................................................................................................... 10
Relative Setpoint .............................................................................................................................................................. 60
Remote IP Address FB..................................................................................................................................................... 93
Replacing INTECONT PLUS with INTECONT Tersus ................................................................................................... 116
Reset Counter 1 ............................................................................................................................................................... 57
Reset Counter 2 ............................................................................................................................................................... 57
Reset print FMZ 1 ............................................................................................................................................................ 70
Reset print FMZ 2 ............................................................................................................................................................ 70
Reset the totalizing counter .............................................................................................................................................. 19
Resolution ........................................................................................................................................................................ 90
S DO Close Flow Gate .................................................................................................................................................... 99
S DO Open Flow Gate .................................................................................................................................................... 99
S I-Component ................................................................................................................................................................ 80
S P-Component............................................................................................................................................................... 80
S Threshold Response .................................................................................................................................................... 80
Safety notes ....................................................................................................................................................................... 3
SC01 Event Setpoint Limited ....................................................................................................................................... 109
SC02 Event Stand-By .................................................................................................................................................. 109
SC03 Event Maint.Feeder Run .................................................................................................................................... 109
SC04 Event Maint. Electric........................................................................................................................................... 109
SC05 Event External Event 1 ....................................................................................................................................... 109
SC06 Event External Event 2 ....................................................................................................................................... 109
Scale Name...................................................................................................................................................................... 55
SCROLL ........................................................................................................................................................................... 16
Sequence Monitoring ..................................................................................................................................................... 109
Serial number of the CPU board .................................................................................................................................... 126
Service Functions ............................................................................................................................................................. 21
Service Values ............................................................................................................................................................... 127
Set option ....................................................................................................................................................................... 128
Setpoint Filter 1st Ord ...................................................................................................................................................... 79
Setpoint Filter 2nd Ord ..................................................................................................................................................... 79
Setpoint Offset ........................................................................................................................................................... 62, 78
Setpoint Range .......................................................................................................................................................... 62, 78
Setpoint Threshold ........................................................................................................................................................... 80
Setting the Time ............................................................................................................................................................... 30
Signal Words ...................................................................................................................................................................... 4
Signal Words for Application Notes .................................................................................................................................... 5
Signal Words for Safety Warnings ..................................................................................................................................... 4
Simulation ........................................................................................................................................................................ 26
software identification ..................................................................................................................................................... 127
Software version .................................................................................................................................................... 126, 127
Source Run Enable .......................................................................................................................................................... 83
Sources of setpoints and switch signals ......................................................................................................................... 130
Stand-By Limit Value ........................................................................................................................................................ 65

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 152 - Schenck Process Group
Index

START Agitator .............................................................................................................................................................. 102


START/STOP................................................................................................................................................................... 16
Starting the calibration functions ...................................................................................................................................... 27
Startup operation .............................................................................................................................................................. 39
Status Report ................................................................................................................................................................... 33
Step controller ................................................................................................................................................................ 139
Store................................................................................................................................................................................. 78
Switch Grav./Vol. command ............................................................................................................................................. 56
Switch Keyboard-/Normal Mode ....................................................................................................................................... 56
Switching on ..................................................................................................................................................................... 18
SY01 Event Memory .................................................................................................................................................... 110
SY08 Event Cyclic Communication .............................................................................................................................. 110
SY09 Event License Violation ...................................................................................................................................... 110
SY10 Event Acyclic Communication ............................................................................................................................ 110
SY14 Event Simulation active ...................................................................................................................................... 110
System Information ........................................................................................................................................................ 126
System Message ............................................................................................................................................................ 110
Tab.1: Using parameter sets ............................................................................................................................................ 43
Tab.10: LED 'Module Status' (below) ............................................................................................................................. 122
Tab.11: Modbus module properties................................................................................................................................ 123
Tab.12: Modbus serial interface pin assignment ............................................................................................................ 123
Tab.13: Function calls on the controller website ............................................................................................................ 125
Tab.14: The states and points in time in the flow chart .................................................................................................. 131
Tab.15: Relevant parameters ......................................................................................................................................... 132
Tab.16: Relevant parameters ......................................................................................................................................... 133
Tab.17: Controller models and how they are used ......................................................................................................... 133
Tab.18: Relevant parameters ......................................................................................................................................... 135
Tab.19: Special cases for KP and TN parameters ......................................................................................................... 136
Tab.2: Abbreviations frequently used in parameters ........................................................................................................ 44
Tab.20: Set-up notes for parameters in the constant controller...................................................................................... 136
Tab.21: Characteristics in special operational states ..................................................................................................... 137
Tab.22: The control parameters for the step controller .................................................................................................. 140
Tab.23: Switching and operational states....................................................................................................................... 140
Tab.24: Some signals of the control logic....................................................................................................................... 141
Tab.3: Event classes ........................................................................................................................................................ 45
Tab.4: Event groups ....................................................................................................................................................... 103
Tab.5: 'Bus activation' connector.................................................................................................................................... 120
Tab.6: LED 'Operating Mode' (below) ............................................................................................................................ 120
Tab.7: LED 'Status' (above) ........................................................................................................................................... 120
Tab.8: 'Bus activation' connector.................................................................................................................................... 121
Tab.9: LED 'Network Status' (above) ............................................................................................................................. 122
Tare Correction ................................................................................................................................................................ 62
Tare TW ........................................................................................................................................................................... 28
Technical Data and Replacement Parts ......................................................................................................................... 111
Test Connector............................................................................................................................................................... 129
Test With Calibration Weight ............................................................................................................................................ 40
Threshold Deviation ......................................................................................................................................................... 75
Time Deviation ................................................................................................................................................................. 75
Timeout Host .................................................................................................................................................................... 88
Total Tare ......................................................................................................................................................................... 61
Totalizer Increment .......................................................................................................................................................... 60
Turn off ............................................................................................................................................................................. 18
Types of operation ........................................................................................................................................................... 25
Units ................................................................................................................................................................................. 55
unregulated ...................................................................................................................................................................... 10
Upper Limit ....................................................................................................................................................................... 77
Userdefined Text .............................................................................................................................................................. 54
Volumetric Mode .............................................................................................................................................................. 10
Volumetric Start-Up .......................................................................................................................................................... 78
Volumetric Synchronous Mode ........................................................................................................................................ 10
WE01 Event Power Failure .......................................................................................................................................... 106
Web Server .................................................................................................................................................................... 125
Web server functions...................................................................................................................................................... 125
Weight Check CW ............................................................................................................................................................ 29
Weight Correction ............................................................................................................................................................ 61
Word Sequence ............................................................................................................................................................... 89

INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual BV-H2478GB, 1249
Schenck Process Group - 153 -
Index

Z1-Numberstep ................................................................................................................................................................ 60
Zero Drop-Out Active ....................................................................................................................................................... 68
Zero Drop-Out Limit ......................................................................................................................................................... 68
Zero Set Difference .......................................................................................................................................................... 67
Zeroing Limit .................................................................................................................................................................... 67

BV-H2478GB, 1249 INTECONT® Tersus MULTISTREAM solids flow feeder, Instruction Manual
- 154 - Schenck Process Group

You might also like