Professional Documents
Culture Documents
408 N.MAIN - FIRE SERVICE-Fire Service Plan
408 N.MAIN - FIRE SERVICE-Fire Service Plan
408 N.MAIN - FIRE SERVICE-Fire Service Plan
A. PRIOR TO INSTALLATION, REQUIRED PERMITS SHALL BE SECURED FROM THE FIRE DEPARTMENT.
idropdesign@gmail.com
1. THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACKFLOW IN ACCORDANCE WITH
HEALTH & SAFETY CODE SECTION 13114.7. THE LOCATION AND TYPE OF CONTROL DEVICES SHALL
iDROPDESIGN
C. APPROVED FIRE DEPARTMENT CONNECTIONS (FDC) SHALL BE LOCATED WITHIN 150’ OF A PUBLIC FIRE
HYDRANT. THE FDC SHALL BE ORIENTED TO FACE THE FIRE DEPARTMENT ACCESS ROAD. THE FDC SHALL
BE PROPERLY SUPPORTED AND SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE. FIRE
DEPARTMENT INLET CONNECTIONS SHALL BE PAINTED OSHA SAFETY RED.
D. FDCS SHALL BE ON THE ADDRESS SIDE OF THE BUILDING AND LOCATED IMMEDIATELY ADJACENT TO THE
APPROVED FIRE DEPARTMENT ACCESS ROAD. THE FDC SHALL BE IN A POSITION ALLOWING HOSE LINES
TO BE READILY AND CONVENIENTLY ATTACHED. THE FDC SHALL CONTAIN A MINIMUM OF TWO 2½” INLETS.
SITES CONTAINING PUBLIC OR PRIVATE HYDRANTS SHALL HAVE FDCS WITH A MINIMUM OF FOUR 2 ½”
INLETS.
E. EVERY SPRINKLER RISER SHALL HAVE A SEPARATE CONNECTION FROM THE PRIVATE FIRE MAIN.
F. PRIVATE FIRE HYDRANTS SHALL MEET CITY OF CORONA WATER STANDARD 412, WITH A MINIMUM OF ONE
2 ½” AND ONE 4” OUTLET. ALL OUTLETS SHALL BE PROVIDED WITH NATIONAL STANDARD THREADS (NST).
ALL FIRE HYDRANTS SHALL BE INSTALLED ON A 6” RISER. 4” OUTLET(S) SHALL FACE TOWARD THE FIRE
DEPARTMENT ACCESS ROADS FIRE HYDRANTS SHALL BE LOCATED A MINIMUM OF 40’ FROM ALL
H. ALL PIPE SHALL BE APPROVED FOR USE IN “FIRE SERVICE SYSTEMS”, CLASS 150 MINIMUM. CLASS 200
SHALL BE PROVIDED WHERE THE PRESSURE EXCEEDS 150 POUNDS PER SQUARE INCH (PSI). ALL
FERROUS METAL PIPE SHALL BE LINED. ALL FERROUS PIPE AND FITTINGS SHALL BE PROTECTED WITH A
LOOSE 8-MIL POLYETHYLENE TUBE. THE ENDS OF THE TUBES SHALL BE SEALED WITH 2” TAPE APPROVED
FOR UNDERGROUND USE. ALL BOLTED JOINT ACCESSORIES SHALL BE CLEANED AND THOROUGHLY
COATED WITH ASPHALT OF OTHER CORROSION RETARDING MATERIAL AFTER ASSEMBLY AND PRIOR TO
POLY-TUBE INSTALLATION
I. A SIX-INCH BED OF CLEAN FILL SAND SHALL BE PROVIDED BOTH BELOW AND 12 INCHES ABOVE THE PIPE
(TOTAL OF 18” PLUS OUTER DIAMETER OF THE PIPING).
J. PIPE SHALL BE CENTER LOADED WITH CLEAN SAND TO PREVENT UPLIFT DURING HYDROSTATIC TEST. ALL
JOINTS SHALL REMAIN EXPOSED.
K. A MINIMUM OF 30” OF COVER FROM FINISHED GRADE TO TOP OF PIPE SHALL BE PROVIDED ABOVE THE
PIPE. WHEN SURFACE LOADS ARE EXPECTED, A MINIMUM OF 36” OF COVER SHALL BE PROVIDED.
