Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

ZXCAB DS04(V2.

0R88M30)
Cabinet Product Description
ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

ZXCAB DS04 ( V2.0R88M30 ) Cabinet Product


Description
Version Date Author Reviewer Notes

V1.0 2021/1/18 Huo Wenquan Wu Donghui Not open to the third party

© 2023 ZTE Corporation. All rights reserved.

ZTE CONFIDENTIAL: This document contains proprietary information of ZTE and is not to be disclosed or used
without the prior written permission of ZTE.

Due to update and improvement of ZTE products and technologies, information in this document is subjected to
change without notice.

ZTE Confidential & Proprietary 1


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

目录

1 Product Overview ............................................................................................................ 4

1.1 General Introduction ....................................................................................................... 4

2 Product Highlight ............................................................................................................ 4

3 Product Configuration .................................................................................................... 5

3.1 Unit Configuration .......................................................................................................... 5

3.2 Corrosion Resistant Performance................................................................................... 5

4 Product Technical Description ....................................................................................... 6

4.1 System Technical Specification ...................................................................................... 6

4.2 Aircon & Smog Sensor Interlock Function ...................................................................... 8

4.3 Air-con Disturbance Switching ........................................................................................ 8

5 Declaration ...................................................................................................................... 8

2 ZTE Confidential & Proprietary


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

FIGURES
Fig. 1-1 Schematic diagram of the cabinet with DC air conditioners ................................... 4

TABLES

Table 3-1 Unit configuration table....................................................................................... 5

Table 3-2 Different types of environmental condition for cabinet ........................................ 5

Table 4-1 System technical specification............................................................................ 6

ZTE Confidential & Proprietary 3


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

1 Product Overview

1.1 General Introduction

This power cabinet is designed for the placement of 21” equipment. The cabinet is
applied for outdoor applications and provides a suitable environment for communication
equipment. The temperature control equipment used in this project is 3000W DC air
conditioner with 1+1 backup. The 1+1 backup ensures the equipment work more
properly and reliably. This power cabinet is easy to install and maintain. Also it has a
variety of features for outdoor applications, such as dust-proof, waterproof, heat
insulation, anti-theft, moisture proof, mildew proof, and corrosion proof.

Fig. 1-1 Schematic diagram of the cabinet with DC air conditioners

2 Product Highlight
 Standardized cabinets with compact structure, saving footprint.

4 ZTE Confidential & Proprietary


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

 DC air-conditioners with 1+1 backup.

 Professional anti-theft design.

 Better ingress protection.

 Easy to maintain.

 Wide application.

3 Product Configuration

3.1 Unit Configuration

Table 3-1 Unit configuration table

Item Description Cooling Equipment

This cabinet is applied for the 3000W DC air-conditioner with


Power Cabinet
placement of 21” instruments 1+1 backup

3.2 Corrosion Resistant Performance

This power cabinet can satisfy general outdoor environment in table 3-2. And harsh
outdoor environment can be satisfied by custom designed.

Table 3-2 Different types of environmental condition for cabinet

Environment environment
SN. Places as examples
Code condition

general outdoor 1)Outside of cabinet which is more than 14km


1 4C2/4K3
environment far away from coastline;

ZTE Confidential & Proprietary 5


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

1)Outside of cabinet which is less than 14km


far away from coastline, or on sea island, or on
the sea, or on the vessel;

2 ) Outside of cabinet which is near to


harsh outdoor
2 4C3/4K3 large-sized factories and mines with heavy
environment
pollutant, such as chemical factory, oil refinery,
or areas with frequent acid rain;

3)Outside of cabinet which is of high humidity


environment for a long time.

Note:Environment Code refers to GB/T4798.3 and GB/T4798.4,which is equal to


IEC60721-3-3, IEC60721-3-4 and IEC 60950-22.

4 Product Technical Description

4.1 System Technical Specification

Table 4-1 System technical specification

Classification Item Description

Product type Power Cabinet


System
Cooling equipment 3000w DC air conditioner(1+1)
information
Input DC48V

Cabinet dimension(mm) 700W*700D*2000H

Single-compartment, none
Compartment
partition, PEF insulation

Mechanical Maximum net weight (kg) ≤350

parameters Cabinet color PANTONECOOL GRAY 2C

Wiring method Cabinet bottom.

Lock Anti-theft three point

Internal rack Standard 21" (535 mm) telecom

6 ZTE Confidential & Proprietary


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

Classification Item Description


Equipment

Base frame height 120mm

Design life 10 years


Others
IP IP55

Operation temperature -10℃ ~ +55℃

Storage temperature -40℃ ~ +70℃


Environment 10%~90%(40%~60%
Relative humidity
recommended)

Air pressure 80kPa~106kPa

Table 4-2 System technical specification

Item Description

Wall plate 45mm(1mm SGCC + PEF + 1mm SGCC)

Dimension H×W×D(mm): 2000×700×700

Door 1 front and 1 rare doors


2*3000w@L35/L35 (In/Out), the total heat rate of the equipment
in the compartment should less than 3000w@L35/L35.
The heat dissipation shall be less than
 2500W@L35/L40;
 1950W@L35/L50;
Air conditioner
 1650W@L35/L55;
 2200W@L40/L50;
 1950W@L40/L55;
Other working condition shall be estimated according to the
actual situation.
Distribution DC power for telecom equipment, aircons, and light.
DCPD
Main and standby output only for telecom equipment.
Smoke, flood alarm, open door alarm, high temperature alarm,
Monitor Unit
aircon failure Alarm. And dry contacts output for alarms.

ZTE Confidential & Proprietary 7


ZXCAB DS04 (V2.0R88M30)Cabinet Product Description

4.2 Aircon & Smog Sensor Interlock Function

When the smoke sensor detects the smog, it sends the alarm signal to cabinet air-cons.
As soon as the air-cons receive smog alarm signal, immediately they stop working.

4.3 Air-con Disturbance Switching

 When one air conditioner has a problem, the other will start immediately.

 If one of aircon is out of work, it does not switch to the other one until time switch is
finished. If the fault is not cleared, the other will work all the time.

 Default setting: When temperature in cabinet is higher than 35 centigrade, single


aircon will start while it reaches 40 centigrade double aircon will work together.
Alarm will be sent to monitoring center when temperature reaches 45 centigrade
send alarm.

5 Declaration
 When the Air-con alarm signal is detected, the professional maintenance engineer
must immediately arrive and take action to diagnose and solve the problem.

 This type of cabinet shall be at least 14km off the shore to avoid corrosion caused
by the salt fog. Site on the island or near the shore shall use special solution.

8 ZTE Confidential & Proprietary