L. LISTED AND APPROVED PIPING SHALL BE INSTALLED UNDER THE BUILDING FOOTINGS. ADEQUATE
CLEARANCE SHALL BE PROVIDED OVER PIPE THAT RUNS UNDER FOOTINGS TO PREVENT DAMAGE FROM
BUILDING SETTLING. A MINIMUM OF 2” CLEARANCE (INTERSTITIAL SPACE) SHALL BE PROVIDED WHERE
PIPE PASSES THROUGH THE FLOOR OR WALL. UNDERGROUND PIPING SERVING FIRE SPRINKLER RISERS
SHALL TERMINATE WITHIN 18” OF AN EXTERIOR WALL AND 6” ABOVE FINISHED FLOOR.
M
NOTE: UNDERGROUND PIPING SERVING FIRE SPRINKLERS SHALL NOT TERMINATE 5’ FROM THE BUILDING.
HARRISON \STREET
M. THRUST BLOCKS OR OTHER APPROVED METHOD OF THRUST RESTRAINT SHALL BE PROVIDED WHEREVER
PIPE CHANGES DIRECTION.
THE TRENCH SHALL BE EXCAVATED FOR THRUST BLOCKS AND INSPECTED PRIOR BEING
COVERED. ALL CORROSION PROTECTION SHALL BE IN PLACE. CARE SHALL BE TAKEN WHEN
FORMING AND POURING THRUST BLOCKS THAT FITTINGS AND JOINTS ARE NOT BURIED IN CONCRETE.
PROPOSED BUILDING C. A HYDROSTATIC TEST (200 PSI PRESSURE FOR 2 HOURS OR 50 PSI OVER THE MAXIMUM STATIC
408 N. MAIN ST. PRESSURE WHEN IT IS OVER 150 PSI) SHALL BE WITNESSED BY AN INSPECTOR BEFORE BACKFILL
ARCHITECT:
AND SOIL COMPACTION. THE TRENCH SHALL BE BACKFILLED BETWEEN JOINTS BEFORE TESTING TO
ADDRESS:
ADDRESS:
PREVENT MOVEMENT OF PIPE.
CLIENT:
PHONE:
PHONE:
D. THE SYSTEM SHALL BE CONNECTED TO THE CITY MAIN AND FLUSHED THOROUGHLY PRIOR TO
CONNECTION TO THE OVERHEAD SYSTEM. FLOW RATE SHALL BE A MINIMUM OF 10 FT./SEC.
THROUGH NOT LESS THAN 4 INCH PIPE OR HOSE. APPROVED EQUIPMENT SHALL BE PROVIDED
BY THE CONTRACTOR, TO ENSURE SAFETY. THE FLUSH SHALL BE WITNESSED BY AN INSPECTOR.
E. PRIVATE FIRE HYDRANTS, SPRINKLER CONTROL VALVES, DETECTOR CHECK ASSEMBLIES, POST
UNDERGROUND FIRE SERVICE GENERAL NOTES INDICATOR VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL BE PAINTED OSHA SAFETY
RED.
INSTALLATION OF UNDERGROUND FIRE SERVICE SHALL STRICTLY CONFORM TO 2013 NFPA 24 AND THE REQUIREMENTS OF THE CITY OF CORONA
FIRE DEPARTMENT, INCLUDING TO THE FOLLOWING: F. ALL CONTROL VALVES SHALL BE PROVIDED WITH PERMANENT SIGNS THAT CLEARLY INDICATE THE
BUILDING, SYSTEM AND FUNCTION THE VALVE SERVES.
METRO AT MAIN
G. ALL FIRE SPRINKLER SYSTEM CONTROL VALVES (INCLUDING DETECTOR CHECK ASSEMBLIES), THAT
--
4. MINIMUM COVER SHALL BE 3'-0" IN TRAFFIC ZONES AND 2'-6" IN PEDESTRIAN ZONES. DEPTH OF BURY SHALL BE VISUALLY VERIFIED BY THE
FIRE INSPECTION PERSONNEL. UG FIRE SERVICE SCOPE OF WORK
5. FITTINGS SHALL BE UL LISTED CLASS 250 DUCTILE IRON WITH FLANGED OR MECHANICAL JOINT (MJ) ENDS, AS APPLICABLE. FITTINGS SHALL BE
VISIBLE FOR VERIFICATION BY FIRE INSPECTION PERSONNEL. PROVIDE A NEW UNDERGROUND FIRE SERVICE
6. PIPE CONNECTIONS SHALL BE VISUALLY VERIFIED BY FIRE INSPECTION PERSONNEL.
WITH A DCDA BACKFLOW AS PER NFPA 24, 2013
EDITION ND THE CITY OF CORONA WATER
7. PIPE RESTRAINTS (THRUST BLOCKS) SHALL BE PROVIDED AT ALL CHANGES OF DIRECTION AND/OR ELEVATION AND SHALL BE VERIFIED BY DEPARTMENT CONNECTION STANDARDS.
FIRE INSPECTION PERSONNEL.
8. ALL PIPES AND FITTINGS SHALL BE HYDROSTATICALLY TESTED at 200psi FOR 2 HOURS - TO BE WITNESSED BY FIRE INSPECTION PERSONNEL.
9. PRIOR TO CONNECTION TO OVERHEAD FIRE SPRINKLER PIPING, ALL PIPING SHALL BE FLUSHED. FLUSH TO BE WITNESSED BY FIRE
INSPECTION PERSONNEL. CORONA DEPARTMENT of WATER and POWER NOTES
10. PIPE SHALL BE INSTALLED WITH SAND OR EQUIVALENT MATERIAL SURROUNDING PIPE ZONE, AS REQUIRED BY THE AUTHORITY HAVING 1. ARRANGEMENT OF WATER SUPPLY AND DEVICES SHALL STRICTLY CONFORM TO THE REQUIREMENTS OF CITY OF CORONA WATER DEPARTMENT. MAIN STEET SEE SHEET 2 OF 2 FOR DESIGNED BY: A.BLANCO
DRAWN BY: A.BLANCO
JURISDICTION.
2. BACK FLOW PREVENTION DEVICE TO BE DOUBLE CHECK DETECTOR ASSEMBLY WITH 2 0S&Y GATE VALVES. DEVICES SHALL BE U.L. LISTED, AWWA FIRE FLOW REPORT CHECKED BY: PEG
408 N.MAIN - FIRE SERVICE.DWG
11. ALL PIPE AND FITTINGS BELOW GRADE SHALL BE WRAPPED AND/OR COATED AGAINST CORROSION IN ACCORDANCE WITH FIRE & WATER APPROVED FOR FIRE SERVICE INSTALLATIONS AND APPROVED BY THE CROSS-CONNECTION INSTITUTE AT THE UNIVERSITY OF SOUTHERN CALIFORNIA.
DEPARTMENT REQUIREMENTS. PROJECT NUMBER
3. BACK FLOW PREVENTION ASSEMBLY SHALL BE TESTED UPON INSTALLATION BY CERTIFIED BACK FLOW ASSEMBLY TECHNICIAN PRIOR TO ACCEPTANCE
12. ALL PIPE PENETRATING CONCRETE OR MASONRY BUILDING WALLS AND FLOOR SLABS SHALL BE METALLIC (NOT PVC) AND PROVIDED WITH 2" OF BACK FLOW ASSEMBLY BY THE WATER DEPARTMENT. ########
CLEAR SPACE AROUND THE OUTSIDE DIAMETER OF PIPE. HOLES FOR PENETRATIONS SHALL BE SLEEVED OR CORED IN ACCORDANCE WITH
THE REQUIREMENTS OF 2013 NFPA 13, Sect 9.3.4.3. 4. CONTRACTOR SHALL FURNISH VALVE SUPPORT STANDS AS REQUIRED BY THE WATER DEPARTMENT.
DRAWING NO.
13. ALL INDICATING GATE VALVES CONTROLLING FIRE PROTECTION WATER SUPPLIES SHALL BE EQUIPPED WITH TAMPER SWITCHES AND 5. CONCRETE SLAB TO BE MINIMUM 4" THICK AND SLOPED TO DRAIN. PAD ELEVATION TO BE 1" ABOVE FINISH GRADE IN LAWN AREAS AND 2" ABOVE FINISH
CONNECTED TO AN APPROVED CENTRAL ALERT STATION. GRADE IN ALL OTHER AREAS.
1
Filename:
SCALE:
NORTH
SITE PLAN: UNDERGROUND FIRE SERVICE 1" = 10' 1 OF 2